3 - MGV Stromversorgungen GmbH
3 - MGV Stromversorgungen GmbH
3 - MGV Stromversorgungen GmbH
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
INPUT<br />
Input voltages see table<br />
Efficiency 70 - 85%<br />
Fuse 6.3 / 4 / 1.6 / 0.8 A for DG 2<br />
(graduated according to<br />
Vi -1 / -2 / -3 / -4) ranges<br />
OUTPUT<br />
25 / 10 / 6.3 / 3.15 AT for DG 6 and DG 10<br />
Adjustment range ±5%<br />
Operation indicator Green LED for Vo<br />
Ripple < 15 mVpp at DG 2<br />
< 20 mVpp at DG 6 and DG 10<br />
Noise voltage < 50 mVpp typ.<br />
(total of all noise components)<br />
Temperature coefficient ≤ 0.025% / K<br />
Switch on/switch off<br />
performance<br />
No overshooting of Vo (soft start)<br />
Shut down on/off SD TTL-compatible for DG 6 and DG 10<br />
Low = off, high or open = on<br />
(in relation to -Vi)<br />
Run-up time (DG 2)<br />
REGULATION<br />
< 500 ms<br />
Line regulation < 0.1% for Vo at Vi according to table<br />
Load regulation < 0.2% for Vo at Io 0 - 100%<br />
Response time < 1 ms at Io 20 - 80%<br />
PROTECTION AND CONTROLLING<br />
Overvoltage protection Input: > 100% of Vimax<br />
Output: 125% -10, +5%,<br />
automatically repeating<br />
Current limitation<br />
EMC<br />
typ. 110% Inominal<br />
Characteristic line (see diagram)<br />
Interference suppression/ EN 50082-2: 1992<br />
interference immunity EN 61000-4-2 Intensity 4<br />
EN 61000-4-3 Noise level 10 V/m<br />
EN 61000-4-4 Intensity 4<br />
EN 61000-4-5<br />
EN 61000-4-11<br />
Intensity 4<br />
Interference emission EN 50081-1: 1992<br />
EN 55011 / EN 55022 Class B, interference<br />
transmission depends on assembly<br />
Vo/%<br />
100<br />
50<br />
▼<br />
0<br />
0<br />
Current limiting characteristic<br />
110<br />
Io/%<br />
▼<br />
Po/% ▼<br />
100<br />
40<br />
0<br />
0<br />
Derating<br />
DC / DC POWER SUPPLY<br />
WITH GALVANIC INSULATION<br />
SINGLE OUTPUT<br />
DG 2, DG 6, DG 10 SERIES<br />
SAFETY<br />
IEC 950, EN 60950, VDE 0805<br />
Insulation voltage Input / Output 3000 VAC<br />
Output voltages SELV<br />
OPERATING DATA<br />
Temperature range 0...+70°C, at free convection<br />
up to -25°C upon request<br />
Derating 3% / K at +50°C (see diagram)<br />
With DG 6 / 10 input voltages < 10.8 V:<br />
full load at output admissible for max. 3 Min.<br />
otherwise reduction of Io by 10% / V.<br />
Parallel operation For load sharing with DG 6 / 10 connect all<br />
pin 6 as shortly as possible. Connect sense<br />
lines with the load lines directly at the plug.<br />
Weight 0.30 kg for DG 2<br />
0.70 kg for DG 6<br />
1.00 kg for DG 10<br />
Ventilation from bottom to top of the power supply and the<br />
housing-specific heatradiation must not be obstructed when<br />
installing the power supply. In general, kindly refer to the <strong>MGV</strong> user<br />
instructions before use. Ensure fire protection by means of the<br />
surrounding housing system.<br />
MECHANICS<br />
Dimensions 19'' plug-in module according to<br />
DIN 41494 Part 5<br />
Connection Plug connector H 15 / DIN 41612 codable<br />
PIN CONNECTIONS<br />
30 26<br />
DIN<br />
41612H15<br />
PE<br />
32<br />
-Ue<br />
2)<br />
+Ue<br />
22<br />
1)<br />
18<br />
-L<br />
28 24 20 16 12 8 4<br />
+Ue 1) 1) -L +L -F SD<br />
1) internally connected<br />
2) only for DG 6 / DG 10<br />
EXPLANATION<br />
PE Protective conductor<br />
Ue Input<br />
L Load connection<br />
(14 A max. for each contact)<br />
F Sense connection (signal line)<br />
For a safe operating mode of the device, it is mandatory to connect<br />
+L with +F and -L with -F.<br />
Maximum voltage compensation of 0.25 V per line.<br />
50 70<br />
Ta/°C<br />
▼<br />
14<br />
+L<br />
10<br />
+F<br />
6<br />
2)<br />
load<br />
share<br />
08/99