Medium voltage BPL installations:<br />
case study from Poland<br />
Smart Metering Central & Eastern Europe <strong>2011</strong>
Smart Metering & Smart Grid for Kleszczow<br />
Basic informations<br />
Medium voltage BPL installations:case study from Poland<br />
Telecontrol and<br />
Supervision Systems<br />
2
Smart Metering & Smart Grid for Kleszczow<br />
The low voltage solution<br />
Gateway (LGW200)<br />
The LGW200 is the <strong>smart</strong> <strong>metering</strong> gateway of the Aranuka system, made by <strong>Power</strong> <strong>Plus</strong><br />
Communication. It enables the real-time readout of <strong>smart</strong> meters. The LGW200 connects the<br />
BPL network to meters via standard short range interfaces such as Wireless-M-Bus or RS485,<br />
RS232, M-Bus and Current Loop (wired) and also narrow band PLC. This system allows easy<br />
integration of meters from different manufacturers in order to build a multi-utility (electricity, gas,<br />
water, heat) <strong>metering</strong> solution.<br />
Repeater (LR200)<br />
The LR200 extends the coverage of the BPL network by regenerating the data signal<br />
dynamically. It serves as <strong>smart</strong> nodes in a meshed network structure.<br />
Headend (LH200)<br />
The LH200 connects the BPL network to the backbone via an Ethernet interface.<br />
Medium voltage BPL installations:case study from Poland<br />
3
Smart Metering & Smart Grid for Kleszczow<br />
The low voltage solution<br />
Medium voltage BPL installations:case study from Poland<br />
4
Smart Metering & Smart Grid for Kleszczow<br />
The medium voltage solution<br />
Coupler<br />
With the BPL medium-voltage coupler a medium-voltage grids can be turned into broadband<br />
data networks. It has been developed specifically for the transmission of broadband signals<br />
over ground-cables and overhead lines. Together with the MV200 BPL modem, this coupler<br />
enables data transmission rates up to 30 Mbps.<br />
MV200<br />
<strong>PPC</strong>'s medium-voltage modem MV200 is able to transmit data on cables with a data rate up to<br />
30 Mbps, in combination with the BPL coupler.<br />
Medium voltage BPL installations:case study from Poland<br />
5
Smart Metering & Smart Grid for Kleszczow<br />
The medium voltage solution<br />
Medium voltage BPL installations:case study from Poland<br />
Installation on underground cables<br />
6
Smart Metering & Smart Grid for Kleszczow<br />
The medium voltage solution<br />
Medium voltage BPL installations:case study from Poland<br />
Installation on overhead cables<br />
7
Smart Metering & Smart Grid for Kleszczow<br />
Basic informations<br />
Area: 12 square km<br />
Population: 5 000 people<br />
Number of electricity customers: over 1 500<br />
Number of stations MV / LV: 12 (two MV rings)<br />
MV cable length between stations: from 200m to 1800m<br />
Type of MV cable: Underground<br />
Aim of installation BPL communication over MV grid:<br />
• implementation of telecommunication connections between all electricity meters<br />
installed at the customers supplied from the LV and fiber-optic backbone network of<br />
energy supplier/distributor<br />
• implementation of telecommunication connections between RTU planned to be<br />
installed in substations MV / LV and supervising system of energy grid (for mapping of<br />
switch location, measurements of MV/LV grid parameters, access control)<br />
Medium voltage BPL installations:case study from Poland<br />
8
Smart Metering & Smart Grid for Kleszczow<br />
Geographic overview of the area of the survey<br />
Medium voltage BPL installations:case study from Poland<br />
9
Smart Metering & Smart Grid for Kleszczow<br />
Schema of MV BPL installation<br />
Medium voltage BPL installations:case study from Poland<br />
10
Smart Metering & Smart Grid for Kleszczow<br />
Schema of installation in 15kV switch gear of HV station<br />
Medium voltage BPL installations: case study from Poland<br />
11
Smart Metering & Smart Grid for Kleszczow<br />
Schema of installation in 15kV MV station ST-3<br />
Medium voltage BPL installations: case study from Poland<br />
12
Smart Metering & Smart Grid for Kleszczow<br />
Schema of installation in 15kV MV station ST-9<br />
