Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Specifications<br />
<strong>•</strong> NOMINAL VOLTAGE: 12V<br />
<strong>•</strong> NOMINAL CAPACITY:<br />
20 hr. rate of 5.0A to 10.5V 100.0Ah<br />
10 hr. rate of 9.0A to 10.5V 90.0Ah<br />
5 hr. rate of 16.0A to 10.2V 80.0Ah<br />
1 hr. rate of 60.0A to 9.60V 60.0Ah<br />
<strong>•</strong> WEIGHT (approx.): 68 pounds (30.8kgs)<br />
<strong>•</strong> <strong>EN</strong>ERGY D<strong>EN</strong>SITY (20 hr. rate):<br />
1.62 WH/cubic inch (99.4 WH/liter)<br />
<strong>•</strong> SPECIFIC <strong>EN</strong>ERGY (20 hr. rate):<br />
17.6 WH/pound (38.9 WH/kg)<br />
<strong>•</strong> INTERNAL RESISTANCE OF CHARGED<br />
BATTERY:<br />
6.5 milliohms (approx.)<br />
<strong>•</strong> MAXIMUM DISCHARGE CURR<strong>EN</strong>T<br />
WITH STANDARD TERMINALS:<br />
150 amperes<br />
<strong>•</strong> MAXIMUM SHORT-DURATION<br />
DISCHARGE CURR<strong>EN</strong>T:<br />
500 amperes<br />
<strong>•</strong> OPERATING TEMPERATURE RANGE:<br />
CHARGE 5 0 F to 122 0 F<br />
(-15 0 C to 50 0 C)<br />
DISCHARGE -4 0 F to 140 0 F<br />
(-20 0 C to 60 0 C)<br />
<strong>•</strong> CHARGE RET<strong>EN</strong>TION (shelf life)<br />
at 68˚F (20˚C):<br />
1 month 97%<br />
3 months 91%<br />
6 months 85%<br />
<strong>•</strong> LIFE EXPECTANCY:<br />
STANDBY USE 3 to 5 years<br />
CYCLE USE (approx.):<br />
100% depth of discharge 250 cycles<br />
50% depth of discharge 550 cycles<br />
30% depth of discharge 1200 cycles<br />
<strong>•</strong> SEALED CONSTRUCTION:<br />
Can be operated in any position<br />
without leakage.<br />
<strong>•</strong> STANDARD TERMINAL:<br />
Receptacle terminal<br />
<strong>•</strong> HOUSING MATERIAL: PP Resin<br />
<strong>•</strong> OPTIONAL:<br />
Container and cover made from<br />
Flame Retardant PP<br />
(UL94-V0/L.O.I.>28%)<br />
Terminal<br />
DIM<strong>EN</strong>SIONS: MM (INCHES)<br />
Dimensions<br />
12.95 (329.0)<br />
DIM<strong>EN</strong>SIONS: INCHES (MM)<br />
NP<br />
<strong>NP100</strong>-<strong>12R</strong><br />
<strong>NP100</strong>-<strong>12R</strong>FR<br />
Sealed Rechargeable<br />
Lead-Acid Battery<br />
12V, 100Ah<br />
6.77 (172.0)<br />
M6<br />
Φ20 (0.79)<br />
UL listing pending - File No MH14328<br />
Publication No: <strong>EN</strong>-<strong>NP100</strong>-<strong>12R</strong>-<strong>01</strong> <strong>•</strong> <strong>June</strong> 2005<br />
8.43 (214.0)
REMAINING CAPACITY<br />
PERC<strong>EN</strong>TAGE OF CAPACITY AVAILABLE<br />
TERMINAL VOLTAGE<br />
SELF DISCHARGE CHARACTERISTICS<br />
(%)<br />
100<br />
75<br />
50<br />
25<br />
0<br />
(AH%)<br />
120<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
DISCHARGE CHARACTERISTIC<br />
CURVES AT 25 0 C (77 0 F)<br />
CYCLE SERVICE LIFE IN RELATION<br />
TO DEPTH OF DISCHARGE<br />
EnerSys<br />
P.O. Box 14145<br />
Reading, PA 19612-4145<br />
USA<br />
Tel:+1-610-208-1991<br />
+1-800-538-3627<br />
EnerSys EMEA<br />
Brussels, Belgium<br />
Tel:+32 (0)2 247 94 47<br />
EnerSys Asia<br />
Guandong, China<br />
Tel:+86 755 689 9220<br />
(V)<br />
14.0<br />
13.0<br />
12.0<br />
11.0<br />
OP<strong>EN</strong> CIRCUIT VOLTAGE<br />
VS REMAINING CAPACITY<br />
10.0<br />
3 6 9 12 15 18 0 20 40 60 80 100<br />
STORAGE TIME (MONTHS)<br />
TESTING CONDITIONS: DISCHARGE CURR<strong>EN</strong>T: 0.17C AMP. (F.V. 1.7V/CELL)<br />
CHARGING CURR<strong>EN</strong>T: 0.09C AMP.<br />
CHARGING VOLUME: 125% OF DISCHARGED CAPACITY<br />
AMBI<strong>EN</strong>T TEMPERATURE: 20 0 C TO 25 0 C (68 0 F TO 77 0 F)<br />
100% D.O.D.<br />
50% D.O.D.<br />
40 0 C (104 0 F)<br />
NUMBER OF CYCLES<br />
30 0 C (86 0 F)<br />
20 0 C (68 0 F)<br />
30% DEPTH OF DISCHARGE<br />
200 400 600 800 1000 1200 1400<br />
OP<strong>EN</strong> CIRCUIT VOLTAGE<br />
PERC<strong>EN</strong>TAGE OF CAPACITY AVAILABLE<br />
(AH%)<br />
120<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
When the battery will be used by current in excess of 3C, consult with EnerSys prior to use.<br />
CHARGING METHODS (At 20˚C) Cycle use: Maximum charging current 0.25C<br />
Charging voltage 14.4 to 15.0V<br />
Standby use: Float charging voltage 13.50 to 13.80V<br />
CAUTION <strong>•</strong>Avoid short circuit<br />
<strong>•</strong>Do not charge in a sealed container.<br />
www.enersys.com<br />
PERC<strong>EN</strong>TAGE OF CAPACITY AVAILABLE<br />
TEMPERATURE EFFECTS IN RELATION<br />
TO BATTERY CAPACITY<br />
REMAINING CAPACITY (%)<br />
FLOAT SERVICE LIFE<br />
TESTING CONDITIONS: FLOATING VOLTAGE 2.25 TO 2.30V/CELL<br />
AMBI<strong>EN</strong>T TEMPERATURE: 20 0 C TO 22 0 C (64 0 F TO 72 0 F)<br />
1 2 3 4 5 5.5<br />
LIFE (YEARS)<br />
Represented by:<br />
AT 25 0 C (77 0 F)<br />
© 2005 EnerSys. All rights reserved.<br />
Trademarks are the property of EnerSys and its<br />
affiliates unless otherwise noted.<br />
Publication No: <strong>EN</strong>-<strong>NP100</strong>-<strong>12R</strong>-<strong>01</strong> <strong>•</strong> <strong>June</strong> 2005 Subject to revisions without prior notice. E.&O.E.