CS-HE9DKE CU-HE9DKE / CS-HE12DKE CU-HE12DKE<br />

9.9. Sleep Timer Operation<br />

• Sleep timer setting with the remote controller makes the unit automatically turn off on the off-set times (0.5, 1, 2, 3, 5 and 7<br />

hours). Remained time shows every one hour on a display of the remote controller. Remained time disappears when time is up.<br />

• In 5- and 7-hour sleep timer settings, “Sleep Shift Control" functions in and after 3 hours.<br />

• Sleep Shift Control in Cooling Operation<br />

− − Indoor fan speed is set to "Lo". (Refer to the “Indoor Fan Control” chapter for each model.)<br />

− − A setting temperature is increased by 1°C.<br />

• Sleep Shift Control in Dry Operation<br />

− − − Indoor fan speed is set to "SLo". (Refer to the “Indoor Fan Control” chapter for each model.)<br />

− − A setting temperature is increased by 1°C.<br />

• Sleep Shift Control in Heating Operation<br />

− − Indoor fan speed is set to "Lo-". (Refer to the “Indoor Fan Control” chapter for each model.)<br />

− − − A setting temperature is decreased by 1°C.<br />

9.10. Timer Operation<br />

On Timer<br />

• • According to air-conditioning load, preliminary operation<br />

is performed to be a set temperature on set time.<br />

Preliminary operation time is as shown in the table on<br />

the right.<br />

• • Indoor and outdoor fans operate for 30 seconds in 70<br />

minutes before a set time, and outdoor and intake air<br />

temperatures are detected.<br />

• • <strong>Air</strong>flow direction in preliminary operation is followed by<br />

remote controller setting. (Same condition as in normal<br />

operation.) Fan speed in preliminary operation is as<br />

shown in the table on the right.<br />

• • In preliminary operation, deicing judgment is performed<br />

after heating operated for 15 minutes in 50 minutes<br />

before set ON-time. This is because it makes start-up<br />

time short when outdoor air temperature is extremely<br />

low in midwinter.<br />

9.11. Auto Restart Control<br />

Preliminary operation in Cooling or Dry operation<br />

Outdoor <strong>Air</strong> Intake <strong>Air</strong> Preliminary Operation<br />

Temperature Temperature<br />

Starting Time<br />

35°C or more — Before 15 min.<br />

— 35°C or more Before 15 min.<br />

30 - 35°C 25 - 30°C Before 10 min.<br />

Below 30°C Below 25°C Before 5 min.<br />

Preliminary operation in Heating operation<br />

Outdoor <strong>Air</strong> Intake <strong>Air</strong> Preliminary Operation<br />

Temperature Temperature<br />

Starting Time<br />

5°C or more — Before 40 min.<br />

— 15 °C or more Before 40 min.<br />

0 - 5°C 5 - 15°C Before 45 min.<br />

Below 0°C Below 5°C Before 50 min.<br />

Fan speed in Preliminary operation<br />

Operation mode Cooling, Cooling<br />

Dry<br />

Heating<br />

Manual speed Selected fan<br />

speed<br />

Selected fan speed<br />

Automatic speed Up to Lo Up to Lo<br />

1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four<br />

minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power<br />

supply resumes.<br />

2. This type of control is not applicable during ON/OFF Timer setting.<br />

32