Customer Driven • Solution Focused<br />

...we’ve got you covered!<br />

Complete catalog available: www.iewc.com


Index<br />

<strong>Tray</strong> <strong>Cable</strong><br />

Small Diameter Neoprene Control <strong>Cable</strong><br />

18 AWG - 16 AWG<br />

14 AWG - 12 AWG<br />

Vinyl Nylon <strong>Tray</strong> <strong>Cable</strong> (VNTC)<br />

Building Wire<br />

18 AWG - 16 AWG, TFN Conductors<br />

14 AWG - 12 AWG, THHN/THWN Conductors<br />

Power Limited <strong>Tray</strong> <strong>Cable</strong> (PLTC)<br />

22 AWG - 14 AWG, Unshielded<br />

22 AWG - 14 AWG, Shielded<br />

TFFN/THHN<br />

XHHW<br />

Welding <strong>Cable</strong><br />

Stranded Class K (30 AWG stranding)<br />

Flex Stranded Class M (34 AWG stranding)<br />

Welding <strong>Cable</strong> Ampacity Chart<br />

Color Code Charts<br />

ICEA Method 1, Table E1<br />

ICEA Method 1, Table E2<br />

Disclaimer: The values and data shown in this catalog represent typical values intended to distinguish one material from<br />

another and to serve as a guide in selecting the proper material for specific applications or end uses. The information<br />

containted herein is given in good faith, but because of the many variables in subsequent manufacturing and installation<br />

operations, no guarantees can be made for the performance of these products in service. Users are requested to make<br />

their own tests to determine the suitability of these materials for the applications and to be guided by the results of<br />

such tests.<br />

Data and suggestions made in this publication are not to be construed as recommendations to use any product in<br />

violation of existing patents covering any material or its use.<br />

2<br />

Page<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12<br />

13<br />

14<br />

14<br />

15<br />

6, 9<br />

3


Small Diameter Neoprene<br />

Flexible Control <strong>Cable</strong> (SDN )<br />

UL Listed as Type TC <strong>Tray</strong> <strong>Cable</strong>, CSA Type CIC TC<br />

600 Volts, 90°C to - 40°C<br />

Description:<br />

• Soft annealed bare flexible copper.<br />

•<br />

• Thermoplastic rubber insulation, color coded, a .005 min nylon<br />

coating over the flame retardant insulation provides mechanical<br />

protection and slippage between conductors for better flexing.<br />

Meets UL 1277 and IEEE 383 flame test at 70,000 BTU/hr. •<br />

• Jute or nylon fillers are used as required and a mylar binder<br />

holds the conductors together and reduces friction.<br />

•<br />

• Color coded per ICEA method 1 table E2.<br />

UL 600V, 90°C Dry, 75°C Wet<br />

Color Code Chart<br />

Per ICEA Method 1 Table E2<br />

COND.<br />

NO.<br />

COLOR<br />

BASE<br />

SPIRAL<br />

STRIPE<br />

COND.<br />

NO.<br />

COLOR<br />

BASE<br />

Note: Beyond 36 conductors, color code repeats starting at #1.<br />

Application:<br />

Designed for control, power, lighting, telemetering,<br />

signal, relay traffic control, wherever flexible small<br />

diameter cable is required such as cranes, hoists,<br />

and some robotic applications<br />

Recommended for wet or dry locations and outdoors<br />

in cable trays where a sunlight resistant rating is<br />

required.<br />

SPIRAL<br />

STRIPE<br />

COND.<br />

NO.<br />

COLOR<br />

BASE<br />

SPIRAL<br />

STRIPE<br />

1 Black 13 Blue Red 25 Yellow Orange<br />

2 Red - 14 Orange Red 26 Brown Orange<br />

3 Blue - 15 Yellow Red 27 Black Yellow<br />

4 Orange - 16 Brown Red 28 Red Yellow<br />

5 Yellow - 17 Black Blue 29 Blue Yellow<br />

6 Brown - 18 Red Blue 30 Orange Yellow<br />

7 Red Black 19 Orange Blue 31 Brown Yellow<br />

8 Blue Black 20 Yellow Blue 32 Black Brown<br />

9 Orange Black 21 Brown Blue 33 Red Brown<br />

10 Yellow Black 22 Black Orange 34 Blue Brown<br />

11 Brown Black 23 Red Orange 35 Orange Brown<br />

12 Black Red 24 Blue Orange 36 Yellow Brown<br />

See Page 9 for Color Code Chart E1<br />

3<br />

®<br />

To be installed in trays, raceways, troughs, channels,<br />

ducts, conduit and by direct burial.


