SINGAPORE CIVIL DEFENCE FORCE<br />

FIRE SAFETY & SHELTER DEPARTMENT<br />

HQ SINGAPORE CIVIL DEFENCE FORCE<br />

91 Ubi Ave 4 <strong>Singapore</strong> 408827 Fax : 6848 1488<br />

Website : http//:www.scdf.gov.sg<br />

Fire Fighting Provisions and Structural Fire Precautions<br />

18. All parts <strong>of</strong> <strong>the</strong> structure are to be located within 100m <strong>of</strong> a <strong>fire</strong> hydrant. And no tent shall be located<br />

within 3m <strong>of</strong> any <strong>fire</strong> hydrant, breeching inlets <strong>of</strong> <strong>fire</strong> fighting rising mains or <strong>fire</strong> exit staircases <strong>of</strong><br />

neighbouring buildings.<br />

19. No activity shall be carried out on <strong>the</strong> <strong>fire</strong> engine access way / <strong>fire</strong> engine hard standing<br />

(parking space).<br />

20. 2.5kg ABC dry chemical powder <strong>fire</strong> extinguisher (PSB approved type) shall be provided such<br />

that no person needs to travel more than 15m to reach <strong>the</strong>m.<br />

21. Two 2.5kg carbon dioxide <strong>fire</strong> extinguishers (PSB approved type) shall be provided in <strong>the</strong><br />

vicinity <strong>of</strong> each generator / air conditioning set. Generators are to be sited at least 5m away<br />

from buildings and tents / stalls.<br />

22. AC units with return-air, must be fitted with smoke detectors.<br />

23. A manual <strong>fire</strong> alarm bell is to be provided if <strong>the</strong> total floor area <strong>of</strong> <strong>the</strong> structure exceeds 400m 2<br />

and it is to be provided at each level. Its sounding must be audible throughout <strong>the</strong> structure.<br />

24. Any row <strong>of</strong> stall inside <strong>the</strong> structure shall not exceed 15m in length.<br />

25. Separation distance <strong>of</strong> at least 3m between rows <strong>of</strong> stalls shall be maintained.<br />

26. Covered structures / booths (if any) are not to exceed 3m in height. Ro<strong>of</strong>ing or ceiling <strong>of</strong> covered booths<br />

shall be <strong>of</strong> non-combustible material or minimum class 2 surface flame spread rating (to be supported<br />

by PSB certificates). Such booths are not to be <strong>of</strong> <strong>the</strong> enclosed type unless prior approval has been<br />

obtained.<br />

27. The erection <strong>of</strong> multi-storey booths is not allowed unless prior approval has been obtained.<br />

27. All sides <strong>of</strong> <strong>the</strong> timber floor decking / stage / plat<strong>for</strong>m shall be properly sealed with no storage<br />

<strong>of</strong> goods / materials / electrical services beneath <strong>the</strong>m.<br />

28. Fabric materials / curtains must be <strong>of</strong> minimum class 2 surface flame spread rating.<br />

O<strong>the</strong>r Fire Safety Precautions<br />

29. Any activity involving <strong>the</strong> use LPG or flammable liquids / gases is not permitted.<br />

30. “Open-flame” cooking is not allowed except where solid fuel burners are used to warm food<br />

that has already been prepared and cooked.<br />

31. Combustible materials are kept to a minimum and away from heat sources.<br />

32. Electrical fixtures /wiring are firmly secured away from public’s path.<br />

33. The event organizer shall provide a team <strong>of</strong> personnel <strong>for</strong> emergency evacuation and <strong>for</strong><br />

fighting incipient <strong>fire</strong>s on site.<br />

34. To contact our <strong>of</strong>ficer at 68481411 to arrange <strong>for</strong> an inspection <strong>of</strong> <strong>the</strong> site 2 days be<strong>for</strong>e <strong>the</strong><br />

commencement <strong>of</strong> <strong>the</strong> event.<br />

35. To remove / clear <strong>the</strong> <strong>temporary</strong> structures within 3 days upon expiry <strong>of</strong> <strong>the</strong> approved period.<br />

The duration <strong>of</strong> <strong>the</strong> event is limited to at most 2 months.<br />

* Note: Normally used <strong>for</strong> events / activities such as<br />

a. Mock-up structures<br />

b. Exhibitions / Trade fairs<br />

c. Expositions<br />

Updated : 01 Mar 2008<br />