12 SEER Package Gas / Electric Units CONVERTIBLE ... - AirEng.com
12 SEER Package Gas / Electric Units CONVERTIBLE ... - AirEng.com
12 SEER Package Gas / Electric Units CONVERTIBLE ... - AirEng.com
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>12</strong> <strong>SEER</strong> <strong>Package</strong><br />
<strong>Gas</strong> / <strong>Electric</strong> <strong>Units</strong><br />
<strong>CONVERTIBLE</strong> MODELS<br />
YCP024-060F<br />
2 – 5 Ton<br />
YCP-D-1<br />
PUB. NO. 22-1708-01-499 (EN)
WATER-SHED Base<br />
High Efficiency<br />
Climatuff ® Compressor<br />
DuraTuff Plate Fin Coil<br />
Single Stage <strong>Gas</strong> Furnace<br />
Easy Access<br />
© American Standard Inc. 1999<br />
General<br />
Features<br />
2<br />
T-TOP<br />
Metal Coil Grille<br />
WEATHERGUARD<br />
Corrosion Resistant Screws<br />
Powder Paint<br />
Pub. No. 22-1708-01-499 (EN)
Features<br />
and Benefits<br />
Pub. No. 22-1708-01-499 (EN)<br />
Standard Equipment<br />
• High Efficiency<br />
IMPACK performance is the highest in the<br />
industry at 16.00 <strong>SEER</strong>.<br />
• Climatuff ® Compressors<br />
Protection against chemical, electrical, and<br />
mechanical stresses are built in for<br />
efficiency and a longer life. The<br />
<strong>com</strong>pressors are backed by a 5-year limited<br />
warranty.<br />
• Powder Paint<br />
Beautiful high gloss silver gray finish blends<br />
with any architectural style. New powder<br />
paint covers surfaces uniformly increasing<br />
protection from rust and corrosion.<br />
• WEATHERGUARD<br />
Corrosion Resistant Screws<br />
Holds it all together beautifully. Resists rust<br />
and corrosion.<br />
• WATER-SHED Base<br />
Superior water integrity is ac<strong>com</strong>plished<br />
with the WATER-SHED base pan having<br />
elevated downflow openings and a<br />
perimeter channel that prevents water from<br />
draining into the ductwork.<br />
• T-TOP<br />
Exclusive one piece, solid unit top for<br />
improved water integrity and easy<br />
<strong>com</strong>ponent access.<br />
• Coil Grille<br />
The metal grille will protect the coil from<br />
hail, kids with sticks, and normal shipping,<br />
installation and handling damage.<br />
• DuraTuff Plate Fin Coil<br />
Refrigeration coils are built with internally<br />
enhanced copper tubing for high efficiency<br />
with less coil area.<br />
(continued on page 4)<br />
Contents<br />
Feature Summary<br />
Features and Benefits<br />
Standard Equipment<br />
IMPACK Accessories<br />
Selection Procedure<br />
Model Number Nomenclature<br />
Optional Equipment<br />
General Data<br />
YCP024F1L0A<br />
YCP024F1M0A<br />
YCP030F1L0A<br />
YCP030F1M0A<br />
YCP036F1L0A<br />
YCP036F1M0A<br />
YCP036F1H0A<br />
YCP036F3L0A<br />
YCP036F3M0A<br />
YCP036F3H0A<br />
YCP036F4H0A<br />
YCP042F1M0A<br />
YCP042F3M0A<br />
YCP048F1H0A<br />
YCP048F3H0A<br />
YCP048F4H0A<br />
YCP060F1M0A<br />
YCP060F3M0A<br />
YCP060F4M0A<br />
Performance Data<br />
Cooling<br />
Indoor Fan<br />
Optional Equipment<br />
Field Wiring<br />
Dimensions<br />
Mechanical Specification Options<br />
3<br />
2<br />
3<br />
5<br />
5<br />
6<br />
7<br />
11<br />
16<br />
18<br />
21<br />
28
• Single Stage <strong>Gas</strong> Furnace<br />
The furnace features aluminized tubular<br />
heat exchangers that have demonstrated<br />
their durability in torturous life cycle tests<br />
and fire tests at either 20 or 25 MBTUH per<br />
tube on natural gas or 24 MBTUH on<br />
propane. The heat exchanger is backed by<br />
a 10 year limited warranty .<br />
• Venting<br />
Induced draft venting reduces <strong>com</strong>bustion<br />
problems associated with high winds and<br />
<strong>com</strong>bustion panels that have been<br />
improperly replaced.<br />
• California NOx<br />
The standard unit meets California NOx<br />
requirements eliminating the inventory<br />
problems associated with unique models or<br />
kits.<br />
• One for Us...<br />
Two for Customer<br />
Three-try direct spark ignition system<br />
eliminates pilot related problems and<br />
provides unsurpassed ignition reliability.<br />
• Commonality<br />
The <strong>com</strong>mon cabinet among the TCC’s,<br />
WCX’s, and YCP’s minimizes both the<br />
training of sales and service personnel and<br />
replacement parts inventory.<br />
• Easy Access<br />
All electrical <strong>com</strong>ponents can be diagnosed<br />
and replaced with the removal of one panel<br />
that is attached with two screws.<br />
• Flexibility<br />
A single curb fits the entire IMPACK line<br />
from 1.5 tons through 5 tons thereby<br />
providing great installation flexibility on<br />
shopping malls, factories, schools, and<br />
other <strong>com</strong>mercial buildings where a mixmatch<br />
of tonnages and utilities is desired.<br />
Features<br />
and Benefits<br />
Standard Equipment<br />
• Shipping<br />
Unit dimensions were carefully selected to<br />
provide an attractive aspect ratio and for<br />
shipping and handling considerations.<br />
• Good Neighbor<br />
Most units can be installed flush with the<br />
residence or building thereby minimizing the<br />
ground space required. Blankets of<br />
insulation reduce blower noise and energy<br />
losses to the outside environments.<br />
• Rooftop Mounting<br />
The cabinets are physically smaller than<br />
most <strong>com</strong>petitive models. This means less<br />
intrusive installations on residential rooftops<br />
where aesthetics are critical.<br />
• Convertibility<br />
IMPACK units are easily converted from<br />
horizontal to down flow with the removal of<br />
one screw from each panel. Accordingly,<br />
the need to stock both dedicated horizontal<br />
and dedicated down flow models has been<br />
eliminated.<br />
• Installation<br />
The ease of installation and application<br />
flexibility exhibited through the design<br />
reduce both field time and material.<br />
• Structure<br />
The units are lighter weight through the use<br />
of high technology <strong>com</strong>ponents thereby<br />
reducing mounting structure requirements<br />
and difficulty when manhandling.<br />
• Handling<br />
The three-way wooden skid allows for easy<br />
loading between the wheel wells on pickup<br />
trucks for transporting to job sites.<br />
• Application<br />
The low profile horizontal duct take-offs<br />
eliminate the need for expensive transition<br />
ducts in crawl space applications.<br />
• Duct Flanges<br />
Only IMPACK has downflow duct flanges for<br />
duct attachments that preserve the built-in<br />
water integrity.<br />
• Service<br />
All wiring is both numbered and color coded<br />
thereby reducing training and servicing<br />
costs related to circuit tracing and<br />
<strong>com</strong>ponents replacements.<br />
• Maintenance<br />
A plug on the outdoor fan motor allows the<br />
top cover to be removed <strong>com</strong>pletely without<br />
the hassle of cumbersome wires. The<br />
unique service orifice ring allows the indoor<br />
fan motor/blower to be removed as a unit.<br />
4<br />
• Corrosion<br />
The drain pan is engineered material and<br />
eliminates the need for coatings and sealers<br />
to prevent sweating and corrosion. The<br />
heavy gauge, zinc-coated steel cabinet has<br />
a weather resistant enamel finish that stays<br />
attractive and protects your investment for<br />
years.<br />
• Low Ambient Control<br />
Standard cooling operation to 55° F as<br />
shipped, zero degree ambient cooling is<br />
ac<strong>com</strong>plished with two kits. One for low cost<br />
installations when full tonnage is not<br />
needed. The other kit maintains head<br />
pressure and full capacity at zero degrees.<br />
• Quality and Reliability Testing<br />
We perform a 100% coil leak test at the<br />
factory. The evaporator and condenser coils<br />
are leak tested at 200 psig and pressure<br />
tested to 450 psig respectively. In addition<br />
the IMPACK designs were rigorously rain<br />
tested at the factory to ensure water<br />
integrity. Shipping tests are performed to<br />
determine packaging requirements. Factory<br />
shake and drop tests are used as part of<br />
the package design process to help assure<br />
that the unit will arrive at the job site in top<br />
condition. Additionally, all <strong>com</strong>ponents are<br />
inspected at the point of final assembly.<br />
Substandard parts and <strong>com</strong>ponents are<br />
identified and rejected immediately. Every<br />
unit receives a 100% run test before leaving<br />
the production line to make sure it lives up<br />
to rigorous Trane requirements. We at Trane<br />
test our designs at our factory and not on<br />
our customers!<br />
Pub. No. 22-1708-01-499 (EN)
• Standard Thermostats<br />
No special thermostats are needed with<br />
IMPACK units.<br />
• Filter Frame Kit<br />
The IMPACK filter frames accept standard<br />
filters and fit inside the unit. The frame kits<br />
function in either horizontal or downflow<br />
duct configurations.<br />
• UNI-CURB<br />
One universal curb fits all the IMPACK<br />
models. It ships knocked down. The curb<br />
design incorporates the popular locking tabs<br />
for quick and easy assembly. Full perimeter<br />
curbs are also available for all models.<br />
• Economizer<br />
The economizer fits inside the unit with only<br />
the rain hood and barometric relief on the<br />
outside. Cabling is shipped with the<br />
economizer. This cabling is easily routed to<br />
the control box where it terminates in low<br />
voltage pigtails. The economizer features a<br />
fully modulating low voltage motor<br />
eliminating the need for any high voltage<br />
wiring. The economizer must be used with<br />
the filter frame kit...no return air filter in the<br />
economizer kit. A dry bulb sensor is shipped<br />
with the economizer. The downflow<br />
economizer was not designed for use in<br />
horizontal applications. A horizontal only<br />
economizer is available.<br />
• Enthalpy Control Kit<br />
For those applications specifying an<br />
economizer with enthalpy control, this<br />
Pub. No. 22-1708-01-499 (EN)<br />
PRODUCT TYPE<br />
YC = <strong>Package</strong>d <strong>Gas</strong>/<strong>Electric</strong><br />
TC = <strong>Package</strong>d Cooling<br />
WC = <strong>Package</strong>d Heat Pumps<br />
DC = Dual Fuel<br />
AIRFLOW CONFIGURATION<br />
C = Convertible<br />
D = Downflow<br />
H = Horizontal<br />
M = Manufactured Housing<br />
X,P = <strong>12</strong> <strong>SEER</strong><br />
Y = 13-14 <strong>SEER</strong><br />
Z = 15-16 <strong>SEER</strong><br />
NOMINAL NET COOLING<br />
CAPACITY (MBH)<br />
018 = 1 1/2 Tons<br />
024 = 2 Tons<br />
030 = 2 1/2 Tons<br />
036 = 3 Tons<br />
042 = 3 1/2 Tons<br />
048 = 4 Tons<br />
060 = 5 Tons<br />
IMPACK<br />
Accessories<br />
control can be used in place of the dry bulb<br />
sensor or, alternately, two enthalpy controls<br />
can be paired to provide differential enthalpy<br />
control.<br />
• 25% Fresh Air Kit<br />
The kit installs over the horizontal return air<br />
opening with six screws for downflow<br />
requirements. It can be used on horizontal<br />
air flow applications by cutting a hole in the<br />
return air duct or in the unit filter access<br />
panel.<br />
• Rectangular to Round Duct Kits<br />
The adapter kit can be used in either<br />
horizontal or downflow applications.<br />
• Propane Kits<br />
One propane kit fits all the IMPACK models.<br />
This kit has been constructed for greatest<br />