Small Diameter Neoprene<br />

Control <strong>Cable</strong> (SDN ® )<br />

600 Volts, 90°C to - 40° C, UL Type TC<br />

18 AWG 16/30 Bare Copper<br />

Insulation: .015 Thickness<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART#<br />

NO. OF<br />

COND.<br />

JACKET<br />

THICKNESS<br />

MILS.-NOM.<br />

DIAMETER<br />

INCHES<br />

NOM.<br />

APPROX.<br />

NET WT.<br />

# /1000 FT<br />

SDN1802* 2 45 0.275 46<br />

SDN1803 3 45 0.285 50<br />

SDN1804* 4 45 0.315 60<br />

SDN1805 5 45 0.335 71<br />

SDN1806 6 45 0.360 83<br />

SDN1807* 7 45 0.380 106<br />

SDN1808 8 45 0.420 109<br />

SDN1809* 9 45 0.450 120<br />

SDN1810 10 45 0.450 126<br />

SDN1811* 11 45 0.470 135<br />

SDN1812 12 45 0.465 142<br />

SDN1813* 13 45 0.490 153<br />

SDN1814 14 45 0.485 165<br />

SDN1815* 15 45 0.515 170<br />

SDN1816 16 45 0.510 175<br />

SDN1817* 17 60 0.590 230<br />

SDN1818* 18 60 0.590 230<br />

SDN1819 19 60 0.590 240<br />

SDN1821* 21 60 0.605 270<br />

SDN1824 24 60 0.660 285<br />

SDN1825* 25 60 0.680 300<br />

SDN1830* 30 60 0.695 335<br />

SDN1837* 37 60 0.775 386<br />

* NOT A NORMAL STOCK ITEM<br />

16 AWG 19/29 Bare Copper<br />

Insulation: .015 Thickness<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART#<br />

NO. OF<br />

COND.<br />

JACKET<br />

THICKNESS<br />

MILS.-NOM.<br />

DIAMETER<br />

INCHES<br />

NOM.<br />

CONTACT YOUR SALES REPRESENTATIVE FOR SPECIAL SIZES AND SHIELDED CONSTRUCTIONS<br />

4<br />

SDN1602 2 45 0.290 51<br />

SDN1603 3 45 0.305 62<br />

SDN1604 4 45 0.330 77<br />

SDN1605* 5 45 0.360 92<br />

SDN1606 6 45 0.390 107<br />

SDN1607 7 45 0.420 123<br />

SDN1608 8 45 0.450 137<br />

SDN1609 9 45 0.475 165<br />

SDN1610 10 45 0.485 165<br />

SDN1611* 11 45 0.500 180<br />

SDN1612 12 45 0.500 188<br />

SDN1613* 13 60 0.555 225<br />

SDN1614* 14 60 0.555 240<br />

SDN1615* 15 60 0.585 255<br />

SDN1616 16 60 0.585 258<br />

SDN1617* 17 60 0.635 290<br />

SDN1618* 18 60 0.635 290<br />

SDN1619 19 60 0.635 296<br />

SDN1621* 21 60 0.650 340<br />

SDN1624 24 60 0.715 367<br />

SDN1625* 25 60 0.730 380<br />

SDN1630 30 60 0.750 432<br />

SDN1637 37 80 0.870 556<br />

SDN1660* 60 80 1.045 953<br />

APPROX.<br />

NET WT.<br />

# /1000 FT


Small Diameter Neoprene<br />

Control <strong>Cable</strong> (SDN ® )<br />

600 Volts, 90°C to - 40°C, UL Type TC<br />

14 AWG 19/27 Bare Copper<br />

Insulation: .015 Thickness<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART#<br />

NO. OF<br />

COND.<br />

JACKET<br />

THICKNESS<br />

MILS.-NOM.<br />

DIAMETER<br />

INCHES<br />

NOM.<br />

APPROX.<br />

NET WT.<br />

# /1000 FT<br />

12 AWG 19/25 Bare Copper<br />

Insulation: .015 Thickness<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART#<br />

