Performance data (cont)<br />
26<br />
EWT<br />
(F)<br />
65<br />
75<br />
85<br />
GPM<br />
150<br />
188<br />
225<br />
263<br />
150<br />
188<br />
225<br />
263<br />
150<br />
188<br />
225<br />
263<br />
GROSS COOLING CAPACITIES (cont)<br />
<strong>50XJ</strong>E074 WITH (4) 15 HP COMPRESSORS<br />
15,200<br />
AIR ENTERING EVAPORATOR — CFM AT 80 F EDB<br />
19,000<br />
Air Entering Evaporator — Ewb (F)<br />
23,000<br />
77 72 67 62 57 77 72 67 62 57 77 72 67 62 57<br />
BF 0.001 0.051 0.054 0.054 0.095 0.018 0.07 0.071 0.076 0.211 0.052 0.088 0.087 0.106 0.31<br />
TC 952 871 796 729 676 995 912 836 767 726 1024 941 863 795 771<br />
SHC 350 434 515 593 666 367 469 567 664 726 382 501 619 730 771<br />
LDB 60.23 54.81 49.63 44.57 39.87 63.43 58.23 53.18 48.24 44.96 65.77 60.76 55.81 51.09 49.26<br />
LWB 60.23 54.68 49.23 43.87 38.34 63.43 57.93 52.52 47.16 41.36 65.72 60.28 54.91 49.54 43.52<br />
kW 45.33 44.16 43.25 42.42 41.82 46.04 44.77 43.80 42.93 42.41 46.42 45.17 44.10 43.29 43.00<br />
TC 959 876 801 732 679 1002 918 841 771 729 1033 948 869 800 775<br />
SHC 353 437 517 595 667 370 472 570 666 729 385 504 622 733 775<br />
LDB 60.08 54.67 49.51 44.44 39.76 63.31 58.11 53.08 48.14 44.81 65.65 60.65 55.71 51.00 49.10<br />
LWB 60.08 54.54 49.11 43.77 38.25 63.31 57.82 52.41 47.06 41.28 65.60 60.17 54.81 49.45 43.44<br />
kW 43.71 42.68 41.81 41.08 40.54 44.31 43.24 42.31 41.53 41.07 44.75 43.63 42.63 41.84 41.59<br />
TC 963 880 804 734 681 1007 922 844 774 731 1039 953 873 803 778<br />
SHC 354 438 518 596 669 372 473 571 667 731 387 506 623 734 778<br />
LDB 59.99 54.58 49.43 44.37 39.69 63.23 58.04 53.01 48.07 44.72 65.58 60.59 55.65 50.94 49.00<br />
LWB 59.99 54.46 49.03 43.71 38.20 63.23 57.75 52.35 47.00 41.23 65.53 60.11 54.75 49.40 43.39<br />
kW 42.68 41.72 40.90 40.21 39.71 43.27 42.23 41.38 40.64 40.19 43.71 42.61 41.69 40.94 40.69<br />
TC 966 883 806 736 682 1011 925 847 776 733 1043 956 875 805 779<br />
SHC 355 439 519 597 669 373 474 572 668 733 389 507 624 735 779<br />
LDB 59.92 54.52 49.37 44.32 39.64 63.17 57.99 52.96 48.03 44.65 65.53 60.54 55.60 50.89 48.94<br />
LWB 59.92 54.40 48.98 43.66 38.16 63.17 57.70 52.30 46.96 41.20 65.48 60.06 54.71 49.36 43.36<br />
kW 41.98 41.03 40.24 39.59 39.13 42.52 41.54 40.69 40.00 39.57 42.95 41.91 41.00 40.27 40.04<br />
TC 926 848 776 710 659 967 887 812 746 710 995 914 838 774 753<br />
SHC 341 425 505 583 659 358 459 557 653 710 372 491 609 719 753<br />
LDB 60.76 55.36 50.19 45.14 40.27 63.87 58.70 53.66 48.73 45.73 66.15 61.15 56.20 51.53 49.98<br />
LWB 60.76 55.22 49.77 44.41 38.91 63.87 58.39 52.98 47.62 41.75 66.09 60.66 55.29 49.92 43.87<br />
kW 49.86 48.84 47.96 47.23 46.69 50.47 49.37 48.44 47.65 47.25 50.88 49.73 48.76 47.99 47.74<br />
TC 934 854 781 714 664 976 894 818 751 714 1004 922 845 779 757<br />
SHC 343 427 507 585 657 361 462 560 656 714 375 494 611 722 757<br />
LDB 60.60 55.21 50.05 45.02 40.39 63.73 58.56 53.54 48.62 45.56 66.03 61.03 56.10 51.42 49.81<br />
LWB 60.60 55.07 49.64 44.30 38.75 63.73 58.26 52.87 47.52 41.66 65.97 60.55 55.19 49.82 43.79<br />