field flexibility and to minimize the number of<br />
parts that have to be discarded.<br />
Selection Procedure<br />
Model Number Nomenclature<br />
1 2 3 4 5 6 7 8 9 10 11 <strong>12</strong><br />
Y C P 0 3 6 F 1 M 0 A A<br />
5<br />
• Low Fire Kits<br />
Seven Low fire kits are available for low fire<br />
operation on all the IMPACK models.<br />
• Low Ambient Kit<br />
An EDC provides low ambient cooling to 0°<br />
F with some reduced capacity and protects<br />
the system against evaporator icing during<br />
other unusual cooling conditions.<br />
• Head Pressure Control Kit<br />
This kit includes a solid state outdoor motor<br />
control, junction box, and wiring. It provides<br />
full capacity down to 0° F.<br />
• Sump Heat Kits<br />
Four sump heat kits are offered for low<br />
ambient operation.<br />
• Lifting Lug Kit<br />
Four reusable lugs in each kit allow units to<br />
be easily lifted to rooftop installations. These<br />
lugs snap (no screws required) into slots in<br />
the unit drip lip channel.<br />
• High Static Motor Kit<br />
Consists of a higher torque indoor fan<br />
motor.<br />
• Start Kits<br />
The kit mounts in the control box for those<br />
installations specific conditions such as<br />
excessive voltage drop due to long wires.<br />
(This is a capacitor and start relay kit not a<br />
PTC device.)<br />
SERVICE DESIGN<br />
MINOR DESIGN SEQUENCE<br />
FACTORY INSTALLED OPTIONS<br />
EXAMPLES:<br />
0 = No factory installed options<br />
B = Oversize Motor*<br />
N = Filter Frame*<br />
T = Fan Delay Relay*<br />
* Product Deviation Required<br />
AUXILIARY HEATING CAPACITY<br />
L = Low Heat<br />
M = Medium Heat<br />
H = High Heat<br />
0 = No Heat<br />
ELECTRICAL CHARACTERISTICS<br />
1 = 208-230/60/1<br />
3 = 208-230/60/3<br />
4 = 460/60/3<br />
MAJOR DEVELOPMENT SEQUENCE<br />
F = IMPACK<br />
G = IMPACK Plus
Optional<br />
Equipment<br />
OPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [✓] indicates accessories included)<br />
Indoor Thermostats — XT300C Prog. Electronic Setback Manual. 1 Htg/1 Clg ..................................................................................... TAYSTAT300C [ ]<br />
XT302C Prog. Auto. 2-Stage Htg/CIg w/ Econ. ............................................................................................... TAYSTAT302C [ ]<br />
Outdoor Temperature Sensor (use with TAYSTAT300,302C) ....................................................................... TAYSENS100A [ ]<br />
Heat/Cool (Horizontal) Man. 1 Htg/1Clg .................................................................................................................. AY28X092 [ ]<br />
Heat/Cool (Vertical) Man. 1Htg/1Clg .................................................................................................................... BAYSTAT305 [ ]<br />
Thermostat 1H/1C Sub-base Required (BAY28X184,187) ................................................................................. BAYSTAT182 [ ]<br />
Thermostat 2H/2C Sub-base Required (BAY28X184,187) ................................................................................. BAYSTAT183 [ ]<br />
Subbase Auto/Manual Changeover ................................................................................................................ BAYSTAT184 [ ]<br />
Subbase Manual Changeover ........................................................................................................................ BAYSTAT187 [ ]<br />
Thermostat 1H/1C Manual Sub-base ................................................................................................................. BAYSTAT008 [ ]<br />
Thermostat 2H/2C Auto Sub-base ...................................................................................................................... BAYSTAT010 [ ]<br />
Thermostat 1H/2C Manual Sub-base w/econ. ..................................................................................................... BAYSTAT0<strong>12</strong> [ ]<br />
Programmable Auto./Manual 1-Stage Htg/CIg .................................................................................................. BAYSTAT036A [ ]<br />
Programmable Auto./Manual 2-Stage Htg/CIg .................................................................................................. BAYSTAT037A [ ]<br />
Remote Indoor Sensor (use with BAYSTAT036A,037A) ............................................................................. BAYSENS025A [ ]<br />
Outdoor Temperature Sensor (use with BAYSTAT036A,037A) ................................................................... BAYSENS024A [ ]<br />
Duct Temperature Sensor (use with BAYSENS025A) 7 ............................................................................. BAYSENS026A [ ]<br />
Retrofit Wall Cover Plate Kit (use with BAYSTAT036A,037A) ...................................................................... BAYMTPL005A [ ]<br />
Locking Thermostat Cover (Thermostats) ............................................................................................................. BAY28X190 [ ]<br />
Anti-short Cycle Timer ............................................................................................................................................................................. BAYASCT001 [ ]<br />
Roof Curb (Flat Roof) Universal 3 ....................................................................................................................................................... BAYCURB030A [ ]<br />
Roof Curb (Flat Roof) Universal 3 Acusti-Curb ................................................................................................................................... BAYCURB038A [ ]<br />
Roof Curb Full Perimeter (YCP036F-H,42F-M) 3 Acusti-Curb ............................................................................................................. BAYCURB033A [ ]<br />
Roof Curb Full Perimeter (YCP048-60F) 3 Acusti-Curb ...................................................................................................................... BAYCURB034A [ ]<br />
Roof Curb Utility Extension Kit (BAYCURB030,038A) ........................................................................................................................... BAYUTIL030A [ ]<br />
Roof Curb Utility Extension Kit (BAYCURB033A) ................................................................................................................................... BAYUTIL033A [ ]<br />
Roof Curb Utility Extension Kit (BAYCURB034A) ................................................................................................................................... BAYUTIL034A [ ]<br />
0-25% Manual Fresh Air Damper (YCP018-42F) 1 ............................................................................................................................ BAYDMPR040A [ ]<br />
0-25% Manual Fresh Air Damper (YCP048-60F) 1 ............................................................................................................................ BAYDMPR041A [ ]<br />
<strong>12</strong>" Round Duct Adapter (2 per box) (YCP018-42F) ........................................................................................................................... BAYDUCT004A [ ]<br />
14" Round Duct Adapter (1 per box) (YCP018-42F) ........................................................................................................................... BAYDUCT005A [ ]<br />
0-100% Mod Economizer w/Baro. Relief (YCP018-42F) <strong>12</strong>4 ........................................................................................................... BAYECON054B [ ]<br />
0-100% Mod. Economizer w/Baro. Relief (YCP048-60F) <strong>12</strong>4 .......................................................................................................... BAYECON055B [ ]<br />
0-100% Horizontal Economizer <strong>12</strong> .................................................................................................................................................... BAYECON073A [ ]<br />
Enthalpy Control for Economizer (solid state) ...................................................................................................................................... BAYENTH001A [ ]<br />
Remote Potentiometer (BAYECON054,055B,073A) ............................................................................................................................... BAYSTAT023 [ ]<br />
Filter Frame (YCP024F-L) (20 x 20 x 1) 1 ............................................................................................................................................. BAYFLTR015A [ ]<br />
Filter Frame (YCP030-036F-L/M,024F-M) (20 x 25 x 1) 1 .....................................................................................................................BAYFLTR0<strong>12</strong>A [ ]<br />
Filter Frame (YCP036F-H,042F-M) (20 x 25 x 1) 1 ............................................................................................................................... BAYFLTR013A [ ]<br />
Filter Frame (YCP048-060G) (3-10 x 25 x 1) 1 ..................................................................................................................................... BAYFLTR014A [ ]<br />
Filter Frame (YCP030-036F-L/M,024F-M) (20 x 25 x 2) 1 .....................................................................................................................BAYFLTR017A [ ]<br />
Filter Frame (YCP036F-H,042F-M) (20 x 25 x 2) 1 ............................................................................................................................. BAYFLTR018A [ ]<br />
Filter Frame (YCP048-060F) (2-16 x 25 x 2) 1 ..................................................................................................................................... BAYFLTR019A [ ]<br />
Low Fire Kit (YCP018/024/030/036F-L) ................................................................................................................................................. BAYLOFR001 [ ]<br />
Low Fire Kit (YCP024F-M) ...................................................................................................................................................................... BAYLOFR002 [ ]<br />
Low Fire Kit (YCP030/036F-M) ............................................................................................................................................................. BAYLOFR0003 [ ]<br />
Low Fire Kit (YCP036F-H-042F-M) .......................................................................................................................................................... BAYLOFR004 [ ]<br />
Low Fire Kit (YCP048-060F) ................................................................................................................................................................... BAYLOFR006 [ ]<br />
High Static Motor (YCP030-042F)(230v/460v)(3/4 HP) ....................................................................................................................... BAYHSMT043A [ ]<br />
High Static Motor (YCP030-042F)(208v)(3/4 HP) ................................................................................................................................ BAYHSMT056A [ ]<br />
High Static Motor (YCP048-060F)(230v/460v)(1 HP) .......................................................................................................................... BAYHSMT044A [ ]<br />