NO. OF<br />

COND.<br />

JACKET<br />

THICKNESS<br />

MILS.-NOM.<br />

DIAMETER<br />

INCHES<br />

NOM.<br />

SDN1402* 2 45 0.320 78 SDN1202* 2 45 0.360 109<br />

SDN1403 3 45 0.340 84 SDN1203 3 45 0.380 115<br />

SDN1404 4 45 0.370 104 SDN1204 4 45 0.415 146<br />

SDN1405 5 45 0.400 127 SDN1205 5 45 0.450 177<br />

SDN1406 6 45 0.435 147 SDN1206 6 45 0.490 209<br />

SDN1408 8 45 0.505 200 SDN1207* 7 60 0.570 230<br />

SDN1409* 9 60 0.570 235 SDN1208 8 60 0.605 294<br />

SDN1410 10 60 0.580 246 SDN1209* 9 60 0.650 325<br />

SDN1412 12 60 0.595 290 SDN1210 10 60 0.655 350<br />

SDN1413* 13 60 0.625 305 SDN1211* 11 60 0.675 375<br />

SDN1414* 14 60 0.625 325 SDN1212 12 60 0.675 395<br />

SDN1415* 15 60 0.655 340 SDM1213* 13 60 0.700 430<br />

SDN1416 16 60 0.655 354 SDN1214* 14 60 0.720 455<br />

SDN1417* 17 60 0.725 400 SDN1215 15 60 0.730 480<br />

SDN1418* 18 60 0.725 410 SDN1216* 16 60 0.755 505<br />

SDN1419* 19 60 0.725 430 SDN1217* 17 60 0.800 530<br />

SDN1421* 21 60 0.740 470 SDN1218* 18 60 0.800 555<br />

SDN1424* 24 60 0.805 510 SDN1219* 19 80 0.800 605<br />

SDN1425* 25 80 0.875 520 SDN1221* 21 80 0.880 680<br />

SDN1430* 30 80 0.875 660 SDN1224 24 80 0.955 773<br />

SDN1437* 37 80 0.990 785 SDN1225 25 80 0.970 782<br />

* NOT A NORMAL STOCK ITEM<br />

CONTACT YOUR SALES REPRESENTATIVE FOR SPECIAL SIZES AND SHIELDED CONSTRUCTIONS<br />

5<br />

APPROX.<br />

NET WT.<br />

# /1000 FT<br />

SDN1230* 30 80 1.010 1032<br />

SDN1237* 37 80 1.145 1120


<strong>Tray</strong> <strong>Cable</strong> (VNTC)<br />

Multi-conductor, Unshielded<br />

TFN, THWN or THHN Conductors<br />

PVC Jacket, 600 Volts<br />

Description:<br />

● Conductors: Stranded Bare Copper<br />

● Singles Insulation: PVC/Nylon<br />

● Singles Rated: THHN, THWN OR TFN<br />

● Color Code: ICEA Method 1, Table E2<br />

(formerly Table K2) Per ICEA S-73-532<br />

● Conductors: Black PVC<br />

● Rated as UL listed TC 90 C, 75 C wet.<br />

70,000 BTU per IEEE 383 Vertical <strong>Tray</strong><br />

Fire Test<br />

Color Code Chart<br />

Per ICEA Method 1 Table E2<br />

COND.<br />

NO.<br />

COLOR<br />

BASE<br />

SPIRAL<br />

STRIPE<br />

COND.<br />

NO.<br />

Note: Beyond 36 conductors, color code repeats starting at #1.<br />

See Page 3 for Color Code Chart E1<br />

COLOR<br />

BASE<br />

Application:<br />

● For use in power, lighting, control and signal<br />

circuits. These cables may be installed in<br />

wet or dry locations; cable trays, raceways,<br />

open air and conduits. Also suitable for<br />

exposure to weather, direct burial and for<br />

Class I, Div. 2 and Class II, Div. 2 for hazardous<br />

locations per NEC.<br />

6<br />

SPIRAL<br />

STRIPE<br />

COND.<br />

NO.<br />

COLOR<br />

BASE<br />

SPIRAL<br />

STRIPE<br />

1 Black 13 Blue Red 25 Yellow Orange<br />

2 Red - 14 Orange Red 26 Brown Orange<br />

3 Blue - 15 Yellow Red 27 Black Yellow<br />

4 Orange - 16 Brown Red 28 Red Yellow<br />

5 Yellow - 17 Black Blue 29 Blue Yellow<br />

6 Brown - 18 Red Blue 30 Orange Yellow<br />

7 Red Black 19 Orange Blue 31 Brown Yellow<br />

8 Blue Black 20 Yellow Blue 32 Black Brown<br />

9 Orange Black 21 Brown Blue 33 Red Brown<br />

10 Yellow Black 22 Black Orange 34 Blue Brown<br />

11 Brown Black 23 Red Orange 35 Orange Brown<br />

12 Black Red 24 Blue Orange 36 Yellow Brown


<strong>Tray</strong> <strong>Cable</strong> (VNTC)<br />

Multi-conductor, Unshielded<br />

TFN Conductors<br />

UL TYPE TC 600 Volts, 18 - 16 AWG<br />

<strong>Cable</strong> Specifications:<br />

Conductors: Stranded Bare Copper<br />

Singles Insulation: PVC/NYLON<br />

Color Code: ICEA Method 1, Table E2 (formerly Table K2) Per ICEA S-73-532<br />

Jacket: Black PVC<br />

Ratings: UL Listed Type TC 90°C dry, 75°C wet VW-1<br />

TFN Singles<br />

70,000 BTU per IEEE-383 Vertical <strong>Tray</strong> Fire Test<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART*<br />

