Introduction<br />
General Joist<br />
Information<br />
Economical<br />
Design Guide<br />
Top Chord<br />
Ext., K-Series<br />
KCS <strong>Joists</strong> Joist Substitutes<br />
& Outriggers<br />
Joist LRFD<br />
Load Tables<br />
Joist ASD<br />
Load Tables<br />
Load/Load<br />
Weight Tables<br />
Joist Girder<br />
Weight Tables<br />
SJI St<strong>and</strong>ard<br />
Specifications<br />
SJI Code of<br />
St<strong>and</strong>. Practice<br />
Fire Resistance<br />
Ratings<br />
OSHA Safety<br />
St<strong>and</strong>ards<br />
SJI Bridging Tables<br />
TABLE 5.4-1<br />
NUMBER OF ROWS OF TOP CHORD BRIDGING - K-Series**<br />
Refer to K-Series Load Table <strong>and</strong> Specification Section 6 for required bolted diagonal bridging.<br />
Distances are Joist Span lengths in feet - See “Definition of Span” on page 27.<br />
Section # * Joist Depth One Row Two Rows Three Rows Four Rows<br />
1 All Up thru 17 Over 17 thru 26 Over 26 thru 28<br />
2 All Up thru 21 Over 21 thru 30 Over 30 thru 32<br />
3 All Up thru 18 Over 18 thru 26 Over 26 thru 40<br />
4 All Up thru 20 Over 20 thru 30 Over 30 thru 41 Over 41 thru 48<br />
5<br />
12K thru 24K<br />
26K<br />
Up thru 20<br />
Up thru 28<br />
Over 20 thru 30<br />
Over 28 thru 41<br />
Over 30 thru 42<br />
Over 41 thru 52<br />
Over 42 thru 48<br />
6<br />
14K thru 24K<br />
26K <strong>and</strong> 28K<br />
Up thru 20<br />
Up thru 28<br />
Over 20 thru 31<br />
Over 28 thru 41<br />
Over 31 thru 42<br />
Over 41 thru 54<br />
Over 42 thru 48<br />
Over 54 thru 56<br />
7<br />
16K thru 24K<br />
26K thru 30K<br />
Up thru 23<br />
Up thru 29<br />
Over 23 thru 34<br />
Over 29 thru 44<br />
Over 34 thru 48<br />
Over 44 thru 60<br />
8<br />
24K<br />
26K thru 30K<br />
Up thru 25<br />
Up thru 29<br />
Over 25 thru 39<br />
Over 29 thru 44<br />
Over 39 thru 48<br />
Over 44 thru 60<br />
9<br />
16K thru 24K<br />
26K thru 30K<br />
Up thru 22<br />
Up thru 29<br />
Over 22 thru 34<br />
Over 29 thru 44<br />
Over 34 thru 48<br />
Over 44 thru 60<br />
10<br />
18K thru 24K<br />
26K thru 30K<br />
Up thru 22<br />
Up thru 29<br />
Over 22 thru 38<br />
Over 29 thru 48<br />
Over 38 thru 48<br />
Over 48 thru 60<br />
11<br />
22K<br />
30K<br />
Up thru 24<br />
Up thru 34<br />
Over 24 thru 39<br />
Over 34 thru 49<br />
Over 39 thru 44<br />
Over 49 thru 60<br />
12<br />
24K<br />
26K thru 30K<br />
Up thru 25<br />
Up thru 29<br />
Over 25 thru 43<br />
Over 29 thru 47<br />
Over 43 thru 48<br />
Over 47 thru 60<br />
Joist Depth<br />
TABLE 2.7-3<br />
LH & DLH - SERIES JOISTS<br />
HORIZONTAL PLUS DIAGONAL BRIDGING REQUIREMENTS<br />
Minimum Joist Space for<br />
Diagonal Only Bridging<br />
(0.70 x Joist Depth)<br />
Discover the easiest way to specify steel <strong>joist</strong>s <strong>and</strong> Joist <strong>Girders</strong>:<br />
8 www.newmill.com/digital-tools<br />
Horizontal <strong>and</strong> Diagonal Bridging<br />
Minimum Angle Size Required*<br />
52 3’ - 0” L 1 x 1 x 7/64<br />
56 3’ - 3” L 1 x 1 x 7/64<br />
60 3’ - 6” L 1 x 1 x 7/64<br />