kW 47.95 46.94 46.21 45.60 45.17 48.55 47.49 46.61 45.97 45.61 48.92 47.84 46.88 46.23 46.03<br />
TC 939 858 784 717 666 981 899 822 754 716 1010 927 849 782 760<br />
SHC 345 429 509 587 658 363 464 562 657 716 377 496 613 724 760<br />
LDB 60.50 55.12 49.97 44.94 40.30 63.64 58.48 53.46 48.54 45.45 65.95 60.96 56.04 51.36 49.70<br />
LWB 60.50 54.98 49.56 44.22 38.68 63.64 58.17 52.79 47.45 41.61 65.89 60.48 55.13 49.76 43.74<br />
kW 46.75 45.86 45.08 44.54 44.18 47.31 46.34 45.52 44.86 44.55 47.67 46.65 45.80 45.10 44.91<br />
TC 942 861 786 719 667 985 902 825 756 718 1015 931 852 785 762<br />
SHC 346 430 510 588 659 364 465 563 658 718 379 498 614 725 762<br />
LDB 60.43 55.05 49.91 44.88 40.24 63.58 58.41 53.40 48.49 45.38 65.89 60.91 55.98 51.31 49.62<br />
LWB 60.43 54.91 49.50 44.16 38.64 63.57 58.11 52.73 47.40 41.57 65.83 60.42 55.08 49.72 43.70<br />
kW 45.90 45.04 44.32 43.78 43.47 46.43 45.51 44.72 44.09 43.78 46.77 45.81 44.98 44.34 44.15<br />
TC 899 823 753 689 642 935 858 786 722 693 962 884 811 750 733<br />
SHC 330 414 494 573 642 347 448 546 641 693 361 480 597 706 733<br />
LDB 61.34 55.98 50.81 45.77 41.30 64.36 59.21 54.19 49.28 46.59 66.56 61.58 56.65 52.03 50.78<br />
LWB 61.34 55.81 50.38 45.02 39.45 64.36 58.89 53.50 48.14 42.19 66.49 61.07 55.72 50.33 44.27<br />
kW 55.54 54.48 53.53 52.76 52.13 56.11 54.96 53.98 53.15 52.83 56.55 55.37 54.37 53.54 53.31<br />
TC 907 830 758 694 645 945 866 793 728 696 972 893 818 755 738<br />
SHC 333 417 497 575 645 350 451 549 644 696 364 483 600 709 738<br />
LDB 61.17 55.81 50.67 45.63 41.09 64.21 59.07 54.05 49.16 46.40 66.43 61.46 56.53 51.91 50.60<br />
LWB 61.17 55.66 50.24 44.89 39.34 64.21 58.75 53.37 48.02 42.09 66.36 60.95 55.61 50.23 44.18<br />
kW 53.29 52.38 51.62 50.97 50.48 53.80 52.81 52.00 51.30 51.02 54.18 53.15 52.28 51.63 51.42<br />
TC 912 834 762 697 647 951 871 797 731 699 979 898 823 759 741<br />
SHC 335 419 499 576 647 352 453 551 646 699 367 485 602 711 741<br />
LDB 61.07 55.71 50.57 45.55 40.96 64.11 58.98 53.97 49.08 46.29 66.35 61.38 56.46 51.84 50.48<br />
LWB 61.07 55.56 50.14 44.81 39.27 64.11 58.67 53.29 47.95 42.03 66.28 60.88 55.54 50.17 44.12<br />
kW 51.85 51.05 50.37 49.81 49.41 52.30 51.44 50.70 50.10 49.85 52.62 51.72 50.97 50.38 50.19<br />
TC 916 837 764 699 649 955 875 800 734 701 984 902 826 762 743<br />
SHC 337 420 500 577 649 354 454 552 647 701 368 487 603 713 743<br />
LDB 60.99 55.64 50.50 45.48 40.86 64.05 58.91 53.91 49.02 46.20 66.29 61.32 56.40 51.78 50.40<br />
LWB 60.99 55.48 50.07 44.75 39.22 64.05 58.60 53.23 47.89 41.99 66.22 60.82 55.49 50.12 44.08<br />
kW 50.79 50.05 49.46 48.98 48.63 51.23 50.42 49.75 49.22 49.01 51.52 50.68 49.98 49.46 49.30<br />
LEGEND<br />
BF — Bypass Factor LDB — Leaving Dry Bulb (F)<br />
EDB — Entering Dry Bulb (F) LWB — Leaving Wet Bulb (F)<br />
EWB — Entering Wet Bulb (F) SHC — Sensible Capacity (1000 Btu/hr)<br />
EWT — Entering Water Temperature (F) TC — Total Capacity (1000 Btu/hr)<br />
kW — Compressor Motor Power Input (kilowatts)