NO. OF<br />

CONDS. STRAND<br />

INSULATION<br />

THICKNESS<br />

MILS.-NOM.<br />

NYLON<br />

INSULATION<br />

MILS.-NOM.<br />

JACKET<br />

THICKNESS<br />

MILS.-NOM.<br />

TC1802F/P 2 Flat 7 BC 15 4 45 .180 X .270 35<br />

TC1803P 3 7 BC 15 4 45 0.290 45<br />

TC1804P 4 7 BC 15 4 45 0.310 54<br />

TC1805P 5 7 BC 15 4 45 0.340 66<br />

TC1807P 7 7 BC 15 4 45 0.360 82<br />

TC1809P 9 7 BC 15 4 45 0.420 108<br />

TC1812P 12 7 BC 15 4 45 0.470 131<br />

TC1815P 15 7 BC 15 4 45 0.500 160<br />

TC1819P 19 7 BC 15 4 60 0.570 210<br />

TC1825P 25 7 BC 15 4 60 0.660 272<br />

TC1837P 37 7 BC 15 4 60 0.750 380<br />

TC1602F/P 2 Flat 7 BC 15 4 45 .190X.290 45<br />

TC1603P 3 7 BC 15 4 45 0.310 59<br />

TC1604P 4 7 BC 15 4 45 0.330 71<br />

TC1605P 5 7 BC 15 4 45 0.360 86<br />

TC1607P 7 7 BC 15 4 45 0.390 110<br />

TC1609P 9 7 BC 15 4 45 0.450 141<br />

TC1612P 12 7 BC 15 4 45 0.510 179<br />

TC1615P 15 7 BC 15 4 60 0.570 232<br />

TC1619P 19 7 BC 15 4 60 0.610 283<br />

TC1625P 25 7 BC 15 4 60 0.720 367<br />

TC1630P 30 7 BC 15 4 60 0.770 430<br />

TC1637P 37 7 BC 15 4 80 0.860 548<br />

Note: Dimensons and weights shown are nominal values. They are subject to standard industry tolerances.<br />

7<br />

DIAMETER APPROX.<br />

INCHES NET WT.<br />

NOM. # /1000 FT


<strong>Tray</strong> <strong>Cable</strong> (VNTC)<br />

Multi-conductor, Unshielded<br />

THHN/THWN CONDUCTORS<br />

UL TYPE TC 600 Volts, 14 - 12 AWG<br />

<strong>Cable</strong> Specifications:<br />

Conductors: Stranded Bare Copper<br />

Singles Insulation: PVC Insulation with nylon armour<br />

Color Code: ICEA Method 1 colors per table K-2.<br />

Jacket: Black PVC<br />

Ratings: UL Listed Type TC 90 C dry, 75 C wet VW-1<br />

(THN/THWN Only) IEE383<br />

70,000 and 210,000 BTU.<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART*<br />

NO. OF<br />

CONDS. STRAND<br />

INSULATION<br />

THICKNESS<br />

MILS.-NOM.<br />

NYLON<br />

INSULATION<br />

MILS.-NOM.<br />

TC1402F/P 2 Flat 7 BC 15 4 45 .205 X .315 58<br />

TC1403P 3 7 BC 15 4 45 0.340 90<br />

TC1404P 4 7 BC 15 4 45 0.370 96<br />

TC1405P 5 7 BC 15 4 45 0.400 117<br />

TC1407P 7 7 BC 15 4 45 0.430 152<br />

TC1409P 9 7 BC 15 4 45 0.500 195<br />

TC1412P 12 7 BC 15 4 45 0.590 266<br />

TC1415P 15 7 BC 15 4 60 0.640 326<br />

TC1419P 19 7 BC 15 4 60 0.690 396<br />

TC1425P 25 7 BC 15 4 60 0.790 518<br />

TC1430P 30 7 BC 15 4 60 0.890 638<br />

TC1437P 37 7 BC 15 4 60 0.950 774<br />

TC1202F/P 2 Flat 7 BC 15 4 45 .225 X .359 77<br />

TC1203P 3 7 BC 15 4 45 0.380 105<br />

TC1204P 4 7 BC 15 4 45 0.410 135<br />

TC1205P 5 7 BC 15 4 45 0.450 166<br />

TC1206P 6 7 BC 15 4 45 0.490 196<br />

TC1207P 7 7 BC 15 4 45 0.490 215<br />

TC1209P 9 7 BC 15 4 60 0.600 304<br />

TC1212P 12 7 BC 15 4 60 0.670 376<br />

TC1215P 15 7 BC 15 4 60 0.720 470<br />

TG1219P 19 7 BC 15 4 60 0.780 573<br />

TC1225P 25 7 BC 15 4 80 0.950 778<br />

TC1230P 30 7 BC 15 4 80 1.010 915<br />

TC1237P 37 7 BC 15 4 80 1.090 1107<br />

Note: Dimensons and weights shown are nominal values. They are subject to standard industry tolerances.<br />

