Applications manual<br />
Diverter Valves:<br />
Straight (part number 1016311) and angled (part number<br />
1016312) diverter valves are available from Buderus for<br />
use in a one pipe system (fi g. 6). Shut offs are located on<br />
the supply and return branches to the radiator, isolating<br />
the radiator from the piping system. This will enable you<br />
to remove the radiator after draining it to do any<br />
maintenance needed to the wall behind it.<br />
Each diverter valve is factory set for 35 % fl ow through<br />
the radiator and 65% through the bypass. Other fl ow<br />
percentages are easily set according to the diagram (fi g.<br />
7). To adjust the bypass, turn the spindle clockwise to the<br />
fully closed position. Then open the bypass spindle the<br />
desired number of turns from the fully closed position.<br />
Refer to the chart that is on page 30, It explains the<br />
pressure drop for a one pipe system with diverter valves<br />
for detailed pressure drop information when using<br />
diverter valves in one pipe systems. You will need to add<br />
pressure drop of radiator and diverter valve together<br />
when sizing circulator<br />
Radiator percentage of flow<br />
Radiator percentage of flow<br />
50<br />
45<br />
40<br />
35<br />
30<br />
50<br />
45<br />
40<br />
35<br />
30<br />
Straight Valve<br />
1 2 3<br />
Factory setting<br />
Number of turns<br />
Angle Valve<br />
¾ 1 1¼ 1½ 1¾<br />
Factory setting<br />
Number of turns<br />
Fig. 2 Setting for Straight and Angled diverter valves<br />
ADJUSTABLE<br />
BYPASS<br />
ADJUSTABLE<br />
BYPASS<br />
<strong>Panel</strong> Radiator<br />
Design Manual<br />
TO RADIATOR FROM RADIATOR<br />
ISOLATION<br />
VALVES<br />
TO RADIATOR FROM RADIATOR<br />
ISOLATION<br />
VALVES<br />
Fig. 3 Straight and Angled Diverter Valves<br />
Installation considerations:<br />
1. The valve mounts directly to the supply and return<br />
of the radiator. The compression fi ttings will now<br />
connect to the diverter valve connections.<br />
2. Allow 5” fl oor clearance below the radiator for the<br />
straight; 4” for the angled diverter valve.<br />
3. Due to its projection towards the mounting wall, the<br />
angle diverter valve cannot be used on the model<br />
#11 radiators unless a small recess is cut into the<br />
wall.<br />
<strong>Panel</strong> Radiator Design Manual | 06.2009 Technical specifi cations are subject to change without prior notice<br />