High Static Motor (YCP048-060F)(208v)(1 HP) ................................................................................................................................... BAYHSMT045A [ ]<br />
LP Conversion Kit ................................................................................................................................................................................ BAYLPKT022A [ ]<br />
Lifting Lug Kit ......................................................................................................................................................................................... BAYLlFT002A [ ]<br />
Evaporator Defrost Control (Low Ambient Cooling) Kit 6 .................................................................................................................... BAYLOAM011A [ ]<br />
Head Pressure Control (Low Ambient Cool) (208/240v) Kit 56 ......................................................................................................... BAYLOAM323A [ ]<br />
Low Ambient Motor (208/230v) 5 ....................................................................................................................................................... BAYMOTR307A [ ]<br />
Low Ambient Motor (460v) 5 .............................................................................................................................................................. BAYMOTR406A [ ]<br />
Quick Start Kit (YCP024F1) ................................................................................................................................................................. BAYKSKT010A [ ]<br />
Quick Start Kit (YCP030-60F1) ............................................................................................................................................................ BAYKSKT254A [ ]<br />
Crankcase Heater (YCP024F1L/M)(230v) 6 ....................................................................................................................................... BAYCCHT003A [ ]<br />
Crankcase Heater (YCP030-048F1/3)(230v) 6 .................................................................................................................................. BAYCCHT202A [ ]<br />
Crankcase Heater (YCP060F1/3)(230v) 6 ......................................................................................................................................... BAYCCHT203A [ ]<br />
Crankcase Heater (YCP036,048F4)(460v) 6 ..................................................................................................................................... BAYCCHT400A [ ]<br />
Crankcase Heater (YCP060F4)(460v) 6 ............................................................................................................................................. BAYCCHT401A [ ]<br />
NOTES:<br />
1 Must use filter frame when economizer/fresh air kit is used. 5 Use Low Ambient Motor With This Kit.<br />
2 Dry bulb control standard with economizer. 6 Low Ambient cooling requires crankcase heater (BAYCCHT----A).<br />
3 Ships knocked down. 7 BAYSENS026A must be used with BAYSENS025A.<br />
4 Downflow only.<br />
6<br />
Pub. No. 22-1708-01-499 (EN)
MODEL<br />
RATED VOLTS/PH/HZ<br />
RATINGS (COOLING) 1<br />
BTUH<br />
Indoor Airflow (CFM)<br />
Power Input (KW)<br />
EER/<strong>SEER</strong> (BTU/Watt-Hr.)<br />
Noise Rating No. 1<br />
A.G.A. RATINGS (HEATING) 2<br />
(High) Input BTUH<br />
Capacity BTUH 57<br />
AFUE<br />
Temp. Rise °F. (Min./Max.)<br />
(Low) Input BTUH<br />
Capacity BTUH 57<br />
AFUE<br />
Temp. Rise °F. (Min./Max.)<br />
Type of <strong>Gas</strong> 3<br />
POWER CONNS.—V/PH/HZ<br />
Min. Brch. Cir. Ampacity<br />
Br. Cir. Max. (Amps)<br />
Prot. Rtg. Recmd. (Amps)<br />
COMPRESSOR<br />
No. Used<br />
Volts/Ph/Hz<br />
R.L. Amps—L.R. Amps<br />
OUTDOOR COIL—TYPE<br />
Rows / F.P.I.<br />
Face Area (Sq. Ft.)<br />
Tube Size (in.)<br />
INDOOR COIL—TYPE<br />
Rows / F.P.I.<br />
Face Area (Sq. Ft.)<br />
Tube Size (in.)<br />
Refrigerant Control<br />
Drain Conn. Size (in.)<br />
Duct Connections<br />
OUTDOOR FAN—TYPE<br />
No. Used / Dia. (in.)<br />
Type Drive / No. Speeds<br />
No. Motors—HP<br />
Motor Speed R.P.M.<br />
Volts/PH/HZ<br />
F.L. Amps—L.R. Amps<br />
INDOOR FAN—TYPE<br />
Dia. x Width (in.)<br />
No. Used<br />
Drive / Speeds (No.)<br />
No. Motors—HP<br />
Motor Speed R.P.M.<br />
Volts/PH/HZ<br />
F.L Amps<br />
COMBUSTION FAN—TYPE<br />
Drive—Speeds (No.)<br />
Motor HP—Speed (RPM)<br />
Volts/PH/HZ<br />
F.L. Amps<br />
FILTER—FURNISHED?<br />
Type Re<strong>com</strong>mended<br />
Min Face Area-Lo (sq. ft.) 6<br />
REFRIGERANT<br />
Charge (lbs. of R-22) 4<br />
GAS PIPE SIZE (IN.)<br />
DIMENSIONS<br />
Crated (in.)<br />
Uncrated<br />
WEIGHT<br />
Shipping (lbs.) / Net (lbs.)<br />
*See unit nameplate for proper input adjustment<br />
1 Rated in accordance with A.R.I. Standard 210/240. Noise tested in accordance with A.R.I. Standard 270. A.R.I.<br />
standard rating conditions are: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoor coil.<br />
2 All models are UL Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a<br />
rate of 4% per 1000 ft. elevation.<br />
3 Convertible to LPG.<br />
Pub. No. 22-1708-01-499 (EN)<br />
YCP024F1L0A<br />
208-230/1/60<br />
23800<br />
800<br />
2.38<br />
10.25 / <strong>12</strong>.00<br />
8.0<br />
48000<br />
38000<br />
79%<br />
30-60<br />
38000<br />
30000<br />
80%<br />
30-60<br />
NATURAL<br />
208-230/1/60<br />
14.6<br />
20<br />
20<br />
CLIMATUFF ®<br />
1<br />
200-230/1/60<br />
9.1 - 62<br />
PLATE FIN<br />
3 / 15<br />
5.43<br />
3/8 COPPER<br />
PLATE FIN<br />
3 / 15<br />
3.25<br />
3/8 COPPER<br />
TXV-NB<br />
3/4" FEMALE NPT<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
9 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/4<br />
1080<br />
200-230/1/60<br />
1.6/1.4 - 2.9<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/35 - 3480<br />
240/1/60<br />
0.5<br />
NO<br />
THROWAWAY<br />
2.67<br />
6 LBS<br />
1/2"<br />
H X W X D<br />
31-1/4 X 38 X 57<br />
SEE OUTLINE DRAWING<br />
380 / 340<br />
General<br />
Data<br />
YCP024F1M0A<br />
208-230/1/60<br />
24000<br />
800<br />
2.39<br />
10.3 / <strong>12</strong>.00<br />
8.0<br />
72000<br />
57000<br />
79%<br />
35-65<br />
57000<br />
46000<br />
80%<br />
35-65<br />
NATURAL<br />
208-230/1/60<br />
14.8<br />
20<br />
20<br />
CLIMATUFF ®<br />
1<br />
200-230/1/60<br />
9.3 - 62<br />
PLATE FIN<br />
3 / 15<br />
6.34<br />
3/8<br />
PLATE FIN<br />
3 / 15<br />
3.00<br />
3/8<br />
TXV NO BLEED<br />
3/4" FEMALE<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
9 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/4<br />
1080<br />
200-230/1/60<br />
1.6/1.4 - 2.9<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/100 - 2920<br />
208-240/1/60<br />
0.17<br />
NO<br />
THROWAWAY<br />
2.67<br />
7 LBS, 10 OZ<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 57<br />
SEE OUTLINE DRAWING<br />
397 / 357<br />
7<br />
YCP030F1L0A<br />
208-230/1/60<br />
30000<br />
1000<br />
2.83<br />
10.90 / <strong>12</strong>.00<br />
48000<br />
38000<br />
79%<br />
25-55<br />
38000<br />
30000<br />
80%<br />
25-55<br />
NATURAL<br />
208-230/1/60<br />
21.2<br />
30<br />
30<br />
CLIMATUFF ®<br />
1<br />
208-230/1/60<br />
13.4 - 72.5<br />
PLATE FIN<br />
3 / 15<br />
6.34<br />
3/8 COPPER<br />
PLATE FIN<br />
3 / 15<br />
3.97<br />
3/8 COPPER<br />
CAPILLARY<br />
3/4" FEMALE NPT<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
200-230/1/60<br />
2.8/2.2 - 5.1<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/35 - 3480<br />
240/1/60<br />
0.5<br />
NO<br />
THROWAWAY<br />
3.33<br />
6 LBS, 10 OZ<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 57<br />
SEE OUTLINE DRAWING<br />
396 / 356<br />
YCP030F1M0A<br />
208-230/1/60<br />
30000<br />
1000<br />
2.83<br />
10.90 / <strong>12</strong>.050<br />
8.0<br />
72000<br />
57000<br />
79%<br />
35-65<br />
56000<br />
44000<br />
80%<br />
35-65<br />
NATURAL<br />
208-230/1/60<br />
21.2<br />
30<br />
30<br />
CLIMATUFF ®<br />
1<br />
208-230/1/60<br />
13.4 - 72.5<br />
PLATE FIN<br />
2 / 15<br />
6.34<br />
3/8 COPPER<br />
PLATE FIN<br />
3 / 15<br />
3.96<br />
3/8 COPPER<br />
CAPILLARY<br />
3/4" FEMALE NPT<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
200-230/1/60<br />
2.8/2.2 - 5.1<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/35 - 3480<br />
240/1/60<br />
0.5<br />
NO<br />
THROWAWAY<br />
3.33<br />
6 LBS, 10 OZ<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 57<br />
SEE OUTLINE DRAWING<br />
403 / 363<br />
YCP036F1L0A<br />
208-230/1/60<br />
36000<br />
<strong>12</strong>00<br />
3.52<br />
10.45 / <strong>12</strong>.00<br />
8.0<br />
50000<br />
39000<br />
79%<br />
15-45<br />
40000<br />
32000<br />
80%<br />
15-45<br />
NATURAL<br />
208-230/1/60<br />
24.4<br />
40<br />
40<br />
CLIMATUFF ®<br />
1<br />
208-230/1/60<br />
16.0 - 90<br />
PLATE FIN<br />
3 / 15<br />
6.34<br />
3/8 COPPER<br />
PLATE FIN<br />
4 / 15<br />
3.96<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE NPT<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
200-230/1/60<br />
2.8/2.2 - 5.1<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/35 - 3480<br />
240/1/60<br />
0.5<br />
NO<br />
THROWAWAY<br />
4.0<br />
6 LBS, 13 OZ<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 57<br />
SEE OUTLINE DRAWING<br />
4<strong>12</strong> / 372<br />
4 This value is approximate. For more precise value, see Unit Nameplate.<br />
5 Based on U.S. Government Standard Tests.<br />
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If<br />
permanent filters are used size per manufacturer's re<strong>com</strong>mendation with a clean resistance of 0.05" W.C.<br />
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.
MODEL<br />
RATED VOLTS/PH/HZ<br />
RATINGS (COOLING) 1<br />
BTUH<br />
Indoor Airflow (CFM)<br />
Power Input (KW)<br />
EER/<strong>SEER</strong> (BTU/Watt-Hr.)<br />
Noise Rating No. 1<br />
A.G.A. RATINGS (HEATING) 2<br />
(High) Input BTUH<br />
Capacity BTUH 57<br />
AFUE<br />
Temp. Rise °F. (Min./Max.)<br />
(Low) Input BTUH<br />
Capacity BTUH 57<br />
AFUE<br />
Temp. Rise °F. (Min./Max.)<br />
Type of <strong>Gas</strong> 3<br />
POWER CONNS.—V/PH/HZ<br />
Min. Brch. Cir. Ampacity<br />
Br. Cir. Max. (Amps)<br />
Prot. Rtg. Recmd. (Amps)<br />
COMPRESSOR<br />
No. Used<br />
Volts/Ph/Hz<br />
R.L. Amps—L.R. Amps<br />
OUTDOOR COIL—TYPE<br />
Rows / F.P.I.<br />
Face Area (Sq. Ft.)<br />
Tube Size (in.)<br />
INDOOR COIL—TYPE<br />
Rows / F.P.I.<br />
Face Area (Sq. Ft.)<br />
Tube Size (in.)<br />
Refrigerant Control<br />
Drain Conn. Size (in.)<br />
Duct Connections<br />
OUTDOOR FAN—TYPE<br />
No. Used / Dia. (in.)<br />
Type Drive / No. Speeds<br />
No. Motors—HP<br />
Motor Speed R.P.M.<br />
Volts/PH/HZ<br />
F.L. Amps—L.R. Amps<br />
INDOOR FAN—TYPE<br />
Dia. x Width (in.)<br />
No. Used<br />
Drive / Speeds (No.)<br />
No. Motors—HP<br />
Motor Speed R.P.M.<br />
Volts/PH/HZ<br />
F.L Amps<br />
COMBUSTION FAN—TYPE<br />
Drive—Speeds (No.)<br />
Motor HP—Speed (RPM)<br />
Volts/PH/HZ<br />
F.L. Amps<br />
FILTER—FURNISHED?<br />
Type Re<strong>com</strong>mended<br />
Min Face Area-Lo (sq. ft.) 6<br />
REFRIGERANT<br />
Charge (lbs. of R-22) 4<br />
GAS PIPE SIZE (IN.)<br />
DIMENSIONS<br />
Crated (in.)<br />
Uncrated<br />
WEIGHT<br />
Shipping (lbs.) / Net (lbs.)<br />
YCP036F1M0A<br />
208-230/1/60<br />
36000<br />
<strong>12</strong>00<br />
3.52<br />
10.45 / <strong>12</strong>.00<br />
8.0<br />
72000<br />
57000<br />
79%<br />
30-60<br />
60000<br />
48000<br />
80%<br />
30-60<br />
