28.03.2013 Views

draft - Office of the State Fire Marshal - State of California

draft - Office of the State Fire Marshal - State of California

draft - Office of the State Fire Marshal - State of California

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

DRAFT<br />

Commercial cooking equipment that produce grease laden vapors shall be provided with a Type I Hood, in<br />

accordance with <strong>the</strong> <strong>California</strong> Mechanical Code, and an automatic fire extinguishing system that is listed and labeled<br />

for its intended use as follows:<br />

1. Wet chemical extinguishing system, complying with UL 300.<br />

2. Carbon dioxide extinguishing systems,<br />

3. Automatic fire sprinkler systems.<br />

All existing dry chemical and wet chemical extinguishing systems shall comply with UL 300, no later than <strong>the</strong> second<br />

required servicing <strong>of</strong> <strong>the</strong> system following <strong>the</strong> effective date <strong>of</strong> this section,<br />

Exception Public schools kitchens, without deep-fat fryers, shall be upgraded to a UL 300 compliant system during<br />

state funded modernization projects that are under <strong>the</strong> jurisdiction <strong>of</strong> <strong>the</strong> Division <strong>of</strong> <strong>the</strong> <strong>State</strong> Architect<br />

All systems shall be installed in accordance with <strong>the</strong> <strong>California</strong> Mechanical Code, appropriate adopted standards,<br />

<strong>the</strong>ir listing and <strong>the</strong> manufacturers’ installation instructions.<br />

Exception: Factory-built commercial cooking recirculating systems that are tested, listed, labeled and installed in<br />

accordance with UL 710B. and listed, labeled and installed in accordance with Section 304.1 <strong>of</strong> <strong>the</strong> International<br />

Mechanical Code.<br />

904.11.5 Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be<br />

provided within a 30-foot (9144 mm) travel distance <strong>of</strong> commercial-type cooking equipment. Cooking equipment<br />

involving solid fuels or vegetable or animal oils and fats shall be protected by a ClassKrated portable extinguisher in<br />

accordance with Sections 904.11.5.1 or 904.11.5.2, as applicable and maintained in accordance with Title 19,<br />

<strong>California</strong> Code <strong>of</strong> Regulations, Title 19, Division 1, Chapter 3.<br />

904.11.5.2 Class K portable fire extinguishers for deep fat fryers. When hazard areas include deep fat fryers,<br />

listed Class K portable fire extinguishers shall be provided in accordance with Title 19, <strong>California</strong> Code <strong>of</strong><br />

Regulations, Title 19, Division 1, Chapter 3 and as follows:<br />

1. For up to four fryers having a maximum cooking medium capacity <strong>of</strong> 80 pounds (36.3 kg) each: One Class K<br />

portable fire extinguisher <strong>of</strong> a minimum 1.5 gallon ( 6 L) capacity.<br />

2. For every additional group <strong>of</strong> four fryers having a maximum cooking medium capacity <strong>of</strong> 80 pounds (36.3 kg) each:<br />

Additional Class K portable fire extinguishers <strong>of</strong> a minimum 1.5 gallon (6 L) capacity shall be provided.<br />

3. For individual fryers exceeding 6 square feet (0.55 m 2 ) in surface area: Class K portable fire extinguishers shall be<br />

installed in accordance with <strong>the</strong> extinguisher manufacturer’s recommendations.<br />

904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in<br />

accordance with Title 19, <strong>California</strong> Code <strong>of</strong> Regulations, Title 19, Division 1, Chapter 5 and this section.<br />

905.2 Installation standard. Standpipe systems shall be installed in accordance with this section and NFPA 14 as<br />

amended in Chapter 47<br />

905.3 Required installations. Standpipe systems shall be installed where required by Sections 905.3.1 through<br />

905.3.710.1 905.3.10.1 and in <strong>the</strong> locations indicated in Sections 905.4, 905.5 and 905.6. Standpipe systems are<br />

allowed to be combined with automatic sprinkler systems.<br />

Exception: Standpipe systems are not required in Group R-3 occupancies.<br />

905.3.1 Height. In o<strong>the</strong>r than Group R-3 and R-3.1 occupancies, Cclass III standpipe systems shall be installed<br />

throughout at each floor where any <strong>of</strong> <strong>the</strong> following occur:<br />

1. Bbuildings where <strong>the</strong> floor level <strong>of</strong> <strong>the</strong> highest story is located more than 30 feet (9144mm) above <strong>the</strong> lowest level<br />

<strong>of</strong> fire department vehicle access,. or<br />

2. Buildings that are four or more stories in height.<br />

<strong>Office</strong> <strong>of</strong> <strong>the</strong> <strong>State</strong> <strong>Fire</strong> <strong>Marshal</strong> 46 <strong>of</strong> 191 April 30, 2009<br />

2009 Annual Rulemaking Cycle<br />

Express Terms – CCR, Title 24, Part 9<br />

2010 <strong>California</strong> <strong>Fire</strong> Code (2009 IFC)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!