8<br />

JACKET DIAMETER APPROX.<br />

THICKNESS INCHES NET WT.<br />

MILS.-NOM. NOM. # /1000 FT


<strong>Tray</strong> <strong>Cable</strong> (PLTC)<br />

Instrumentation <strong>Cable</strong><br />

PVC Conductors<br />

UL TYPE PLTC 300 V<br />

Description:<br />

● Conductors: Stranded Tinned Copper<br />

● Singles Insulation: PVC<br />

● Color Code: ICEA Method 1, Table E1 or E2<br />

● Jacket: Gray PVC<br />

● Sunlight and Oil resistant jacket<br />

● Rated as UL listed PLTC, ITC, 105°C<br />

● Meets UL 1685 Vertical Flame Test<br />

Color Code Chart<br />

Per ICEA Method 1 Table E-1<br />

COND.<br />

NO.<br />

COLOR<br />

BASE STRIPE<br />

COND.<br />

NO.<br />

COLOR<br />

BASE STRIPE<br />

COND.<br />

NO.<br />

COLOR<br />

BASE STRIPE<br />

1 Black - 13 Red White 25 Green Black/White<br />

2 White - 14 Green White 26 Orange Black/White<br />

3 Red - 15 Blue White 27 Blue Black/White<br />

4 Green - 16 Black Red 28 Black Red/Green<br />

5 Orange - 17 White Red 29 White Red/Green<br />

6 Blue - 18 Orange Red 30 Red Black/Green<br />

7 White Black 19 Blue Red 31 Green Black/Orange<br />

8 Red Black 20 Red Green 32 Orange Black/Green<br />

9 Green Black 21 Orange Green 33 Blue White/Orange<br />

10 Orange Black 22 Black White/Red 34 Black White/Orange<br />

11 Blue Black 23 White Black/Red 35 White Red/Orange<br />

12 Black White 24 Red Black/White 36 Orange White/Blue<br />

See Page 6 for Color Code Chart E2<br />

Application:<br />

Unshielded - Twisted non-shielded paris and triads<br />

provide a minimal OD allowing greater tray and<br />

conduit fill.<br />

Overall Shield - Recommended for use in<br />

instrumentation applications where signals are<br />

transmitted in excess of 100 millivolts except in<br />

areas where high voltage and current sources<br />

create excessive noise interference.<br />

9


<strong>Tray</strong> <strong>Cable</strong> (PLTC)<br />

Instrumentation <strong>Cable</strong><br />

PVC Conductors<br />

UL TYPE PLTC 300V<br />

<strong>Cable</strong> Specifications:<br />

Conductors: Stranded Tinned Copper<br />

Singles Insulation: PVC<br />

Color Code: ICEA Method 1, Table E1 or E2<br />

Jacket: Gray PVC<br />

UNSHIELDED<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART #<br />

AWG<br />

PAIR/<br />

TRIAD<br />

STRAND<br />

Ratings:<br />

UL listed PLTC, ITC, 105°C<br />

Meets UL1685 Vertical Flame Test<br />

Sunlight and Oil resistant jacket<br />

INSULATION<br />

THICKNESS<br />

MILS.-NOM.<br />

COLOR<br />

CODE<br />

JACKET<br />

THICKNESS<br />

MILS.-NOM.<br />

PLTC2202P 22 1 Pair 7x30 0.016 E2 0.037 0.198 16.7<br />

PLTC2203T 22 1 Triad 7x30 0.016 E1 0.037 0.208 23<br />

PLTC2002P 20 1 Pair 19x32 0.016 E2 0.037 0.214 23<br />

PLTC2003T 20 1 Triad 19x32 0.016 E1 0.037 0.225 27<br />

PLTC1802P 18 1 Pair 19x30 0.017 E2 0.037 0.230 27<br />

PLTC1803T 18 1 Triad 19x30 0.017 E1 0.037 0.242 35.9<br />

PLTC1602P 16 1 Pair 19x29 0.016 E1 0.037 0.254 34<br />

PLTC1603T 16 1 Triad 19x29 0.016 E1 0.037 0.268 48.5<br />

PLTC1402P 14 1 Pair 42x30 0.022<br />

E2 0.042 0.322 58<br />

PLTC1403T 14 1 Triad 42x30 0.022 E1 0.042 0.340 76.3<br />

10<br />

DIAMETER APPROX.<br />

INCHES NET WT<br />

NOM. #/ 1000 FT