NATURAL<br />
208-230/1/60<br />
24.4<br />
40<br />
40<br />
CLIMATUFF ®<br />
1<br />
208-230/1/60<br />
16.0 - 90<br />
PLATE FIN<br />
3 / 15<br />
6.34<br />
3/8 COPPER<br />
PLATE FIN<br />
4 / 15<br />
3.96<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE NPT<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
200-230/1/60<br />
2.8/2.2 - 5.1<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/35 - 3480<br />
240/1/60<br />
0.5<br />
NO<br />
THROWAWAY<br />
4.0<br />
6 LBS, 13 OZ<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 57<br />
SEE OUTLINE DRAWING<br />
419 / 379<br />
General<br />
Data<br />
YCP036F1H0A<br />
208-230/1/60<br />
36000<br />
<strong>12</strong>00<br />
3.52<br />
10.45 / <strong>12</strong>.00<br />
8.0<br />
96000<br />
76000<br />
79%<br />
40-70<br />
76000<br />
60000<br />
80%<br />
40-70<br />
NATURAL<br />
208-230/1/60<br />
24.4<br />
40<br />
40<br />
CLIMATUFF ®<br />
1<br />
208-230/1/60<br />
16.0 - 90<br />
PLATE FIN<br />
3 / 15<br />
6.34<br />
3/8 COPPER<br />
PLATE FIN<br />
4 / 15<br />
3.96<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE NPT<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
200-230/1/60<br />
2.8/2.2 - 5.1<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-240/1/60<br />
0.4<br />
NO<br />
THROWAWAY<br />
4.0<br />
6 LBS, 13 OZ<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 64-5/8<br />
SEE OUTLINE DRAWING<br />
440 / 393<br />
*See unit nameplate for proper input adjustment<br />
1 Rated in accordance with A.R.I. Standard 210/240. Noise tested in accordance with A.R.I. Standard 270. A.R.I.<br />
standard rating conditions are: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoor coil.<br />
2 All models are UL Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a<br />
rate of 4% per 1000 ft. elevation.<br />
3 Convertible to LPG.<br />
8<br />
YCP036F3L0A<br />
208-230/3/60<br />
36000<br />
<strong>12</strong>00<br />
3.52<br />
10.45 / <strong>12</strong>.00<br />
8.0<br />
50000<br />
39000<br />
79%<br />
15-45<br />
40000<br />
32000<br />
80%<br />
15-45<br />
NATURAL<br />
208-230/3/60<br />
17.4<br />
25<br />
25<br />
CLIMATUFF ®<br />
1<br />
208-230/3/60<br />
10.4 - 88<br />
PLATE FIN<br />
3 / 15<br />
6.34<br />
3/8 COPPER<br />
PLATE FIN<br />
4 / 15<br />
3.96<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE NPT<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
200-230/1/60<br />
2.8/2.2 - 5.1<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/35 - 3480<br />
240/1/60<br />
0.5<br />
NO<br />
THROWAWAY<br />
4.0<br />
6 LBS, 13 OZ<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 57<br />
SEE OUTLINE DRAWING<br />
4<strong>12</strong> / 372<br />
YCP036F3M0A<br />
208-230/3/60<br />
36000<br />
<strong>12</strong>00<br />
3.52<br />
10.45 / <strong>12</strong>.00<br />
8.0<br />
72000<br />
57000<br />
79%<br />
30-60<br />
60000<br />
48000<br />
80%<br />
30-60<br />
NATURAL<br />
208-230/3/60<br />
17.4<br />
25<br />
25<br />
CLIMATUFF ®<br />
1<br />
208-230/1/60<br />
10.4 - 88<br />
PLATE FIN<br />
3 / 15<br />
6.34<br />
3/8 COPPER<br />
PLATE FIN<br />
4 / 15<br />
3.96<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE NPT<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
200-230/1/60<br />
2.8/2.2 - 5.1<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/35 - 3480<br />
240/1/60<br />
0.5<br />
NO<br />
THROWAWAY<br />
4.0<br />
6 LBS, 13 OZ<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 57<br />
SEE OUTLINE DRAWING<br />
419 / 379<br />
YCP036F3H0A<br />
208-230/3/60<br />
36000<br />
<strong>12</strong>00<br />
3.52<br />
10.45 / <strong>12</strong>.00<br />
8.0<br />
96000<br />
76000<br />
79%<br />
40-70<br />
76000<br />
60000<br />
80%<br />
40-70<br />
NATURAL<br />
208-230/3/60<br />
17.4<br />
25<br />
25<br />
CLIMATUFF ®<br />
1<br />
208-230/3/60<br />
10.4 - 88<br />
PLATE FIN<br />
3 / 15<br />
6.34<br />
3/8 COPPER<br />
PLATE FIN<br />
4 / 15<br />
3.96<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE NPT<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
200-230/1/60<br />
2.8/2.2 - 5.1<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-240/1/60<br />
0.4<br />
NO<br />
THROWAWAY<br />
4.0<br />
6 LBS, 13 OZ<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 64-5/8<br />
SEE OUTLINE DRAWING<br />
440 / 393<br />
4 This value is approximate. For more precise value, see Unit Nameplate.<br />
5 Based on U.S. Government Standard Tests.<br />
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If<br />
permanent filters are used size per manufacturer's re<strong>com</strong>mendation with a clean resistance of 0.05" W.C.<br />
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.<br />
Pub. No. 22-1708-01-499 (EN)
MODEL<br />
RATED VOLTS/PH/HZ<br />
RATINGS (COOLING) 1<br />
BTUH<br />
Indoor Airflow (CFM)<br />
Power Input (KW)<br />
EER/<strong>SEER</strong> (BTU/Watt-Hr.)<br />
Noise Rating No. 1<br />
A.G.A. RATINGS (HEATING) 2<br />
(High) Input BTUH<br />
Capacity BTUH 57<br />
AFUE<br />
Temp. Rise °F. (Min./Max.)<br />
(Low) Input BTUH<br />
Capacity BTUH 57<br />
AFUE<br />
Temp. Rise °F. (Min./Max.)<br />
Type of <strong>Gas</strong> 3<br />
POWER CONNS.—V/PH/HZ<br />
Min. Brch. Cir. Ampacity<br />
Br. Cir. Max. (Amps)<br />
Prot. Rtg. Recmd. (Amps)<br />
COMPRESSOR<br />
No. Used<br />
Volts/Ph/Hz<br />
R.L. Amps—L.R. Amps<br />
OUTDOOR COIL—TYPE<br />
Rows / F.P.I.<br />
Face Area (Sq. Ft.)<br />
Tube Size (in.)<br />
INDOOR COIL—TYPE<br />
Rows / F.P.I.<br />
Face Area (Sq. Ft.)<br />
Tube Size (in.)<br />
Refrigerant Control<br />
Drain Conn. Size (in.)<br />
Duct Connections<br />
OUTDOOR FAN—TYPE<br />
No. Used / Dia. (in.)<br />
Type Drive / No. Speeds<br />
No. Motors—HP<br />
Motor Speed R.P.M.<br />
Volts/PH/HZ<br />
F.L. Amps—L.R. Amps<br />
INDOOR FAN—TYPE<br />
Dia. x Width (in.)<br />
No. Used<br />
Drive / Speeds (No.)<br />
No. Motors—HP<br />
Motor Speed R.P.M.<br />
Volts/PH/HZ<br />
F.L Amps<br />
COMBUSTION FAN—TYPE<br />
Drive—Speeds (No.)<br />
Motor HP—Speed (RPM)<br />
Volts/PH/HZ<br />
F.L. Amps<br />
FILTER—FURNISHED?<br />
Type Re<strong>com</strong>mended<br />
Min Face Area-Lo (sq. ft.) 6<br />
REFRIGERANT<br />
Charge (lbs. of R-22) 4<br />
GAS PIPE SIZE (IN.)<br />
DIMENSIONS<br />
Crated (in.)<br />
Uncrated<br />
WEIGHT<br />
Shipping (lbs.) / Net (lbs.)<br />
Pub. No. 22-1708-01-499 (EN)<br />
YCP036F4H0A<br />
460/3/60<br />
37000<br />
<strong>12</strong>00<br />
3.52<br />
10.45 / <strong>12</strong>.00<br />
8.0<br />
96000<br />
76000<br />
79%<br />
40-70<br />
76000<br />
60000<br />
80%<br />
40-70<br />
NATURAL<br />
460/3/60<br />
10.0<br />
15<br />
15<br />
CLIMATUFF ®<br />
1<br />
460/3/60<br />
5.5 - 39.0<br />
PLATE FIN<br />
3 / 15<br />
6.34<br />
3/8 COPPER<br />
PLATE FIN<br />
4 / 15<br />
3.96<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE NPT<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/2<br />
1080<br />
460/1/60<br />
1.5 - 3.8<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
460/1/60<br />
1.1 - 2.6<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-240/1/60<br />
0.4<br />
NO<br />
THROWAWAY<br />
4.0<br />
6 LBS, 13 OZ<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 64-5/8<br />
SEE OUTLINE DRAWING<br />
440 / 393<br />
General<br />
Data<br />
YCP042F1M0A<br />
208-230/1/60<br />
42000<br />
1400<br />
4.09<br />
10.55 / <strong>12</strong>.00<br />
8.0<br />
96000<br />
76000<br />
79%<br />
40-70<br />
76000<br />
60000<br />
80%<br />
40-75<br />
NATURAL<br />
208-230/1/60<br />
26.8<br />
40<br />
40<br />
CLIMATUFF ®<br />
1<br />
208-230/1/60<br />
17.9 - 104<br />
PLATE FIN<br />
2 / 15<br />
11.35<br />
3/8<br />
PLATE FIN<br />
4 / 15<br />
3.97<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
200-230/1/60<br />
2.8/2.2 - 5.1<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-240/1/60<br />
0.4<br />
NO<br />
THROWAWAY<br />
4.67<br />
8 LBS<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 64-5/8<br />
SEE OUTLINE DRAWING<br />
454 / 407<br />
*See unit nameplate for proper input adjustment<br />
1 Rated in accordance with A.R.I. Standard 210/240. Noise tested in accordance with A.R.I. Standard 270. A.R.I.<br />
standard rating conditions are: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoor coil.<br />
2 All models are UL Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a<br />
rate of 4% per 1000 ft. elevation.<br />
3 Convertible to LPG.<br />
9<br />
YCP042F3M0A<br />
208-230/3/60<br />
42000<br />
1400<br />
4.09<br />
10.55 / <strong>12</strong>.00<br />
8.0<br />
96000<br />
76000<br />
79%<br />
40-70<br />
76000<br />
60000<br />
80%<br />
40-70<br />
NATURAL<br />
208-230/3/60<br />
19.9<br />
30<br />
30<br />
CLIMATUFF ®<br />
1<br />
208-230/3/60<br />
<strong>12</strong>.4 - 88<br />
PLATE FIN<br />
2 / 15<br />
11.35<br />
3/8<br />
PLATE FIN<br />
4 / 15<br />
3.97<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 18<br />
DIRECT / 1<br />
1 - 1/5<br />
1080<br />
230/1/60<br />
1.6 - 3.3<br />
CENTRIFUGAL<br />
10 X 9<br />
1<br />
DIRECT / 2<br />
1 - 1/3<br />
1080<br />
200-230/1/60<br />
2.8/2.2 - 5.1<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-240/1/60<br />
0.4<br />
NO<br />
THROWAWAY<br />
4.67<br />
8 LBS<br />
1/2"<br />
H X W X D<br />
35-1/4 X 38 X 64-5/8<br />
SEE OUTLINE DRAWING<br />
454 / 407<br />
YCP048F1H0A<br />
208-230/1/60<br />
47000<br />
1600<br />
4.27<br />
11.45 / <strong>12</strong>.20<br />
8.4<br />
<strong>12</strong>0000<br />
95000<br />
79%<br />
40-70<br />
98000<br />
78000<br />
80%<br />
40-70<br />
NATURAL<br />
208-230/1/60<br />
31.9<br />
50<br />
50<br />
CLIMATUFF ®<br />
1<br />
208-230/1/60<br />
18.3 - 109<br />
PLATE FIN<br />
3 / 15<br />
9.2<br />
3/8<br />
PLATE FIN<br />
3 / 15<br />
5.4<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 22<br />
DIRECT / 1<br />
1 - 1/2<br />
1080<br />
200-230/1/60<br />
3.3/3.9 - 8.5<br />
CENTRIFUGAL<br />
11 X 11<br />
1<br />
DIRECT / 2<br />
1 - 1/2<br />
840<br />
200-230/1/60<br />
3.3 - 6.5<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-240/1/60<br />
0.40<br />
NO<br />
THROWAWAY<br />
5.33<br />
10 LBS , 6 OZ<br />
1/2"<br />
H X W X D<br />
39-3/8 X 47 X 66-1/4<br />
SEE OUTLINE DRAWING<br />
582 / 515<br />
YCP048F3H0A<br />
208-230/3/60<br />
47000<br />
1600<br />
4.27<br />
11.45 / <strong>12</strong>.20<br />
8.4<br />
<strong>12</strong>0000<br />
95000<br />
79%<br />
40-70<br />
98000<br />
78000<br />
80%<br />
40-70<br />
NATURAL<br />
208-230/3/60<br />
24.5<br />
35<br />
35<br />
CLIMATUFF ®<br />
1<br />
208-230/3/60<br />
<strong>12</strong>.4 - 88<br />
PLATE FIN<br />
3 / 15<br />
9.2<br />
3/8<br />
PLATE FIN<br />
3 / 15<br />
5.4<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 22<br />
DIRECT / 1<br />
1 - 1/2<br />
1080<br />
200-230/1/60<br />
3.3/3.9 - 8.5<br />
CENTRIFUGAL<br />
11 X 11<br />
1<br />
DIRECT / 2<br />
1 - 1/2<br />
840<br />
200-230/1/60<br />
3.3 - 6.5<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-240/1/60<br />
0.40<br />
NO<br />
THROWAWAY<br />
10 LBS , 6 OZ<br />
1/2"<br />
H X W X D<br />
39-3/8 X 47 X 66-1/4<br />
SEE OUTLINE DRAWING<br />
582 / 515<br />
4 This value is approximate. For more precise value, see Unit Nameplate.<br />
5 Based on U.S. Government Standard Tests.<br />
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If<br />
permanent filters are used size per manufacturer's re<strong>com</strong>mendation with a clean resistance of 0.05" W.C.<br />
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.