Medium voltage BPL installations: case study from Poland<br />
Part of implementation<br />
for LV BPL<br />
13
Smart Metering & Smart Grid for Kleszczow<br />
Installation of BPL24CC on underground cables<br />
Cable to MV200 modem<br />
Medium voltage BPL installations:case study from Poland<br />
14
Smart Metering & Smart Grid for Kleszczow<br />
MV200 modem in HV/MV GPZ Kleszczow station<br />
Medium voltage BPL installations:case study from Poland<br />
TCP/IP Backbone Router<br />
15
Smart Metering & Smart Grid for Kleszczow<br />
MV200 modems in MV/LV ST-3 station<br />
MV200 direction GPZ<br />
Medium voltage BPL installations: case study from Poland<br />
MV200 direction ST-9<br />
16
Smart Metering & Smart Grid for Kleszczow<br />
Schema of MV BPL implementation for GPZ, ST-3, ST-9<br />
Medium voltage BPL installations:case study from Poland<br />
17
Smart Metering & Smart Grid for Kleszczow<br />
Measurements - Link for connection between ST9–GPZ (1.2km)<br />
The following Figure shows the link quality. One can see that only the first two bands can be<br />
used with QPSK-modulation for data transmission due to the attenuation of the 1.200 meter<br />
long cable.<br />
Medium voltage BPL installations:case study from Poland<br />
18
Smart Metering & Smart Grid for Kleszczow<br />
Measurements - Link for connection between ST9–GPZ (1.2km)<br />
Link ST9 – GPZ (1.200 meter)<br />
Two Bandwidth measurements have been made. For this test, the devices in ST-3 have been<br />
powered off.<br />
The first was made with the default configuration of the Aranuka modems, for meshed BPL<br />
infrastructure. The bandwidth was 1.45 Mbps.<br />
The second measurements where done with optimised configuration for Point-To-Point Links.<br />
With optimised configuration, on this communication link increased from 1.45 Mbps to 2.45<br />
Mbps in average.<br />
Medium voltage BPL installations:case study from Poland<br />
19
Smart Metering & Smart Grid for Kleszczow<br />
Measurements - Link for connection between ST3–GPZ (800m)<br />
The following Figure shows the link quality between GPZ and ST3. One can see that four of<br />
seven bands can be used, with all types of modulation for data transmission on the 800 meter<br />
long cable.<br />
The average bandwidth was 6 Mbps<br />
Medium voltage BPL installations: case study from Poland<br />
20
Smart Metering & Smart Grid for Kleszczow<br />
The MV BPL network extension to the area of LV grid (ST-9)<br />
RS485 to ETH converter<br />
Router<br />
Medium voltage BPL installations: case study from Poland<br />
MV200 direction ST-3<br />
LH200 connection to LV grid<br />
LH200 connection to router LH200<br />
21
Smart Metering & Smart Grid for Kleszczow<br />
The MV BPL network extension to the area of LV grid<br />
Meters cabinet in multifamily apartments<br />
Medium voltage BPL installations: case study from Poland<br />
LGW200<br />
Meter<br />
RS485 to ETH converter<br />
RS485 bus<br />
22
Smart Metering & Smart Grid for Kleszczow<br />
MV BPL network extension to LV grid - Measurements<br />
Medium voltage BPL installations: case study from Poland<br />
23
Smart Metering & Smart Grid for Kleszczow<br />
MV BPL - conclusions<br />
• Low implementation costs - comparable with narrowband PLC technology<br />
• Higher speed of transmission than narrowband PLC technology offering<br />
• Easy to install<br />
• A good way to extend the TCP / IP backbone network to the MV / LV station<br />
• Allows the coexistence of multiple systems, not only Smart Meterig or Smart Grid<br />
The surveillance system for energy networks<br />
Control of street lighting and traffic lights<br />
Access control system<br />
• MV BPL is an alternative to Fibre-Optic link<br />
Cheaper to implementation<br />
Faster to implementation<br />
Often the only way to use in an urban area<br />
• The possibility of extending the TCP/IP backbone to the LV grid area<br />
Medium voltage BPL installations: case study from Poland<br />
24
Medium voltage BPL installations:<br />
case study from Poland<br />
Smart Metering Central & Eastern Europe <strong>2011</strong><br />
Thank you for your attention<br />
Jacek Koźbiał – <strong>Mikronika</strong><br />
Thomas Wolski – <strong>Power</strong> <strong>Plus</strong> Communication AG