Nalco® wt-222 - Aquatech-vandbehandling.dk
Nalco® wt-222 - Aquatech-vandbehandling.dk
Nalco® wt-222 - Aquatech-vandbehandling.dk
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
PRODUCT NAME<br />
NALCO® WT-<strong>222</strong><br />
Corrosion Inhibitor<br />
PRODUCT DESCRIPTION AND APPLICATION<br />
Nalco WT-<strong>222</strong> is a multifunctional, one-drum, scale and corrosion inhibitor for industrial open recirculating<br />
cooling water systems.<br />
This product was designed for systems with corrosive water and low to medium hardness and/or alkalinity.<br />
Nalco WT-<strong>222</strong> will provide protection over a wide range of operating conditions.<br />
Nalco WT-<strong>222</strong> can provide the following benefits in customer systems:<br />
Management of cooling system operation based on the operational stresses placed upon it.<br />
Extended tube bundle and equipment life due to reduced corrosion and scale<br />
Reduced energy costs due to cleaner heat transfer surfaces<br />
PHYSICAL & CHEMICAL PROPERTIES<br />
These properties are typical. Refer to the Material Safety Data Sheet (MSDS),<br />
SECTION 9, for the most current data.<br />
Form Liquid<br />
Color Light Yellow<br />
Odor None<br />
Specific Gravity @ 77°F (25°C) 1.12<br />
Density 1.12 kg/l [ 9.3 lb/gal ]<br />
pH (100%) 0.4<br />
Viscosity @ 68°F (20°C) 6 cp<br />
Freezing Point 11°F [-12°C]<br />
Freeze-Thaw Recovery Complete<br />
Boiling Point 212°F [100°C]<br />
Solubility in Water Complete<br />
VOC Content Not Available<br />
Product Viscosity vs. Temperature<br />
Viscosity (cp) Temperature<br />
10 -3°C (26.6°F)<br />
7 9°C (48.2°F)<br />
6 24°C (75.2°F)<br />
REGULATORY APPROVALS<br />
Nalco WT-<strong>222</strong> is intended for industrial use only. It must not be fed to potable water systems.<br />
Refer to the Material Safety Data Sheet (MSDS), SECTION 15 for the most recent information on approvals.<br />
09-07-09/JLM ; NALCO WT-<strong>222</strong> CPP-DPL 1
MATERIALS OF COMPATIBILITY<br />
Compatible Not Compatible<br />
Buna-N Aluminum<br />
Plasite 4005 Brass<br />
Plasite 6000 Carbon Steel<br />
Plasite 7122 Nickel<br />
Hypalon Stainless Steel 304<br />
Neoprene Stainless Steel 316<br />
Polyethylene<br />
Polypropylene<br />
PVC<br />
Teflon<br />
Polyurethane<br />
Vinyl<br />
Viton<br />
DOSAGE AND FEEDING<br />
For complete dosage and feeding recommendations, consult your Nalco Sales Engineer.<br />
DOSAGE REQUIREMENTS<br />
START-UP<br />
Initially, feed Nalco WT-<strong>222</strong> at the target dosage plus 25% based upon system volume. If the system volume<br />
is unknown or uncertain, perform Diagnostic TRASAR® to determine. See Figure 1 "Nalco WT-<strong>222</strong> control<br />
chart " to determine the appropriate dosage of Nalco WT-<strong>222</strong> and see CPP Presection under A-Z -LITE<br />
section for further details regarding proper program control limits. Also, remember that the pH should never<br />
rise above 8.5.<br />
09-07-09/JLM ; NALCO WT-<strong>222</strong> CPP-DPL 2
M-alkalinity M-alkalinity (ppm (ppm CaCo3) CaCo3)<br />
350<br />
300<br />
200<br />
100<br />
0<br />
Figure 1. Nalco WT-<strong>222</strong> Control Chart<br />
CHART TRASAR 23<strong>222</strong><br />
100 ppm<br />
125 ppm<br />
100 200 300 400 500 600 700 800<br />
Ca-Hardness (ppm CaCo3)<br />
PRODUCT FEEDING AND PROGRAM COMPATIBILITY<br />
150 ppm<br />
Nalco WT-<strong>222</strong> should be fed via a closed feed system. A closed feed system is defined as a system in which<br />
fluid is moved from a closed storage vessel into a treated media without exposure to the atmosphere except<br />
through normal venting or pressure relief devices.<br />
Nalco WT-<strong>222</strong> should be fed continuously to assure that adequate zinc residuals are maintained at all times.<br />
Slug feed can cause localized chemical concentrations, and undesirable reactions such as precipitation of<br />
zinc in the bulk water and potential reactions with other chemicals in the cooling water. Low product levels<br />
will result in excessive corrosion.<br />
Nalco WT-<strong>222</strong> should be applied to a point in the system where rapid mixing and adequate distribution will<br />
occur. The suction side of the circulating water pump is recommended.<br />
This product contains anionic materials. Do not feed cationic containing materials with this program.<br />
Periodic testing for zinc or phosphate may be useful. The soluble zinc level (0.45 micron filter) should be at<br />
least 0.3 ppm. The difference between the filtered and unfiltered orthophosphate should be < 2 ppm.<br />
Monitoring the water chemistry will help determine how well the chemical treatment program is working. The<br />
following tests should be conducted on a routine basis to ensure that the water chemistry is kept in an<br />
appropriate range.<br />
09-07-09/JLM ; NALCO WT-<strong>222</strong> CPP-DPL 3
Parameters Range Method or Kit<br />
pH 7.3-8.5 pH meter<br />
Conductivity