Applications manual<br />

Diverter Valves:<br />

Straight (part number 1016311) and angled (part number<br />

1016312) diverter valves are available from Buderus for<br />

use in a one pipe system (fi g. 6). Shut offs are located on<br />

the supply and return branches to the radiator, isolating<br />

the radiator from the piping system. This will enable you<br />

to remove the radiator after draining it to do any<br />

maintenance needed to the wall behind it.<br />

Each diverter valve is factory set for 35 % fl ow through<br />

the radiator and 65% through the bypass. Other fl ow<br />

percentages are easily set according to the diagram (fi g.<br />

7). To adjust the bypass, turn the spindle clockwise to the<br />

fully closed position. Then open the bypass spindle the<br />

desired number of turns from the fully closed position.<br />

Refer to the chart that is on page 30, It explains the<br />

pressure drop for a one pipe system with diverter valves<br />

for detailed pressure drop information when using<br />

diverter valves in one pipe systems. You will need to add<br />

pressure drop of radiator and diverter valve together<br />

when sizing circulator<br />

Radiator percentage of flow<br />

Radiator percentage of flow<br />

50<br />

45<br />

40<br />

35<br />

30<br />

50<br />

45<br />

40<br />

35<br />

30<br />

Straight Valve<br />

1 2 3<br />

Factory setting<br />

Number of turns<br />

Angle Valve<br />

¾ 1 1¼ 1½ 1¾<br />

Factory setting<br />

Number of turns<br />

Fig. 2 Setting for Straight and Angled diverter valves<br />

ADJUSTABLE<br />

BYPASS<br />

ADJUSTABLE<br />

BYPASS<br />

<strong>Panel</strong> Radiator<br />

Design Manual<br />

TO RADIATOR FROM RADIATOR<br />

ISOLATION<br />

VALVES<br />

TO RADIATOR FROM RADIATOR<br />

ISOLATION<br />

VALVES<br />

Fig. 3 Straight and Angled Diverter Valves<br />

Installation considerations:<br />

1. The valve mounts directly to the supply and return<br />

of the radiator. The compression fi ttings will now<br />

connect to the diverter valve connections.<br />

2. Allow 5” fl oor clearance below the radiator for the<br />

straight; 4” for the angled diverter valve.<br />

3. Due to its projection towards the mounting wall, the<br />

angle diverter valve cannot be used on the model<br />

#11 radiators unless a small recess is cut into the<br />

wall.<br />

<strong>Panel</strong> Radiator Design Manual | 06.2009 Technical specifi cations are subject to change without prior notice<br />