SWITCH TERMINAL BLOCKS<br />

(BACKSIDE OF FACEPLATE)<br />

SUPERVISORY CIRCUIT<br />

FROM CONTROL PANEL<br />

OR ADDRESSABLE<br />

MONITOR MODULE<br />

RELEASE CIRCUIT FROM<br />

CONTROL PANEL OR<br />

-<br />

RELEASING MODULE<br />

+<br />

24 VDC<br />

(SEE NOTE 3)<br />

-<br />

+<br />

DISARMED<br />

R<br />

G<br />

ARMED<br />

SWITCH TERMINAL BLOCKS<br />

(BACKSIDE OF FACEPLATE)<br />

SUPERVISORY CIRCUIT<br />

FROM CONTROL PANEL<br />

OR ADDRESSABLE<br />

MONITOR MODULE<br />

RELEASE CIRCUIT FROM<br />

CONTROL PANEL OR<br />

-<br />

RELEASING MODULE<br />

+<br />

NO NC<br />

NOTES:<br />

1. WIRING DIAGRAM SHOWS SWITCH IN ARMED POSITION.<br />

2. ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED.<br />

NC NO NC<br />

NO NC<br />

NOTES:<br />

1. WIRING DIAGRAM SHOWS SWITCH IN ARMED POSITION.<br />

2. ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED.<br />

3. 24 VDC POWER TO SWITCH LEDs SHALL COME FROM THE<br />

ASSOCIATED CONTROL PANEL OR FROM A BATTERY<br />

BACKED 24 VDC, REGULATED, POWER-LIMITED POWER<br />

SUPPLY LISTED FOR FIRE PROTECTIVE SIGNALING USE.<br />

Exhibit 5: Wiring Diagram of <strong>Switch</strong> with LEDs<br />

Fike ® , 704 SW 10 th Street, P.O. Box 610, Blue Springs, Missouri 64013-<strong>06</strong>10 U.S.A. ● Tel: (816) 229-3405 ● Fax: (816) 229-4615<br />

P/N <strong>06</strong>-<strong>472</strong> Rev. 1 page 4 of 4 www.fike.com<br />

NC<br />

TO NEXT DISCONNECT<br />

SWITCH OR END-OF-LINE<br />

RESISTOR<br />

Exhibit 4: Wiring Diagram of <strong>Switch</strong> without LEDs<br />

-<br />

+<br />

TO ARM, IRM OR<br />

RELEASING SOLENOID<br />

-<br />

+<br />

TO NEXT DISCONNECT<br />

SWITCH OR END-OF-LINE<br />

RESISTOR<br />

TO ARM, IRM OR<br />

RELEASING SOLENOID