<strong>Tray</strong> <strong>Cable</strong> (PLTC)<br />

Instrumentation <strong>Cable</strong><br />

PVC Conductors<br />

UL TYPE PLTC 300V<br />

<strong>Cable</strong> Specifications:<br />

Conductors: Stranded Tinned Copper<br />

Singles Insulation: PVC<br />

Color Code: ICEA Method 1, Table E1 or E2<br />

Jacket: Gray PVC<br />

Shield: Overall Foil<br />

SHIELDED<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART #<br />

AWG<br />

PAIR/<br />

TRIAD<br />

STRAND<br />

Ratings:<br />

UL listed PLTC, ITC, 105°C<br />

Meets UL1685 Vertical Flame Test<br />

Sunlight and Oil resistant jacket<br />

INSULATION<br />

THICKNESS<br />

MILS.-NOM.<br />

PLTC2202POFS 22 1 Pair 7x30 0.016 E2 0.037 0.201 21<br />

PLTC2204POFS 22 2 Pair 7x30 0.016 E2 0.042 0.310 37<br />

PLTC2203TOFS 22 1 Triad 7x30 0.016 E1 0.037 0.208 26<br />

PLTC2002POFS 20 1 Pair 19x32 0.016 E2 0.037 0.217 26<br />

PLTC2003TOFS 20 1 Triad 19x32 0.016 E1 0.037 0.228 31<br />

PLTC1802POFS 18 1 Pair 19x30 0.017 E2 0.037 0.233 32<br />

PLTC1804POFS 18 2 Pair 19x30 0.017 E2 0.042 0.368 59<br />

PLTC1602POFS 16 1 Pair 19x29 0.017 E2 0.037 0.256 41<br />

PLTC1402POFS 14 1 Pair 42x30 0.022 E2 0.042 0.324 67<br />

11<br />

COLOR<br />

CODE<br />

JACKET<br />

THICKNESS<br />

MILS.-NOM.<br />

PLTC1803TOFS 18 1 Triad 19x30 0.016 E1 0.037<br />

PLTC1603TOFS 16 1 Triad 19x29 0.016 E1 0.037<br />

DIAMETER APPROX.<br />

INCHES NET WT<br />

NOM. #/ 1000 FT<br />

0.245 39<br />

0.270 53<br />

PLTC1403TOFS 14 1 Triad 42x30 0.022<br />

E1 0.042 0.343 86


TFFN/THHN Building Wire<br />

90°C, 600 Volts, C(UL) T90 Nylon<br />

Description:<br />

● Conductor of soft drawn bare copper, concentric,<br />

compressed concentric, or combination unilay.<br />

● Singles Insulation: PVC/Nylon<br />

● Listed by Underwriters Laboratories under<br />

standards 83 and 1063 as:<br />

-Type THHN 90 C in dry locations<br />

-Type THWN 75 C in wet locations<br />

-Gasoline and oil resistant.<br />

-Type MTW 90 C Machine Tool Wire (stranded<br />

only)<br />

-105 C AWM, 80 C where exposed to oil.<br />

● TFFN is UL 1315, 105 C approved & CSA<br />

TEWN approved<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART# AWG<br />

NO. OF<br />

STRANDS<br />

INSULATION<br />

THICKNESS<br />

MILS-NOM<br />

NYLON<br />

INSULATION<br />

MILS-NOM<br />

Application:<br />

● General Purpose wiring in accordance<br />

with the NEC, maximum conductor<br />

temperature of 90 C in dry locations and<br />

75 C in wet locations, 600 volts for<br />

installation in conduit or other recognized<br />

race way. For wiring of machine tools<br />

(stranded), appliances and control<br />

circuits not exceeding 600 volts.<br />

DIAMETER<br />

INCHES<br />

NOM.<br />

APPROX.<br />

NET WT.<br />

#/1000 FT<br />

RoHS compliant material available upon request.<br />

*Listed as 105 C Appliance Wiring Material and 90 C MTW, also as Type TFFN (stranded conductor)<br />

and TFN (solid conductor) 90 C, CSA approved as Type TEWN.<br />

**Ampacity in accordance with NEC<br />

As THHN 90 C, conductor temperature at 30 C ambient in dry locations.<br />

As THHN 75 C, conductor temperature at 30 C ambient in wet or dry locations.<br />