MODEL<br />
RATED VOLTS/PH/HZ<br />
RATINGS (COOLING) 1<br />
BTUH<br />
Indoor Airflow (CFM)<br />
Power Input (KW)<br />
EER/<strong>SEER</strong> (BTU/Watt-Hr.)<br />
Noise Rating No. 1<br />
A.G.A. RATINGS (HEATING) 2<br />
(High) Input BTUH<br />
Capacity BTUH 57<br />
AFUE/CSE*<br />
Temp. Rise °F. (Min./Max.)<br />
(Low) Input BTUH<br />
Capacity BTUH 57<br />
AFUE/CSE*<br />
Temp. Rise °F. (Min./Max.)<br />
Type of <strong>Gas</strong> 3<br />
POWER CONNS.—V/PH/HZ<br />
Min. Brch. Cir. Ampacity<br />
Br. Cir. Max. (Amps)<br />
Prot. Rtg. Recmd. (Amps)<br />
COMPRESSOR<br />
No. Used<br />
Volts/Ph/Hz<br />
R.L. Amps—L.R. Amps<br />
OUTDOOR COIL—TYPE<br />
Rows / F.P.I.<br />
Face Area (Sq. Ft.)<br />
Tube Size (in.)<br />
INDOOR COIL—TYPE<br />
Rows / F.P.I.<br />
Face Area (Sq. Ft.)<br />
Tube Size (in.)<br />
Refrigerant Control<br />
Drain Conn. Size (in.)<br />
Duct Connections<br />
OUTDOOR FAN—TYPE<br />
No. Used / Dia. (in.)<br />
Type Drive / No. Speeds<br />
No. Motors—HP<br />
Motor Speed R.P.M.<br />
Volts/PH/HZ<br />
F.L. Amps—L.R. Amps<br />
INDOOR FAN—TYPE<br />
Dia. x Width (in.)<br />
No. Used<br />
Drive / Speeds (No.)<br />
No. Motors—HP<br />
Motor Speed R.P.M.<br />
Volts/PH/HZ<br />
F.L Amps<br />
COMBUSTION FAN—TYPE<br />
Drive—Speeds (No.)<br />
Motor HP—Speed (RPM)<br />
Volts/PH/HZ<br />
F.L. Amps<br />
FILTER—FURNISHED?<br />
Type Re<strong>com</strong>mended<br />
Min Face Area-Lo (sq. ft.) 6<br />
REFRIGERANT<br />
Charge (lbs. of R-22) 4<br />
GAS PIPE SIZE (IN.)<br />
DIMENSIONS<br />
Crated (in.)<br />
Uncrated<br />
WEIGHT<br />
Shipping (lbs.) / Net (lbs.)<br />
YCP048F4H0A<br />
460/3/60<br />
47000<br />
1600<br />
4.27<br />
11.45 / <strong>12</strong>.20<br />
8.4<br />
<strong>12</strong>0000<br />
95000<br />
79%<br />
40-70<br />
98000<br />
78000<br />
80%<br />
40-70<br />
NATURAL<br />
460/3/60<br />
15.4<br />
20<br />
20<br />
CLIMATUFF ®<br />
1<br />
460/3/60<br />
9.3 - 44<br />
PLATE FIN<br />
3 / 15<br />
9.2<br />
3/8<br />
PLATE FIN<br />
3 / 15<br />
5.4<br />
3/8<br />
CAPILLARY<br />
3/4" FEMALE<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 22<br />
DIRECT / 1<br />
1 - 1/2<br />
1080<br />
460/1/60<br />
1.7 - 3.8<br />
CENTRIFUGAL<br />
11 X 11<br />
1<br />
DIRECT / 2<br />
1 - 1/2<br />
840<br />
460/1/60<br />
1.6 - 2.9<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-240/1/60<br />
0.60<br />
NO<br />
THROWAWAY<br />
5.33<br />
10 LBS , 6 OZ<br />
1/2"<br />
H X W X D<br />
39-3/8 X 47 X 66-1/4<br />
SEE OUTLINE DRAWING<br />
582 / 515<br />
General<br />
Data<br />
*See unit nameplate for proper input adjustment<br />
1 Rated in accordance with A.R.I. Standard 210/240. Noise tested in accordance with A.R.I. Standard 270. A.R.I.<br />
standard rating conditions are: 80 D.B. 67 W.B. entering air to indoor coil. 95 D.B. entering air to outdoor coil.<br />
2 All models are UL Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a<br />
rate of 4% per 1000 ft. elevation.<br />
3 Convertible to LPG.<br />
YCP060F1M0A<br />
208-230/1/60<br />
60000<br />
2000<br />
5.84<br />
10.55 / <strong>12</strong>.00<br />
8.4<br />
<strong>12</strong>2000<br />
97000<br />
79%<br />
30-60<br />
100000<br />
80000<br />
80%<br />
30-60<br />
NATURAL<br />
208-230/1/60<br />
45.0<br />
70<br />
70<br />
CLIMATUFF ®<br />
1<br />
208-230/1/60<br />
28.8 - 169.0<br />
PLATE FIN<br />
2 / 22<br />
15.0<br />
3/8<br />
PLATE FIN<br />
4 / 15<br />
5.4<br />
3/8<br />
TXV-NB<br />
3/4" FEMALE<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 22<br />
DIRECT / 1<br />
1 - 1/2<br />
1080<br />
200-230/1/60<br />
3.3/3.9 - 8.5<br />
CENTRIFUGAL<br />
11 X 11<br />
1<br />
DIRECT / 2<br />
1 - 3/4<br />
200-230/1/60<br />
5.0/4.3 - 9.7<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-230/1/60<br />
0.4<br />
NO<br />
THROWAWAY<br />
6.67<br />
10 LBS<br />
1/2"<br />
H X W X D<br />
39-3/8 X 47 X 64-1/4<br />
SEE OUTLINE DRAWING<br />
609 / 542<br />
10<br />
YCP060F3M0A<br />
208-230/3/60<br />
60000<br />
2000<br />
5.84<br />
10.55 / <strong>12</strong>.00<br />
8.4<br />
<strong>12</strong>2000<br />
97000<br />
79%<br />
30-60<br />
100000<br />
80000<br />
80%<br />
30-60<br />
NATURAL<br />
208-230/3/60<br />
30.6<br />
45<br />
45<br />
CLIMATUFF ®<br />
1<br />
208-230/3/60<br />
17.3 - <strong>12</strong>3<br />
PLATE FIN<br />
2 / 22<br />
15.0<br />
3/8<br />
PLATE FIN<br />
4 / 15<br />
5.4<br />
3/8<br />
TXV-NB<br />
3/4" FEMALE<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 22<br />
DIRECT / 1<br />
1 - 1/2<br />
1080<br />
200-230/1/60<br />
3.3/3.9 - 8.5<br />
CENTRIFUGAL<br />
11 X 11<br />
1<br />
DIRECT / 2<br />
1 - 3/4<br />
200-230/1/60<br />
5.0/4.3 - 9.7<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-230/1/60<br />
0.4<br />
NO<br />
THROWAWAY<br />
6.67<br />
10 LBS<br />
1/2"<br />
H X W X D<br />
39-3/8 X 47 X 64-1/4<br />
SEE OUTLINE DRAWING<br />
609 / 542<br />
YCP060F4M0A<br />
460/3/60<br />
60000<br />
2000<br />
5.84<br />
10.55 / <strong>12</strong>.00<br />
8.4<br />
<strong>12</strong>2000<br />
97000<br />
79%<br />
30-60<br />
100000<br />
80000<br />
80%<br />
30-60<br />
NATURAL<br />
460/3/60<br />
15.1<br />
20<br />
20<br />
CLIMATUFF ®<br />
1<br />
460/3/60<br />
9.0 - 62<br />
PLATE FIN<br />
2 / 22<br />
15.0<br />
3/8<br />
PLATE FIN<br />
4 / 15<br />
5.4<br />
3/8<br />
TXV-NB<br />
3/4" FEMALE<br />
SEE OUTLINE DRAWING<br />
PROPELLER<br />
1 / 22<br />
DIRECT / 1<br />
1 - 1/2<br />
1080<br />
460/1/60<br />
1.7 - 3.8<br />
CENTRIFUGAL<br />
11 X 11<br />
1<br />
DIRECT /<br />
1 - 3/4<br />
4601/60<br />
2.1 - 4.8p<br />
CENTRIFUGAL<br />
DIRECT - 1<br />
1/50 - 3030<br />
208-230/1/60<br />
0.4<br />
NO<br />
THROWAWAY<br />
6.67<br />
10 LBS<br />
1/2"<br />
H X W X D<br />
39-3/8 X 47 X 64-1/4<br />
SEE OUTLINE DRAWING<br />
609 / 542<br />
4 This value is approximate. For more precise value, see Unit Nameplate.<br />
5 Based on U.S. Government Standard Tests.<br />
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If<br />
permanent filters are used size per manufacturer's re<strong>com</strong>mendation with a clean resistance of 0.05" W.C.<br />
7 Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.<br />
Pub. No. 22-1708-01-499 (EN)
Pub. No. 22-1708-01-499 (EN)<br />
Performance Data<br />
Cooling<br />
YCP024F1L0A AT 800 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP.DEW<br />
D.B. W.B. CAP. 72 74 76 78 80 KW PT.<br />
59 21.4 17.3 18.7 20.1 21.5* 22.1* 1.59 46.1<br />
85 63 23.2 14.5 15.9 17.4 18.8 20.2 1.63 49.9<br />
67 25.1 11.5 <strong>12</strong>.9 14.3 15.8 17.2 1.68 54.0<br />
71 27.1 8.3 9.8 11.2 <strong>12</strong>.6 14.1 1.74 58.2<br />
59 20.9 17.0 18.5 19.9 21.1* 21.7* 1.66 46.4<br />
90 63 22.7 14.3 15.7 17.1 18.6 20.0 1.70 50.3<br />
67 24.5 11.2 <strong>12</strong>.6 14.1 15.5 16.9 1.76 54.4<br />
71 26.4 8.1 9.5 10.9 <strong>12</strong>.4 13.8 1.81 58.6<br />
59 20.4 16.8 18.2 19.7 20.7* 21.2* 1.73 46.8<br />
95 63 22.1 14.0 15.5 16.9 18.3 19.8 1.78 50.6<br />
67 23.8 10.9 <strong>12</strong>.4 13.8 15.2 16.7 1.83 54.8<br />
71 25.6 7.8 9.2 10.7 <strong>12</strong>.1 13.5 1.88 59.0<br />
59 19.9 16.6 18.0 19.4 20.3* 20.8* 1.80 47.1<br />
100 63 21.4 13.8 15.2 16.6 18.1 19.5 1.85 51.0<br />
67 23.1 10.7 <strong>12</strong>.1 13.5 15.0 16.4 1.90 55.2<br />
71 24.8 7.5 9.0 10.4 11.8 13.3 1.95 59.5<br />
59 19.3 16.3 17.8 19.2 19.8* 20.3* 1.87 47.5<br />
105 63 20.8 13.5 15.0 16.4 17.8 19.3 1.92 51.4<br />
67 22.4 10.4 11.8 13.3 14.7 16.2 1.97 55.6<br />
71 24.0 7.2 8.7 10.1 11.6 13.0 2.03 59.9<br />
59 18.2 15.9 17.3 18.4* 18.8* 19.3* 2.02 48.2<br />
115 63 19.5 13.0 14.4 15.9 17.3 18.8 2.07 52.2<br />
67 21.0 9.9 11.3 <strong>12</strong>.8 14.2 15.6 2.<strong>12</strong> 56.4<br />
71 22.5 6.7 8.1 9.6 11.0 <strong>12</strong>.4 2.17 60.7<br />
11<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 700 900<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.94 X1.06<br />
COMPR. KW X0.99 X1.01<br />
A.D.P. -1.4 1.1<br />
VALUES AT ARI RATING CONDITIONS<br />
TOTAL NET CAPACITY = 23800 BTUH<br />
AIRFLOW = 800 CFM<br />
APP. DEW PT. = 54.8 DEG. F<br />
COMPRESSOR POWER = 1827 WATTS<br />
I.D. FAN POWER = 300 WATTS<br />
O.D. FAN POWER = 250 WATTS<br />
S.E.E.R. = <strong>12</strong>.00 BTUH/WATT<br />
E.E.R. = 10.25 BTUH/WATT<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
YCP024F1M0A AT 800 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP.DEW<br />
D.B. W.B. CAP. 72 74 76 78 80 KW PT.<br />
59 21.1 16.5 17.9 19.3 20.7 21.5* 1.61 45.3<br />
85 63 22.8 13.9 15.3 16.6 18.0 19.4 1.65 49.1<br />
67 24.7 10.9 <strong>12</strong>.3 13.7 15.1 16.4 1.70 53.2<br />
71 26.6 7.9 9.3 10.7 <strong>12</strong>.1 13.4 1.76 57.4<br />
59 20.7 16.4 17.7 19.1 20.5 21.2* 1.68 45.5<br />
90 63 22.4 13.7 15.1 16.4 17.8 19.2 1.72 49.4<br />
67 24.1 10.7 <strong>12</strong>.1 13.5 14.8 16.2 1.78 53.5<br />
71 25.9 7.7 9.1 10.4 11.8 13.2 1.83 57.8<br />
59 20.3 16.2 17.6 18.9 20.3* 20.8* 1.75 45.8<br />
95 63 21.9 13.5 14.9 16.2 17.6 19.0 1.80 49.7<br />
67 23.5 10.5 11.9 13.3 14.6 16.0 1.85 53.9<br />
71 25.2 7.5 8.8 10.2 11.6 13.0 1.90 58.2<br />
59 19.7 16.0 17.3 18.7 19.9* 20.4* 1.82 46.2<br />
100 63 21.2 13.2 14.6 16.0 17.4 18.8 1.87 50.1<br />
67 22.8 10.2 11.6 13.0 14.4 15.8 1.92 54.3<br />
71 24.4 7.2 8.6 9.9 11.3 <strong>12</strong>.7 1.97 58.6<br />
59 19.2 15.7 17.1 18.5 19.5* 19.9* 1.90 46.5<br />
105 63 20.6 13.0 14.4 15.8 17.1 18.5 1.94 50.5<br />
67 22.1 10.0 11.4 <strong>12</strong>.8 14.1 15.5 2.00 54.7<br />
71 23.6 6.9 8.3 9.7 11.1 <strong>12</strong>.4 2.05 59.0<br />
59 18.1 15.3 16.7 18.0 18.6* 19.0* 2.05 47.3<br />
115 63 19.4 <strong>12</strong>.5 13.9 15.3 16.7 18.0 2.10 51.3<br />
67 20.7 9.5 10.9 <strong>12</strong>.2 13.6 15.0 2.14 55.5<br />
71 22.1 6.4 7.8 9.2 10.5 11.9 2.19 59.9<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 700 900<br />
TOTAL CAP. X0.98 X1.02<br />
SENS. CAP. X0.94 X1.06<br />
COMPR. KW X0.99 X1.01<br />
A.D.P. -1.3 1.1<br />
VALUES AT ARI RATING CONDITIONS<br />
TOTAL NET CAPACITY = 23500 BTUH<br />
AIRFLOW = 800 CFM<br />
APP. DEW PT. = 53.9 DEG. F<br />
COMPRESSOR POWER = 1846 WATTS<br />
I.D. FAN POWER = 300 WATTS<br />
O.D. FAN POWER = 250 WATTS<br />
S.E.E.R. = <strong>12</strong>.00 BTUH/WATT<br />
E.E.R. = 10.3 BTUH/WATT<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
YCP030F—A AT 1000 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP.DEW<br />
D.B. W.B. CAP. 72 74 76 78 80 KW PT.<br />
59 26.5 21.4 23.2 25.1 26.7* 27.3* 1.92 46.1<br />
85 63 28.5 17.7 19.5 21.4 23.3 25.1 1.94 50.1<br />
67 30.6 13.6 15.5 17.4 19.2 21.1 1.96 54.4<br />
71 32.7 9.5 11.4 13.3 15.1 17.0 1.98 58.7<br />
59 26.3 21.3 23.1 25.0 26.5* 27.1* 2.03 46.3<br />
90 63 28.2 17.6 19.4 21.3 23.1 25.0 2.05 50.2<br />
67 30.3 13.5 15.4 17.3 19.1 21.0 2.07 54.5<br />
71 32.4 9.4 11.3 13.2 15.0 16.9 2.09 58.8<br />
59 26.0 21.1 23.0 24.9 26.3* 26.9* 2.15 46.4<br />
95 63 28.0 17.5 19.3 21.2 23.0 24.9 2.17 50.3<br />
67 30.0 13.4 15.3 17.2 19.0 20.9 2.19 54.6<br />
71 32.1 9.3 11.2 13.1 14.9 16.8 2.21 58.9<br />
59 25.5 20.9 22.8 24.7 25.9* 26.5* 2.29 46.6<br />
100 63 27.4 17.3 19.1 21.0 22.8 24.7 2.31 50.6<br />
67 29.4 13.2 15.1 17.0 18.8 20.7 2.33 54.8<br />
71 31.5 9.1 11.0 <strong>12</strong>.9 14.7 16.6 2.35 59.2<br />
59 25.0 20.7 22.6 24.4 25.5* 26.1* 2.43 46.9<br />
105 63 26.9 17.0 18.9 20.8 22.6 24.5 2.45 50.8<br />
67 28.9 13.0 14.9 16.7 18.6 20.5 2.47 55.1<br />
71 30.9 8.9 10.8 <strong>12</strong>.7 14.5 16.4 2.50 59.4<br />
59 24.0 20.3 22.2 24.1* 24.7* 25.2* 2.72 47.3<br />
115 63 25.8 16.6 18.5 20.4 22.2 24.1 2.74 51.3<br />
67 27.7 <strong>12</strong>.6 14.5 16.3 18.2 20.1 2.76 55.5<br />
71 29.7 8.5 10.4 <strong>12</strong>.2 14.1 16.0 2.78 59.9<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 875 1100<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.94 X1.05<br />
COMPR. KW X0.99 X1.00<br />
A.D.P. -1.3 0.9<br />
VALUES AT ARI RATING CONDITIONS<br />
TOTAL NET CAPACITY = 30000 BTUH<br />
AIRFLOW = 1000 CFM<br />
APP. DEW PT. = 54.6 DEG. F<br />
COMPRESSOR POWER = 2189 WATTS<br />
I.D. FAN POWER = 390 WATTS<br />
O.D. FAN POWER = 250 WATTS<br />
S.E.E.R. = <strong>12</strong>.00 BTUH/WATT<br />
E.E.R. = 10.9 BTUH/WATT<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.
