Gallagher TM - Gallagher.eu
Gallagher TM - Gallagher.eu
Gallagher TM - Gallagher.eu
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
What does Stored Energy tell you?<br />
Stored Energy is the first reading – identified by the “J” symbol. Stored Energy is the amount<br />
of energy (Joules) available - the actual output energy depends on the fence load and the<br />
efficiency of the Energizer. When your fence is in good condition the Energizer uses only a<br />
small volume of energy per pulse – minimum Stored Energy is 13 Joules in New Zealand,<br />
Australia and South Africa – 7 Joules in Europe. As your fence becomes more heavily loaded<br />
Adaptive Control delivers more energy in each pulse – e.g. MX5000 up to 48 Joules. Figure 1<br />
illustrates the Stored Energy reading.<br />
Stored Energy is therefore a measure of fence condition. If the MX5000 increases to 40 Joules<br />
or greater (equally the MX2500 increases to 20 Joules or greater or the MX1600 increases to<br />
14 Joules or greater) then the fence is in poor condition and close to overloading your<br />
Energizer’s capacity. Fence maintenance is required.<br />
If additional fence is connected, the level of Stored Energy will indicate whether the<br />
Energizer is able to cope with the extra load or you need to upgrade to a larger Energizer.<br />
What does Output Voltage tell you?<br />
Stored Energy Waiting for the<br />
Measurement next Pulse<br />
FIGURE 1: Stored Energy Reading<br />
Output Voltage is the second reading – identified by the lightning bolt symbol ( ). Output<br />
Voltage is the voltage leaving your Energizer. Under heavy fence load Output Voltage will<br />
normally be higher than Fence Voltage. Figure 2 illustrates the Output Voltage reading, in<br />
kilovolts (kV).<br />
FIGURE 2: Output Voltage Reading<br />
Your SmartPower Energizer features a low Output voltage Alarm (OA). If Output Voltage<br />
drops below 3kV (factory default setting) and the Energizer is unable to re-establish 3kV, even<br />
at maximum Stored Energy, then the Output Alarm is activated. The Output Alarm can be<br />
either turned OFF, or set at 2kV, 3kV or 4kV – consult your <strong>Gallagher</strong> Dealer or National<br />
Distributor if you wish to change the default setting. The symbol ‘A’ is displayed (Figure 2)<br />
when the Output Alarm is set.<br />
– 6 –<br />
Waiting for the<br />
next Pulse