NEC AMPACITY**<br />

75°C 90°C<br />

THWN THHN<br />

TFN18B01* 18 SOLID 15 5 0.083 8 0 6<br />

TFN16B01* 16 SOLID 15 5 0.094 11 0 8<br />

TFFN18B16* 18 16 16 5 0.090 8 0 6<br />

TFFN16B26* 16 26 16 5 0.103 12 0 8<br />

THHN14B01 14 SOLID 15 4 0.104 16 15 15<br />

THHN12B01 12 SOLID 15 4 0.121 24 20 20<br />

THHN10B01 10 SOLID 20 4 0.152 38 30 30<br />

THHN14B19 14 19 15 4 0.112 17 15 15<br />

THHN12B19 12 19 15 4 0.131 26 20 20<br />

THHN10B19 10 19 20 4 0.164 40 30 30<br />

THHN08B19 8 19 30 5 0.216 66 50 55<br />

THHN06B19 6 19 30 5 0.253 100 65 75<br />

THHN04B19 4 19 40 6 0.322 159 85 95<br />

THHN03B19 3 19 40 6 0.350 191 100 110<br />

THHN02B19 2 19 40 6 0.381 241 115 130<br />

THHN01B19 1 19 50 7 0.443 305 130 150<br />

THHN1/0B19 1/0 19 50 7 0.483 377 150 170<br />

THHN2/0B19 2/0 19 50 7 0.528 468 175 195<br />

THHN3/0B19 3/0 19 50 7 0.579 581 200 225<br />

THHN4/0B19 4/0 19 50 7 0.636 722 230 260<br />

THHN250B37 250 37 60 8 0.704 860 255 290<br />

THHN300B37 300 37 60 8 0.758 1018 310 350<br />

THHN350B37 350 37 60 8 0.808 1180 310 350<br />

THHN400B37 400 37 60 8 0.855 1342 335 380<br />

THHN500B37 500 37 60 8 0.938 1661 380 430<br />

12


XHHW-2 Building Wire<br />

90°C, 600 Volts<br />

Description:<br />

● Conductor of soft drawn bare copper<br />

with concentric stranding<br />

● Singles Insulation: Crosslinked<br />

polyethylene (XLPE)<br />

● Listed by Underwriters Laboratories as<br />

type XHHW-2 per UL standard 44.<br />

Application:<br />

● General purpose wiring in accordance<br />

with the NEC, maximum conductor<br />

temperature of 90 C in wet or dry<br />

locations<br />

INDUSTRIAL<br />

INSULATION DIAMETER APPROX.<br />

ELECTRIC<br />

NO. OF THICKNESS INCHES NET WT. NEC AMPACITY*<br />

PART # AWG STRANDS MILS. - NOM. NOM. # /1000 FT<br />

75°C 90°C<br />

XHHW14B07 14 7 30 0.133 18 15 25<br />

XHHW12B07 12 7 30 0.152 27 20 30<br />

XHHW10B07 10 7 30 0.175 39 30 40<br />

XHHW08B07 8 7 45 0.235 66 50 55<br />

XHHW06B07 6 7 45 0.275 99 65 75<br />

XHHW04B07 4 7 45 0.320 151 85 95<br />

XHHW02B07 2 7 45 0.380 232 115 130<br />

XHHW01B19 1 19 55 0.440 300 130 150<br />

XHHW1/0B19 1/0 19 55 0.480 372 150 170<br />

XHHW2/0B19 2/0 19 55 0.525 461 175 195<br />

XHHW3/0B19 3/0 19 55 0.575 573 200 225<br />

XHHW4/0B19 4/0 19 55 0.635 714 230 260<br />

XHHW250B37 250 37 65 0.700 846 255 290<br />

XHHW300B37 300 37 65 0.755 1005 285 320<br />

XHHW350B37 350 37 65 0.805 1166 310 350<br />

XHHW400B37 400 37 65 0.850 1318 335 380<br />

XHHW500B37 500 37 65 0.935 1642 380 430<br />

XHHW600B61 600 61 80 1.045 1986 420 475<br />

XHHW750B61 750 61 80 1.145 2453 475 535<br />

RoHS compliant material available upon request.<br />

* Ampacity in accordance with NEC for not more than three conductors in raceway.<br />