Performance Data<br />
Cooling<br />
YCP036F—A AT <strong>12</strong>00 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP.DEW<br />
D.B. W.B. CAP. 72 74 76 78 80 KW PT.<br />
59 32.2 26.2 28.4 30.6 32.5* 33.2* 2.41 46.4<br />
85 63 34.5 21.7 23.9 26.2 28.4 30.6 2.45 50.4<br />
67 36.9 16.8 19.0 21.3 23.5 25.7 2.48 54.7<br />
71 39.4 11.8 14.0 16.3 18.5 20.8 2.52 59.0<br />
59 31.9 26.0 28.2 30.5 32.2* 32.9* 2.56 46.5<br />
90 63 34.1 21.5 23.8 26.0 28.2 30.5 2.60 50.5<br />
67 36.5 16.6 18.8 21.1 23.3 25.6 2.64 54.8<br />
71 38.9 11.6 13.8 16.1 18.3 20.6 2.68 59.2<br />
59 31.5 25.9 28.1 30.3 31.9* 32.6* 2.71 46.7<br />
95 63 33.7 21.4 23.6 25.8 28.1 30.3 2.75 50.7<br />
67 36.0 16.4 18.7 20.9 23.2 25.4 2.80 55.0<br />
71 38.4 11.4 13.7 15.9 18.1 20.4 2.85 59.4<br />
59 30.8 25.6 27.8 30.0 31.3* 32.0* 2.89 47.0<br />
100 63 32.9 21.0 23.3 25.5 27.8 30.0 2.93 51.0<br />
67 35.1 16.1 18.3 20.6 22.8 25.1 2.99 55.3<br />
71 37.4 11.1 13.3 15.6 17.8 20.1 3.04 59.7<br />
59 30.1 25.3 27.5 29.7 30.7* 31.4* 3.06 47.2<br />
105 63 32.1 20.7 23.0 25.2 27.5 29.7 3.<strong>12</strong> 51.3<br />
67 34.3 15.8 18.0 20.3 22.5 24.7 3.17 55.6<br />
71 36.4 10.8 13.0 15.2 17.5 19.7 3.23 60.0<br />
59 28.6 24.6 26.9 28.8* 29.5* 30.1* 3.41 47.8<br />
115 63 30.5 20.1 22.3 24.6 26.8 29.1 3.48 51.9<br />
67 32.5 15.1 17.4 19.6 21.9 24.1 3.55 56.2<br />
71 34.5 10.1 <strong>12</strong>.4 14.6 16.8 19.1 3.62 60.6<br />
YCP042F—A AT 1400 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)<br />
O.D. I.D. TOTALSENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP.DEW<br />
D.B. W.B. CAP. 72 74 76 78 80 KW PT.<br />
59 37.5 30.5 33.1 35.7 37.9* 38.7* 2.78 46.4<br />
85 63 40.2 25.3 27.9 30.5 33.1 35.7 2.83 50.4<br />
67 43.0 19.6 22.2 24.8 27.4 30.0 2.88 54.7<br />
71 45.8 13.8 16.4 19.0 21.6 24.2 2.93 59.1<br />
59 37.2 30.3 32.9 35.5 37.6* 38.4* 2.96 46.5<br />
90 63 39.8 25.1 27.7 30.3 32.9 35.5 3.01 50.5<br />
67 42.5 19.4 22.0 24.6 27.2 29.8 3.07 54.8<br />
71 45.3 13.6 16.2 18.8 21.4 24.0 3.<strong>12</strong> 59.2<br />
59 36.8 30.2 32.8 35.4 37.3* 38.1* 3.14 46.7<br />
95 63 39.4 24.9 27.5 30.1 32.7 35.3 3.20 50.7<br />
67 42.0 19.2 21.8 24.4 27.0 29.6 3.26 55.0<br />
71 44.7 13.4 16.0 18.6 21.2 23.8 3.32 59.4<br />
59 35.9 29.8 32.4 35.0 36.5* 37.3* 3.35 47.0<br />
100 63 38.4 24.6 27.2 29.8 32.4 34.9 3.41 51.0<br />
67 41.0 18.8 21.4 24.0 26.6 29.2 3.48 55.3<br />
71 43.6 13.0 15.6 18.2 20.8 23.4 3.54 59.7<br />
59 35.1 29.4 32.0 34.6 35.8* 36.6* 3.55 47.3<br />
105 63 37.5 24.2 26.8 29.4 32.0 34.6 3.62 51.3<br />
67 39.9 18.4 21.0 23.6 26.2 28.8 3.69 55.6<br />
71 42.5 <strong>12</strong>.6 15.2 17.8 20.4 23.0 3.77 60.1<br />
59 33.3 28.7 31.3 33.6* 34.3* 35.0* 3.95 47.9<br />
115 63 35.5 23.4 26.0 28.6 31.2 33.8 4.04 51.9<br />
67 37.8 17.7 20.3 22.9 25.5 28.1 4.13 56.3<br />
71 40.2 11.8 14.4 17.0 19.6 22.2 4.23 60.7<br />
<strong>12</strong><br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1050 1350<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.94 X1.06<br />
COMPR. KW X0.99 X1.01<br />
A.D.P. -1.4 1.1<br />
VALUES AT ARI RATING CONDITIONS<br />
TOTAL NET CAPACITY = 36000 BTUH<br />
AIRFLOW = <strong>12</strong>00 CFM<br />
APP. DEW PT. = 55.0 DEG. F<br />
COMPRESSOR POWER = 2799 WATTS<br />
I.D. FAN POWER = 475 WATTS<br />
O.D. FAN POWER = 250 WATTS<br />
S.E.E.R. = <strong>12</strong>.00 BTUH/WATT<br />
E.E.R. = 10.45 BTUH/WATT<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW <strong>12</strong>25 1575<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.94 X1.06<br />
COMPR. KW X0.99 X1.01<br />
A.D.P. -1.4 1.1<br />
VALUES AT ARI RATING CONDITIONS<br />
TOTAL NET CAPACITY = 42000 BTUH<br />
AIRFLOW = 1400 CFM<br />
APP. DEW PT. = 55.0 DEG. F<br />
COMPRESSOR POWER = 3257 WATTS<br />
I.D. FAN POWER = 580 WATTS<br />
O.D. FAN POWER = 250 WATTS<br />
S.E.E.R. = <strong>12</strong>.00 BTUH/WATT<br />
E.E.R. = 10.55 BTUH/WATT<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
YCP048F—A AT 1600 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP.DEW<br />
D.B. W.B. CAP. 72 74 76 78 80 KW PT.<br />
59 41.1 34.2 37.1 39.9 41.8* 42.7* 2.79 47.0<br />
85 63 44.1 28.5 31.4 34.2 37.1 39.9 2.82 51.0<br />
67 47.2 22.3 25.1 28.0 30.8 33.7 2.85 55.2<br />
71 50.4 15.9 18.7 21.6 24.4 27.3 2.88 59.6<br />
59 41.1 34.2 37.0 39.9 41.7* 42.7* 2.97 47.1<br />
90 63 44.0 28.5 31.4 34.2 37.1 39.9 3.00 51.0<br />
67 47.1 22.2 25.1 27.9 30.8 33.6 3.03 55.3<br />
71 50.3 15.8 18.7 21.5 24.4 27.2 3.06 59.6<br />
59 41.0 34.2 37.0 39.9 41.7* 42.6* 3.14 47.1<br />
95 63 44.0 28.5 31.3 34.2 37.0 39.9 3.18 51.0<br />
67 47.0 22.2 25.0 27.9 30.7 33.6 3.22 55.3<br />
71 50.1 15.8 18.6 21.5 24.3 27.2 3.25 59.6<br />
59 40.3 33.9 36.7 39.6 41.1* 42.1* 3.35 47.3<br />
100 63 43.2 28.2 31.0 33.9 36.7 39.6 3.39 51.3<br />
67 46.2 21.9 24.7 27.6 30.4 33.3 3.43 55.5<br />
71 49.3 15.5 18.3 21.2 24.0 26.9 3.48 59.9<br />
59 39.7 33.6 36.4 39.3 40.6* 41.5* 3.56 47.5<br />
105 63 42.5 27.9 30.7 33.6 36.4 39.3 3.61 51.5<br />
67 45.4 21.6 24.4 27.3 30.1 33.0 3.65 55.8<br />
71 48.4 15.2 18.0 20.9 23.7 26.6 3.70 60.1<br />
59 38.3 33.0 35.8 38.4* 39.4* 40.3* 3.97 48.0<br />
115 63 41.0 27.3 30.1 33.0 35.8 38.7 4.03 52.0<br />
67 43.8 21.0 23.8 26.7 29.5 32.4 4.09 56.3<br />
71 46.7 14.5 17.4 20.2 23.1 26.0 4.16 60.6<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1400 1800<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.95 X1.05<br />
COMPR. KW X0.99 X1.01<br />
A.D.P. -1.5 1.1<br />
VALUES AT ARI RATING CONDITIONS<br />
TOTAL NET CAPACITY = 47000 BTUH<br />
AIRFLOW = 1600 CFM<br />
APP. DEW PT. = 55.3 DEG. F<br />
COMPRESSOR POWER = 3215 WATTS<br />
I.D. FAN POWER = 550 WATTS<br />
O.D. FAN POWER = 500 WATTS<br />
S.E.E.R. = <strong>12</strong>.20 BTUH/WATT<br />
E.E.R. = 11.45 BTUH/WATT<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
Pub. No. 22-1708-01-499 (EN)
Pub. No. 22-1708-01-499 (EN)<br />
Performance Data<br />
Cooling<br />
YCP060F—A AT 2000 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED)<br />
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. APP.DEW<br />
D.B. W.B. CAP. 72 74 76 78 80 KW PT.<br />
59 54.3 43.9 47.6 51.3 54.7* 56.0* 3.84 46.3<br />
85 63 58.4 36.5 40.3 44.0 47.7 51.4 3.88 50.3<br />
67 62.6 28.4 32.2 35.9 39.6 43.3 3.92 54.5<br />
71 67.0 20.2 23.9 27.6 31.3 35.1 3.96 58.8<br />
59 53.1 43.4 47.1 50.8 53.7* 55.0* 4.07 46.6<br />
90 63 57.1 36.0 39.8 43.5 47.2 50.9 4.11 50.6<br />
67 61.3 27.9 31.7 35.4 39.1 42.8 4.15 54.8<br />
71 65.6 19.7 23.4 27.1 30.9 34.6 4.20 59.1<br />
59 51.9 42.9 46.6 50.3 52.8* 54.0* 4.29 46.9<br />
95 63 55.9 35.5 39.3 43.0 46.7 50.4 4.34 50.9<br />
67 60.0 27.4 31.2 34.9 38.6 42.3 4.39 55.1<br />
71 64.3 19.2 22.9 26.6 30.4 34.1 4.44 59.4<br />
59 50.6 42.3 46.1 49.8 51.7* 53.0* 4.56 47.2<br />
100 63 54.5 35.0 38.7 42.4 46.1 49.9 4.62 51.2<br />
67 58.5 26.9 30.6 34.3 38.0 41.8 4.67 55.4<br />
71 62.7 18.6 22.4 26.1 29.8 33.5 4.73 59.8<br />
59 49.3 41.8 45.5 49.2 50.6* 51.9* 4.83 47.6<br />
105 63 53.1 34.4 38.1 41.8 45.6 49.3 4.89 51.5<br />
67 57.0 26.3 30.0 33.8 37.5 41.2 4.95 55.8<br />
71 61.1 18.1 21.8 25.5 29.3 33.0 5.02 60.1<br />
59 46.7 40.7 44.4 47.3* 48.5* 49.6* 5.37 48.2<br />
115 63 50.3 33.3 37.0 40.7 44.5 48.2 5.44 52.2<br />
67 54.1 25.2 28.9 32.7 36.4 40.1 5.52 56.4<br />
71 58.0 17.0 20.7 24.4 28.2 31.9 5.60 60.7<br />
CFM<br />
700<br />
800<br />
875<br />
900<br />
1000<br />
1050<br />
1<strong>12</strong>5<br />
<strong>12</strong>00<br />
<strong>12</strong>25<br />
1350<br />
1400<br />
1575<br />
1600<br />
1750<br />
1800<br />
2000<br />
2250<br />
<br />
<br />
<br />
Performance Data<br />
Indoor Fan<br />
TEMPERATURE RISE F - 80% S.S. EFFICIENCY 300 - 500 CFM/TON<br />
BASED ON TR =<br />
BTU (.80)<br />
1.08 CFM<br />
13<br />
CORRECTION FACTORS - OTHER AIRFLOWS<br />
(MULTIPLY OR ADD AS INDICATED)<br />
AIRFLOW 1750 2250<br />
TOTAL CAP. X0.98 X1.01<br />
SENS. CAP. X0.94 X1.05<br />
COMPR. KW X1.00 X1.00<br />
A.D.P. -1.4 1.2<br />
VALUES AT ARI RATING CONDITIONS<br />
TOTAL NET CAPACITY = 60000 BTUH<br />
AIRFLOW = 2000 CFM<br />
APP. DEW PT. = 55.1 DEG. F<br />
COMPRESSOR POWER = 4388 WATTS<br />
I.D. FAN POWER = 950 WATTS<br />
O.D. FAN POWER = 500 WATTS<br />
S.E.E.R. = <strong>12</strong>.00 BTUH/WATT<br />
E.E.R. = 10.55 BTUH/WATT<br />
* DRY COIL CONDITION (TOTAL CAPACITY =<br />