64 3’ - 8” L 1 1/4 x 1 1/4 x 7/64<br />
68 3’ - 11” L 1 1/4 x 1 1/4 x 7/64<br />
72 4’ - 2” L 1 1/4 x 1 1/4 x 7/64<br />
80 4’ - 8” L 1 1/4 x 1 1/4 x 7/64<br />
88 5’ - 1” L 1 1/2 x 1 1/2 x 7/64<br />
96 5’ - 7” L 1 1/2 x 1 1/2 x 7/64<br />
104 6’ - 0” L 1 3/4 x 1 3/4 x 7/64<br />
112 6’ - 6” L 1 3/4 x 1 3/4 x 7/64<br />
120 7’ - 0” L 2 x 2 x 1/8<br />
* When <strong>joist</strong> span is greater than 60’-0” <strong>and</strong> <strong>joist</strong> space is less than space shown (0.70 x Joist Depth), bolted horizontal bridging<br />
is required in addition to bolted diagonal bridging.<br />
TABLE 2.7-4<br />
BOLT SIZES WHICH MEET BOLTED BRIDGING<br />
CONNECTION REQUIREMENTS<br />
Joist Series Section Number* Bolt Diameter <strong>and</strong> Grade<br />
K ALL 3/8” A307<br />
LH/DLH 2 thru 12 3/8” A307<br />
LH/DLH 13 thru 17 1/2” A307<br />
DLH 18 thru 20 5/8” A307<br />
DLH 21 <strong>and</strong> 22 5/8” A325<br />
DLH 23 thru 25 3/4” A325<br />
* Refer to last digit(s) of st<strong>and</strong>ard SJI <strong>joist</strong> designation.<br />
Note: Washers shall be used with slotted or over-sized holes. Bolts shall be tightened to a minimum snug tight condition.<br />
* Refer to last digit(s) of st<strong>and</strong>ard SJI <strong>joist</strong> designation.<br />
** See Section 5.11 for additional bridging required<br />
for uplift design.<br />
OSHA TABLES A <strong>and</strong> B<br />
ERECTION BRIDGING<br />
Joist Span Joist Span<br />
12K1 23’ - 0” 30K9 45’ - 0”<br />
14K1 27’ - 0” 30K10 50’ - 0”<br />
16K2 29’ - 0” 30K11 52’ - 0”<br />
16K3 30’ - 0” 30K12 54’ - 0”<br />
16K4 32’ - 0” 18KCS2 35’ - 0”<br />
16K5 32’ - 0” 20KCS2 36’ - 0”<br />
18K3 31’ - 0” 20KCS3 39’ - 0”<br />
18K4 32’ - 0” 22KCS2 36’ - 0”<br />
18K5 33 - 0” 22KCS3 40’ - 0”<br />
18K6 35’ - 0” 24KCS2 39’ - 0”<br />
20K3 32’ - 0” 24KCS3 44’ - 0”<br />
20K4 34’ - 0” 26KCS2 39’ - 0”<br />
20K5 34’ - 0” 26KCS3 44’ - 0”<br />
20K6 36’ - 0” 28KCS2 40’ - 0”<br />
20K7 39’ - 0” 28KCS3 45’ - 0”<br />
20K9 39’ - 0” 28KCS4 53’ - 0”<br />
22K4 34’ - 0” 28KCS5 53’ - 0”<br />
22K5 35’ - 0” 30KCS3 45’ - 0”<br />
22K6 36’ - 0” 30KCS4 54’ - 0”<br />
22K7 40’ - 0” 30KCS5 54’ - 0”<br />
22K9 40’ - 0” 18LH02 33’ - 0”<br />
24K4 36’ - 0” 20LH02 33’ - 0”<br />
24K5 38’ - 0” 20LH03 38’ - 0”<br />
24K6 39’ - 0” 24LH03 35’ - 0”<br />
24K7 43’ - 0” 24LH04 39’ - 0”<br />
24K8 43’ - 0” 24LH05 40’ - 0”<br />
24K9 44’ - 0” 24LH06 45’ - 0”<br />
26K5 38’ - 0” 28LH05 42’ - 0”<br />
26K6 39’ - 0” 28LH06 46’ - 0”<br />
26K7 43’ - 0” 28LH07 54’ - 0”<br />
26K8 44’ - 0” 28LH08 54’ - 0”<br />
26K9 44’ - 0” 32LH06 47’ - 0”<br />
26K10 49’ - 0” 32LH07 47’ - 0”<br />
28K6 40’ - 0” 32LH08 55’ - 0”<br />
28K7 43’ - 0” 36LH07 47’ - 0”<br />
28K8 44’ - 0” 36LH08 47’ - 0”<br />
28K9 45’ - 0” 36LH09 57’ - 0”<br />
28K10 49’ - 0” 40LH08 47’ - 0”<br />
28K12 53’ - 0” 40LH09 47’ - 0”<br />
30K7 44’ - 0” 44LH09 52’ - 0”<br />
30K8 45’ - 0”<br />
<strong>Joists</strong> not listed above do not require OSHA<br />
erection bridging through spans per SJI<br />
Specifications 5.2 <strong>and</strong> 104.2 or 60’-0”.