90°C conductor temperature at 30°C ambient in dry locations.<br />

90°C conductor temperature at 30°C ambient in wet locations.<br />

13


Welding <strong>Cable</strong><br />

Application<br />

● Secondary voltage resistance welding leads<br />

● Power Supply appllications not exceeding 600 Volt AC<br />

● Sizes 1/0 and larger for permanent wiring in conduit or tray of 600V power supplies,<br />

hoists, cranes or other applications where flexible power leads may be installed in<br />

conduit, raceways or tray.<br />

Class K (30 AWG STRAND)<br />

600 Volts 105°C - 50°C<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART# AWG<br />

NO. OF<br />

STRANDS<br />

NOTE: Stranding may vary slightly by manufacturer.<br />

Flexible bare copper conductor<br />

EPDM Insulation, Color Black<br />

Red insulation available upon request.<br />

INSULATION<br />

THICKNESS<br />

MILS. - NOM.<br />

Welding <strong>Cable</strong>, Extra Flexible<br />

UL Listed, Class M (34 AWG Strand)<br />

o o<br />

600 Volts, 90 C - 50 C<br />

14<br />

DIAMETER<br />

INCHES<br />

NOM.<br />

WC06 6 266/30 0.060 0.320 116<br />

WC04 4 392/30 0.060 0.375 163<br />

WC02 2 644/30 0.060 0.440 251<br />

WC01 1 784/30 0.080 0.515 321<br />

WC1/0 1/0 1026/30 0.080 0.550 388<br />

WC2/0 2/0 1254/30 0.080 0.590 474<br />

WC3/0 3/0 1615/30 0.080 0.660 601<br />

WC4/0 4/0 2052/30 0.080 0.725 762<br />

INDUSTRIAL<br />

ELECTRIC<br />

PART*<br />

AWG<br />

NO. OF<br />

STRANDS<br />

INSULATION<br />

THICKNESS<br />

MILS. - NOM.<br />

DIAMETER<br />

INCHES<br />

NOM.<br />

WC06 6<br />

660/34 0.078 0.370 125<br />

WC04 4<br />

1045/34 0.082 0.420 190<br />

WC02 2<br />

1650/34 0.091 0.475 260<br />

WC01 1<br />

2090/34 0.091 0.525 325<br />

WC1/0 1/0<br />

2640/34 0.095 0.610 410<br />

WC2/0 2/0<br />

3300/34 0.095 0.635 495<br />

WC3/0 3/0<br />

4180/34 0.104 0.700 620<br />

WC4/0 4/0<br />

5225/34 0.115 0.800 795<br />

NOTE: Stranding may vary slightly by manufacturer.<br />

Extra flexible bare copper conductor<br />

CPE Insulation, Color Orange<br />

Oil Resistant<br />

APPROX.<br />

NET WT.<br />

#/ 1000 FT<br />

APPROX.<br />

NET WT.<br />

# /1000 FT


Welding <strong>Cable</strong> Ampacities<br />

Required <strong>Cable</strong> Sizes:<br />

For Arc Welding <strong>Cable</strong> Application<br />

Length in feet for total circuit* for secondary voltages only<br />

- do not use this table for 600 volt applications.<br />

AMPS 100' 150' 200' 250' 300' 350' 400'<br />

100 4 4 2 2 1 1/0 1/0<br />

150 4 2 1 1/0 1/0 3/0 3/0<br />

200 2 1 1/0 2/0 3/0 4/0 4/0<br />

250 1 1/0 2/0 3/0<br />

300 1/0 2/0 3/0 4/0<br />

350 2/0 3/0 4/0<br />

400 2/0 3/0<br />

450 2/0 4/0<br />

500 3/0 4/0<br />

550 3/0 4/0<br />

600 4/0 REQUIRED CABLE SIZES SHOW IN GUAGE NUMBERS<br />

*The total circuit length includes both welding and ground leads (based on 4-volt drop) 60% duty cycle<br />

These values for current-carrying capacity are based on a copper temperature of 60 C (140 F), an<br />

ambient temperature of 40 C (104 F), and yield load factors from approximately 32% for the 2 AWG<br />

cable to approximately 23% for the 3/0 AWG <strong>Cable</strong>, and higher for the smaller sizes. The sizes of<br />

cables generally used range from 2 AWG to 3/0 AWG. In actual service, the load factor may be much<br />

higher than indicated without overheating the cable as the ambient temperature will generally be<br />

substantially lower than -40 C.<br />

Suggested Ampacities<br />

For 600 Volt In-Line Applications<br />

AWG AMPERES AWG AMPERES<br />

4/0 315 1 170<br />

3/0 275 2 150<br />

2/0 235 3 130<br />

1/0 200 4 110<br />

6 85<br />

15<br />

Per standards: ICEA S-19-81<br />

NEMA WC-3 Part 8, Appendix J<br />

Ampacities for portable cable,<br />

continuous duty (Ambient Temperature<br />

of 40 C)