SENSIBLE CAPACITY)<br />
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.<br />
ARE VALID ONLY FOR WET COIL<br />
ALL TEMPERATURES IN DEGREES F.<br />
YCP/YCX024*L YCP/YCX024*M YCP/YCX030*L YCP/YCX030*M YCP/YCX036*L YCP/YCX036*M YCP/YCX036*H YCP/YCX042*M YCP/YCX048*H<br />
2.0 TONS<br />
2.0 TONS<br />
2.5 TONS<br />
2.5 TONS<br />
3.0 TONS<br />
3.0 TONS<br />
3.0 TONS<br />
3.5 TONS<br />
4.0 TONS<br />
800 CFM NOM<br />
800 CFM NOM<br />
1000 CFM NOM<br />
1000 CFM NOM<br />
<strong>12</strong>00 CFM NOM<br />
<strong>12</strong>00 CFM NOM<br />
<strong>12</strong>00 CFM NOM<br />
1400 CFM NOM<br />
1600 CFM NOM<br />
HTG - INPUT<br />
HTG - INPUT<br />
HTG - INPUT<br />
HTG - INPUT<br />
HTG - INPUT<br />
HTG - INPUT<br />
HTG - INPUT<br />
HTG - INPUT<br />
HTG - INPUT<br />
38000 48000<br />
57000 72000<br />
38000 48000<br />
56000 72000<br />
40000 50000<br />
60000 72000<br />
76000 96000<br />
76000 96000<br />
98000 <strong>12</strong>0000<br />
40.2 50.8 60.3<br />
- 40.2 50.8 59.3 - 42.3 - 63.5 -<br />
- -<br />
- -<br />
- -<br />
35.2 44.4 52.8 66.7 35.2 44.4 51.9 66.7 37.0 46.3 55.6 66.7 70.4<br />
- 70.4<br />
-<br />
-<br />
-<br />
32.2 40.6 48.3 61.0 32.2 40.6 47.4 61.0 33.9 42.3 50.8 61.0 64.3<br />
- 64.3<br />
-<br />
-<br />
-<br />
31.3 39.5 46.9 59.3 31.3 39.5 46.1 59.3 32.9 41.2 49.4 59.3 62.6<br />
- 62.6<br />
-<br />
-<br />
-<br />
28.1 35.6 42.2 53.3 28.1 35.6 41.5 53.3 29.6 37.0 44.4 53.3 56.3 71.1 56.3 71.1 72.6<br />
-<br />
- 33.9 40.2 50.8 26.8 33.9 39.5 50.8 28.2 35.3 42.3 50.8 53.6 67.7 53.6 67.7 69.1<br />
-<br />
- 31.6 37.5 47.4 25.0 31.6 36.9 47.4 26.3 32.9 39.5 47.4 50.0 63.2 50.0 63.2 64.5<br />
-<br />
- 29.6 35.2 44.4 23.5 29.6 34.6 44.4 24.7 30.9 37.0 44.4 46.9 59.3 46.9 59.3 60.5<br />
-<br />
- 29.0 34.5 43.5<br />
- 29.0<br />
- 43.5 24.2 30.2 36.3 43.5 46.0 58.0 46.0 58.0 59.3 72.6<br />
_ _<br />
- 39.5<br />
- 26.3<br />
- 39.5 21.9 27.4 32.9 39.5 41.7 52.7 41.7 52.7 53.8 65.8<br />
_ _<br />
_ 38.1<br />
- 25.4<br />
- 38.1 21.2 26.5 31.7 38.1 40.2 50.8 40.2 50.8 51.9 63.5<br />
_ _<br />
_ 33.9<br />
- 22.6<br />
- 33.9 18.8 23.5 28.2 33.9 35.7 45.1<br />
- 45.1 46.1 56.4<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
- 18.5 23.1<br />
- 33.3<br />
- 44.4<br />
- 44.4 45.4 55.6<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
- 16.9 21.2<br />
- 30.5<br />
- 40.6<br />
- 40.6 41.5 50.8<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
- 16.5 20.6<br />
- 29.6<br />
- 39.5<br />
- 39.5 40.3 49.4<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
- 14.8 18.5<br />
-<br />
-<br />
-<br />
-<br />
-<br />
- 36.3 44.4<br />
-<br />
-<br />
-<br />
-<br />
- -<br />
-<br />
-<br />
- 16.5<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
- 39.5<br />
-<br />
-<br />
- -<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
- - -<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
NOTE: TEMPERATURE RISE OUTSIDE OF DARKENED BORDER IS NOT<br />
WITHIN RECOMMENDED NAMEPLATE OPERATING SPECIFICATIONS.<br />
YCP/YCX060*M<br />
5.0 TONS<br />
2000 CFM NOM<br />
HTG - INPUT<br />
100000 <strong>12</strong>2000<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
61.7<br />
60.5<br />
54.9<br />
- -<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
52.9 64.6<br />
47.0 57.4<br />
46.3 56.5<br />
42.3 51.6<br />
41.2 50.2<br />
37.0 45.2<br />
32.9 40.2<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-
Performance Data<br />
Indoor Fan<br />
YCP024F TCP024F YCP030F TCP030F<br />
YCP036F TCP036F<br />
667772<br />
14<br />
YCP042F TCP042F<br />
730859<br />
Pub. No. 22-1708-01-499 (EN)
Pub. No. 22-1708-01-499 (EN)<br />
YCP036F-L<br />
YCP048F-H<br />
7309<strong>12</strong><br />
Performance Data<br />
Indoor Fan<br />
YCP030F-M<br />
YCP036F-M,H<br />
YCP042F-M<br />
15<br />
730915<br />
YCP060F TCP060F<br />
YCP048F-H<br />
YCP060F-M<br />
730904<br />
730923
Optional<br />
Equipment<br />
BAYECON073A Horizontal Economizer and Rain Hood<br />
16<br />
Pub. No. 22-1708-01-499 (EN)
Pub. No. 22-1708-01-499 (EN)<br />
ECONOMIZER<br />
MODEL<br />
APPLICATION<br />
MODELS<br />
Optional<br />
Equipment<br />
Economizer and Rain Hood<br />
(Downflow Applications)<br />
A B C D E F G H<br />
BAYECON054B YCP024-042F 20 16-5/8 23-1/2 22-9/16 8-5/8 22-1/4 25-1/8 1-1/2<br />
BAYECON055B YCP048-060F 20 21 26 OMIT <strong>12</strong>-1/8 26-1/8 32-1/8 1-3/4<br />
17
Field<br />
Wiring<br />
Field Wiring for YCP-F Cooling Models<br />
18<br />
From Dwg. 21C756979 Rev. 1<br />
Pub. No. 22-1708-01-499 (EN)
Pub. No. 22-1708-01-499 (EN)<br />
Field<br />
Wiring<br />
Wiring Diagram for Typical <strong>Units</strong><br />
continued on next page<br />
19<br />
From Dwg. 21D757307 P04
Field<br />
Wiring<br />
Wiring Diagram for Typical <strong>Units</strong><br />
20<br />
From Dwg. 21D757307 P04<br />
Pub. No. 22-1708-01-499 (EN)
Pub. No. 22-1708-01-499 (EN)<br />
Dimensions<br />
BAYCURB030A,038A Roof Curb Outline With YCP024,060F <strong>Units</strong><br />
MODEL NO.<br />
AIR DUCT<br />
OPENINGS<br />
A B C D E<br />
YCP024-36F-L<br />
YCP024-36F-M<br />
SUPPLY<br />
RETURN<br />
21<br />
-<br />
11-1/4 - -<br />
14-3/4<br />
- 11-1/2 18-1/8<br />
YCP036F-H<br />
YCP042F-M<br />
SUPPLY<br />
RETURN<br />
21<br />
-<br />
16-3/4<br />
-<br />
-<br />
21<br />
-<br />
21-1/8<br />
6-1/4<br />
YCP048F-H<br />
YCP060F-M<br />
SUPPLY<br />
RETURN<br />
21<br />
-<br />
19<br />
-<br />
-<br />
21<br />
-<br />
22-1/8<br />
3<br />
Required Clearance for Unit Installation and Roof Penetration Hole Size Required<br />
INSULATED DECK PANS<br />
ARE INCLUDED WITH THE<br />
BAYCURB038A ONLY.<br />
CLEARANCE TO<br />
COMBUSTIBLE MATERIAL<br />
BOTTOM 0.0"<br />
BACK 1.0"<br />
LEFT SIDE 6.0"<br />
RIGHT SIDE 6.0"<br />
FRONT SIDE <strong>12</strong>.0"<br />
TOP 36.0"<br />
SERVICE CLEARANCE & PENETRATION DIMENSIONS<br />
MODEL NO. A B C D E F<br />
YCP024-36F-L,F-M 42" 30" *6" 24" 36" 25"<br />
YCP036F-H,042F-M 42" 30" *<strong>12</strong>" 30" 44" 25"<br />
YCP048-60F 42" 30" *<strong>12</strong>" 36" 50" 25"<br />
* 18" WITH FRESH AIR ACCESSORY<br />
* 30" WITH ECONOMIZER<br />
21<br />
From Dwg. 21C729942<br />
From Dwg. 662039
AIR DUCT<br />
OPENINGS<br />
A B C<br />
SUPPLY 21 16-3/4 -<br />
RETURN 21 - 21-1/8<br />
Dimensions<br />
BAYCURB033A Roof Curb Outline With YCP036F-H,042F-M <strong>Units</strong><br />
Required Clearance for Unit Installation and Roof Penetration Hole Size Required<br />
SERVICE CLEARANCE DIMENSIONS<br />
A B C D<br />
42" 30" *<strong>12</strong>" 30"<br />
*18" WITH 25% FRESH AIR ACCESSORY<br />
30" WITH ECONOMIZER<br />
22<br />
CLEARANCE TO<br />
COMBUSTIBLE MATERIAL<br />
BOTTOM 0.0"<br />
BACK 1.0"<br />
LEFT SIDE 6.0"<br />
RIGHT SIDE 6.0"<br />
FRONT SIDE <strong>12</strong>.0"<br />
TOP 36.0"<br />
From Dwg. 21C662035<br />
From Dwg. 662039<br />
Pub. No. 22-1708-01-499 (EN)
AIR DUCT<br />
OPENINGS<br />
A B C<br />
SUPPLY 21 19 -<br />
RETURN 21 - 21-1/8<br />
Pub. No. 22-1708-01-499 (EN)<br />
Dimensions<br />
BAYCURB034A Roof Curb Outline With YCP048-60F <strong>Units</strong><br />
Required Clearance for Unit Installation and Roof Penetration Hole Size Required<br />
SERVICE CLEARANCE DIMENSIONS<br />
A B C D<br />
42" 30" *<strong>12</strong>" 36"<br />
*18" WITH 25% FRESH AIR ACCESSORY<br />
30" WITH ECONOMIZER<br />
23<br />
CLEARANCE TO<br />
COMBUSTIBLE MATERIAL<br />
BOTTOM 0.0"<br />
BACK 1.0"<br />
LEFT SIDE 6.0"<br />
RIGHT SIDE 6.0"<br />
FRONT SIDE <strong>12</strong>.0"<br />
TOP 36.0"<br />
From Dwg. 21C662034<br />
From Dwg. 662038
Field Fabricated (Side X Side) Ducts — YCP024-060F <strong>Units</strong><br />
Installed from Above Mounting Curb<br />
P.V.C. Rubber <strong>Gas</strong>ket Position on BAYCURB030A for Unit Placement — YCP024-060F <strong>Units</strong><br />
NOTES:<br />
1. OVERLAP AND POSITION JOINTS IN P.V.C. RUBBER<br />
GASKET.<br />
2. AIR SEALS – APPLY P.V.C. RUBBER LAST TO INSURE<br />
THERE IS ADEQUATE P.V.C. FOR THE WATER SEAL.<br />
3. USE TYPICAL SEALING METHODS TO PREVENT AIR<br />
DUCT LEAKAGE AT CURB-DUCT JOINT.<br />
Dimensions<br />
24<br />
Pub. No. 22-1708-01-499 (EN)
Pub. No. 22-1708-01-499 (EN)<br />
Dimensions<br />
YCP024-060F OUTLINE DRAWING — Front<br />
NOTE: ALL DRAWING DIMENSIONS ARE IN INCHES<br />
CABINET<br />
SIZE<br />
