10.04.2013 Views

N1-Switches, Tumbler, Disconnect, Explosionproof

N1-Switches, Tumbler, Disconnect, Explosionproof

N1-Switches, Tumbler, Disconnect, Explosionproof

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Typical Application<br />

Right End<br />

Unit<br />

Right Hand Single Unit<br />

(with option Warning Lamp)<br />

Wiring Information<br />

Single Pole, Double Throw Micro Switch<br />

Rating: 20 AMPS, 125, 250 or 480 VAC •<br />

10 AMPS, 125 VAC “L” (tungsten lamp load)<br />

• 1 HP, 125 VAC • 2 HP, 250 VAC • 1/2<br />

AMP, 125 VDC • 1/4 AMP, 250 VDC<br />

Two Circuit, Double Break Micro Switch<br />

Rating: 15 AMPS, 120, 240, 480 or 600<br />

VAC • 1/2 HP, 120 VAC • 1 HP, 240 VAC •<br />

0.8 AMPS, 115 VDC • 0.4 AMP, 230 VDC<br />

0.8, 250 VAC • 1/2 AMP, 125 VDC • 1/4 AMP, 250<br />

VDC<br />

Effective September, 2005<br />

Copyright 2005<br />

AFU, AFUX Conveyor Control <strong>Switches</strong><br />

Pull Cord Type, Left or Right Hand, Single or Double End.<br />

Double End Unit<br />

200’ Maximum 200’ Maximum<br />

Double End Unit Right and Left Handed<br />

(with option Warning Lamp)<br />

SINGLE POLE, DOUBLE THROW CIRCUIT<br />

<br />

TWO CIRCUIT, DOUBLE BREAK CIRCUIT<br />

MOTOR CONTROL CIRCUIT WARNING CIRCUIT<br />

N-27<br />

Left End<br />

Unit<br />

Left Hand Single Unit<br />

(with option Warning Lamp)<br />

NOTE: Two circuit double break switches must be wired to equal voltage sources and the same polarity. Loads should be on the same side<br />

of the lines. 1B has the same polarity as 3A.<br />

800-621-1506<br />

www.appletonelec.com<br />

PAGE 27<br />