<strong>DNV</strong> Statutory Interpretations, June 2011<br />

Page 24 – SOLAS Ch. II-2: Construction – Fire Protection, Fire Detection and Fire Extinction, FSS Code<br />

— transportable extinguishers (every 5th year).<br />

The service supplier shall be approved according to Rules Pt.1 Ch.1 Sec.1, D200.<br />

1.1.3.4 The foam concentrates of the following systems shall be tested at a service supplier / test laboratory<br />

(typically after 3 years and then annually):<br />

— deck foam system (tankers)<br />

— high expansion and inside air foam systems (protecting engine rooms, enclosed cargos spaces, etc.)<br />

— Additives in water mist systems<br />

— Other systems, for instance foam system for protection of helidecks.<br />

Special requirements apply to protein based, alcohol-resistant foam on chemical tankers, see 1.5.1.3 and Rules<br />

Pt.7 Ch.1 Sec.2, C200.<br />

1.2 General Requirements<br />

1.2.1 All systems<br />

1.2.1.1 The necessary and required operation instructions, marking of main and essential components and<br />

warning signs (for instance gas release) shall be in good and readable condition and available in a relevant<br />

language.<br />

1.2.2 Gas systems<br />

1.2.2.1 The agent cylinders or tanks shall be refilled if the losses for any CO 2 high pressure cylinder exceed<br />

10%. For low pressure CO 2 tanks, Halon cylinders or tanks and other gases the cylinder or tanks shall be<br />

refilled if the losses exceed 5%.<br />

1.2.2.2 Section valves (the term “control valves” is also used by IMO) of fixed gas fire-fighting systems shall<br />

be internally inspected (MSC/Circ.850, 8.2).<br />

1.2.3 Foam concentrates<br />

1.2.3.1 These requirements address foam concentrates used in any system, including those used for fixed fire<br />

fighting in engine room or cargo deck and portable equipment.<br />

1.2.3.2 The content of the foam tank shall in general never be below the defined minimum level as determined<br />

in the approved documentation. It is recommended that this minimum level is indicated on the tank.<br />

1.2.3.3 The requirement for periodic testing of foam concentrates will in general apply to concentrates stored<br />

on tanks provided for fixed fire fighting systems.<br />

Foam in sealed transport containers (for topping up of storage tank or use with portable foam applicators) can<br />

normally be accepted without periodic testing if not more than 10 years old.<br />

Protein based foam concentrate containers shall though be checked on a spot basis if more than 5 years old and<br />

testing or renewal to be required if the condition is not satisfactory. The same applies to non-sealed containers<br />

and containers where production data can not be documented.<br />

1.2.3.4 Topping up of foam tanks shall only be done with a foam concentrate being identical to that already<br />

stored on the tank (same brand and type). If this is not possible a foam concentrate recommended by the maker<br />

of the original foam and case by case approved by the Society may be used.<br />

1.2.3.5 If the foam concentrate is replaced by a new type the following shall be verified:<br />

— the tank shall be emptied and clean properly before refilled with the new foam concentrate<br />

— the foam concentrate shall have the same mixing ration (for instance 1%, 3% or 6%)<br />

— the foam concentrate shall have equivalent approvals (approved as regular, alcohol resistant or multipurpose<br />

foam concentrate, as applicable)<br />

— the new foam concentrate shall have similar viscosity as the previous foam (otherwise new foam pumps<br />

may be needed and foam mixing unit may need adjusted and verified)<br />

— only foam concentrate approved according to MSC.1/Circ.1312 shall be used for tanks refilled after 1st July<br />

2012.<br />

If it is not possible to comply with the requirements the owner shall submit documentation for a case by case<br />

approval by the Society.<br />