Sprinkler News - Bafsa
Sprinkler News - Bafsa
Sprinkler News - Bafsa
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Protecting Property, Life and the Environment <strong>News</strong>letter No 17 Page 6<br />
New Products and services<br />
The “Shawston Firesleeve” will save you in labour time due to its unique Snap Lock Design.<br />
As you will be aware there is increasing responsibility placed on contractors to make good any area where the services penetrate<br />
a firewall. To assist you in doing this Shawston have put a wide range of the most common fire stopping products into<br />
stock.<br />
The “Shawston Firesleeve” is suitable for fire containment in both plasterboard and block work walls for a 2-hour rated seal. It<br />
has a stainless steel sleeve lined with a high expansion intumescent compound overlaid with a fire resistant acoustic foam<br />
compression seal.<br />
Viking Offers ESFR Protection in Freezers<br />
The Viking Corporation announces a new system for protecting freezer and cold storage environments. This new system, utilizing Vi-<br />
king’s K25 ESFR Pendent <strong>Sprinkler</strong>s (VK510) and a pre-mix of propylene glycol antifreeze and water, can enhance flexibility by eliminat-<br />
ing in-rack sprinklers in certain applications. Testing utilizing Viking’s K25 ESFR <strong>Sprinkler</strong> has been completed, and UL Listing is pend-<br />
ing.<br />
Viking’s K25 Antifreeze System protects up to Class II Storage Commodities in buildings up to 40 feet<br />
(12,2 m) high with racked storage up to 35 feet (10,7 m). The listing is for the 165° F (74° C) Viking<br />
K25 ESFR <strong>Sprinkler</strong> (VK510), though intermediate temperature sprinklers rated to 205° F (96° C) may<br />
be applied as referenced in NFPA 13 for installation in close proximity to heat sources. This special<br />
application for the K25 ESFR <strong>Sprinkler</strong> requires a minimum starting pressure of 40 psi (278 kPa) and<br />
has a maximum volume of antifreeze solution per system of 1100 gallons (4163 liters).<br />
The Viking K25 Antifreeze System provides a cost effective alternative to in-rack sprinkler systems for<br />
protecting storage environments as cold as –23° F (-30.6° C). In addition to having a positive impact on<br />
total installed cost, the system is also far less vulnerable to damage than traditional in-rack sprinklers.<br />
Viking Introduces New Concealed Dry <strong>Sprinkler</strong>s (see photo)<br />
This new line includes both standard response and quick response versions for both standard coverage<br />
and extended coverage applications.<br />
Standard Coverage Extended Coverage<br />
Standard Response (1” NPT) 5.6 (8,1) K-factor 5.6 (8,1) K-factor<br />
8.0 (11,5) K-factor<br />
Quick Response (1” NPT) 5.6 (8,1) K-factor 5.6 (8,1) K-factor<br />
The push-on, thread-off cover design allows for easy installation after the system has been tested and the ceiling has been finished. The<br />
cover provides ½” (12,7mm) vertical adjustment, a critical factor for proper installation of concealed sprinklers. It is only 3-1/8” (80mm) in<br />
diameter, may be removed without taking the system out of service and is available in chrome, white, ivory, black and custom colors.<br />
Protect Combustible Concealed Spaces with New Viking COIN <strong>Sprinkler</strong><br />
The new COIN Quick Response Combustible Interstitial Space <strong>Sprinkler</strong> has been tested and listed for use in specific light hazard com-<br />
bustible and non-combustible concealed horizontal spaces requiring sprinkler protection per installation standards. In some cases, it can<br />
allow the use of any listed CPVC piping system within concealed spaces requiring sprinkler protection.<br />
With extended cov erage listings for spacing up to 12’ x 12’ (3,7m x 3,7m), the COIN <strong>Sprinkler</strong> can be used with Wet Pipe Systems using<br />
steel or any listed CPVC pipe, or Dry Pipe Systems using galvanized steel pipe.<br />
The COIN sprinkler (VK900) is cULus Listed. It has a 4.2 (6,0 metric) K-factor and a starting pressure of 11.8 psi (81,4 kPa) at its maximum<br />
spacing and .1 gpm/ft 2 (4,1mm/min) density. Minimum starting pressure is 8 psi (55 kPa).<br />
For more information on any of Viking’s full-line of products, please visit www.vikingcorp.com