MODEL BAYCURB "A" "B" "C" "D" "E" "F" "G" "H"<br />
"A" YCP024F-L 030A 14-1/8 16-5/8 36 34 25-3/16 13-3/4 -- --<br />
"B"<br />
"C"<br />
"D"<br />
YCP024G-M<br />
YCP030-36F-L<br />
YCP030-36F-M<br />
YCP036F-H<br />
YCP042F-M<br />
YCP048F-H<br />
YCP060F-M<br />
030A 14-1/8 16-5/8 36 34 29-3/16 13-3/4 -- --<br />
030A 14-1/8 16-5/8 36 34 29-3/16 13-3/4 8-1/8<br />
033A 14-13/16 16-5/8 36 34 29-3/16 13-3/4 -- --<br />
030A 14-1/8 21 45 34 33-3/8 13-3/4 10-1/8 9-7/8<br />
034A 14-13/16 21 45 43 33-3/8 13-3/4 -- --<br />
25<br />
From Dwg. 661772
RECOMMENDED SERVICE<br />
CLEARANCE<br />
BACK * 6.0"<br />
LEFT SIDE 30.0"<br />
RIGHT SIDE 24.0"<br />
FRONT SIDE 42.0"<br />
* 18" WITH FRESH AIR ACCESSORY<br />
* 30" WITH ECONOMIZER<br />
Dimensions<br />
YCP024-060F OUTLINE DRAWING — Front<br />
NOTE: ALL DRAWING DIMENSIONS ARE IN INCHES<br />
MODEL A B C D<br />
YCP024F-L<br />
YCP024F-M<br />
56 1/2 36 25 3/16 25 1/8<br />
YCP030F-L<br />
YCP030F-M<br />
YCP036F-L<br />
YCP036F-M<br />
YCP036F-H<br />
YCP042F-M<br />
YCP048F-H<br />
YCP060F-M<br />
56 1/2 36 29 3/16 25 1/8<br />
64 36 29 3/16 26 9/16<br />
65 1/8 45 33 5/8 27 15/16<br />
26<br />
CLEARANCE TO<br />
COMBUSTIBLE MATERIAL<br />
BOTTOM 0.0"<br />
BACK 1.0"<br />
LEFT SIDE 6.0"<br />
RIGHT SIDE 6.0"<br />
FRONT SIDE <strong>12</strong>.0"<br />
TOP 36.0"<br />
From Dwg. 21D667977 Rev. 1<br />
Pub. No. 22-1708-01-499 (EN)
MODEL<br />
Pub. No. 22-1708-01-499 (EN)<br />
CORNER WEIGHT (LBS) UNIT<br />
W1 W2 W3 W4 WEIGHT<br />
Dimensions<br />
YCP024-060F OUTLINE DRAWING — Rear<br />
NOTE: ALL DRAWING DIMENSIONS ARE IN MM (INCHES)<br />
A B C D E F G H J K L M N P<br />
YCP024F-L 82 64 85 109 340 56-1/2 36 25-3/16 18 9/16 11-1/16 6-9/16 6-13/16 17 21 21-1/4<br />
YCP024F-M 84 68 93 113 357<br />
YCP030F-L<br />
YCP030F-M<br />
84<br />
85<br />
68<br />
70<br />
93<br />
94<br />
111<br />
114<br />
356<br />
363 56-1/2 36 29-3/16 18-9/16 11-1/16 6-9/16 6-13/16 17<br />
21 21-7/8<br />
17-1/2 10 3 4-7/16<br />
YCP036F-L<br />
YCP036F-M<br />
88<br />
88<br />
73<br />
74<br />
97<br />
97<br />
114<br />
119<br />
372<br />
379<br />
20-1/2 25-1/8<br />
YCP036F-H<br />
YCP042F-M<br />
93<br />
97<br />
76<br />
79<br />
100<br />
105<br />
<strong>12</strong>4<br />
<strong>12</strong>7<br />
393<br />
407<br />
64 36 29-3/16 18-9/16 11-1/16 6-9/16 11-1/8 17 20-1/2 28-1/2 17-1/2 10 3 8-3/4<br />
YCP048F-H<br />
YCP060F-M<br />
<strong>12</strong>1<br />
133<br />
106<br />
109<br />
134<br />
134<br />
154<br />
165<br />
515<br />
542<br />
65-1/8 45 33-3/8 21-1/16 15-1/16 4-15/16 9-1/8 21-15/16<br />
25-3/8<br />
25-3/16<br />
30-1/4<br />
28-7/8<br />
20 14 3-1/2 8-5/16<br />
27<br />
From Dwg. 21D667953
General<br />
All units shall be factory assembled, piped,<br />
internally wired and fully charged with R-22.<br />
All units shall be designed to operate at<br />
outdoor ambient temperatures as high as<br />
115°F Cooling capacities shall be rated in<br />
accordance with A.R.I. standards. The YCP-F<br />
heating/cooling unit design is UL listed,<br />
specifically for outdoor applications using<br />
propane or natural gas. All units shall be<br />
designed for outdoor rooftop or ground level<br />
installation. Exterior surfaces of all units shall<br />
be phosphatized, zinc-coated steel with epoxy<br />
resin primer and baked enamel finish.<br />
Shipped for horizontal application,<br />
convertible to downflow.<br />
Casings<br />
All panels shall be 20-gauge steel, gasketed<br />
and insulated. Foil-faced glass fiber insulation<br />
shall be in the heat exchanger section. Matfaced<br />
insulation shall be in the evaporator<br />
section. Base pan and mounting rails shall be<br />
18 gauge. WEATHERGUARD exterior<br />
corrosion resistant screws shall be used for<br />
added resistance to rust and corrosion.<br />
Controls<br />
Refrigeration cycle controls shall include<br />
condenser fan, evaporator fan and<br />
<strong>com</strong>pressor contactors. Compressors shall be<br />
equipped with a <strong>com</strong>bination internal winding<br />
thermostat/current overload. Internal high<br />
pressure relief shall also be provided.<br />
Refrigeration System<br />
Compressors — All units shall have<br />
hermetically sealed Climatuff ® <strong>com</strong>pressors.<br />
Compressors shall be equipped with over<br />
temperature, over current and high pressure<br />
protection. Crankcase heaters shall be<br />
standard on all three phase models.<br />
Evaporator Coil — Internally enhanced<br />
3/8-inch OD seamless copper tubing<br />
mechanically bonded to aluminum fins,<br />
factory pressure and leak tested at 250 to 300<br />
psig.<br />
The Trane Company<br />
Unitary Products Group<br />
6200 Troup Highway<br />
Tyler, TX 75707<br />
An American-Standard Company<br />
Mechanical<br />
Specification Options<br />
Condenser Coil — Outdoor coils shall be<br />
internally enhanced 3/8-inch OD seamless<br />
copper tubing mechanically bonded to<br />
aluminum fins. Each coil shall be factory<br />
pressure and leak tested at 420 psig.<br />
Indoor Air Fan — Direct-drive, forwardcurved,<br />
centrifugal type. Motor shall have<br />
thermal overload protection. Permanently<br />
lubricated motor bearings. Motor/blower<br />
assembly isolated from unit with rubber<br />
mounts.<br />
Condenser Fan — Direct-drive, draw thru<br />
propeller type. Weather-proofed permanent<br />
split capacitor fan motor shall have built-in<br />
thermal overload and permanently lubricated<br />
motor bearings.<br />
Low Ambient — Standard refrigerant system<br />
operation down to 55°F Low ambient<br />
accessory required for operation in 0°F<br />
ambient condition.<br />
Heating System<br />
<strong>Gas</strong>-Fired Heating Section — Models shall<br />
provide <strong>com</strong>pletely assembled, wired and<br />
piped gas fired heating systems within unit.<br />
Design certified by U.L., specifically for<br />
outdoor application. Threaded gas connection<br />
on the unit.<br />
Electronic Ignition System — Main burner<br />
is lit each time thermostat calls for heat.<br />
Flame sensor proves flame and keeps the<br />
main burners on. Should a loss of flame<br />
occur, the main valve closes and the spark<br />
recurs within 0.8 second. When thermostat is<br />
satisfied, main burner is extinguished.<br />
Forced Combustion Blower — Insures<br />
flame stability under varying wind conditions.<br />
Gives higher <strong>com</strong>bustion efficiency and<br />
location flexibility.<br />
Heat Exchanger — Aluminized steel tubes.<br />
Free floating design.<br />
Burners — 20-gauge aluminized steel. Multiport<br />
inshot.<br />
Downflow Accessories<br />
(U.S. Domestic Models)<br />
Roof Curb — The roof curb shall be designed<br />
to mate with the unit and provide support and<br />
<strong>com</strong>plete weather-tight installation when<br />
properly installed. Curb shall ship knocked<br />
down for field assembly, and include wood<br />
nailer strips.<br />
Economizer<br />
Modulating Economizer — This accessory<br />
shall be field installed and be <strong>com</strong>posed of<br />
the following items: 0-100% fresh air damper,<br />
damper drive motor fixed dry bulb enthalpy<br />
control, and low voltage polarized plug for<br />
electrical connections. Solid state enthalpy or<br />
differential enthalpy control is optional.<br />
Economizer operations shall be controlled by<br />
the preset position of the enthalpy control. A<br />
barometic relief damper shall be standard with<br />
the economizer and provide a pressure<br />
operated damper that shall be gravity closing<br />
and prohibit entrance of outside air on<br />
equipment “off” cycle.<br />
Manual Fresh Air Hood<br />
Manual outside air provides a fixed outside air<br />
quantity from 0 to 25 percent. Includes hood<br />
and birdscreen.<br />
Low Ambient Control<br />
Control allows cycling of <strong>com</strong>pressor under<br />
low ambient cooling conditions. Required for<br />
cooling operation to 0°F.<br />
Propane <strong>Gas</strong><br />
Conversion Kit — For conversion from<br />
natural gas to LP gas.<br />
File No. PL-UN-RT-YCP-D-1-4-99 P.I.<br />
Supersedes New<br />
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change<br />
design and specifications without notice.