PRODUCT NAME<br />

NALCO® WT-<strong>222</strong><br />

Corrosion Inhibitor<br />

PRODUCT DESCRIPTION AND APPLICATION<br />

Nalco WT-<strong>222</strong> is a multifunctional, one-drum, scale and corrosion inhibitor for industrial open recirculating<br />

cooling water systems.<br />

This product was designed for systems with corrosive water and low to medium hardness and/or alkalinity.<br />

Nalco WT-<strong>222</strong> will provide protection over a wide range of operating conditions.<br />

Nalco WT-<strong>222</strong> can provide the following benefits in customer systems:<br />

Management of cooling system operation based on the operational stresses placed upon it.<br />

Extended tube bundle and equipment life due to reduced corrosion and scale<br />

Reduced energy costs due to cleaner heat transfer surfaces<br />

PHYSICAL & CHEMICAL PROPERTIES<br />

These properties are typical. Refer to the Material Safety Data Sheet (MSDS),<br />

SECTION 9, for the most current data.<br />

Form Liquid<br />

Color Light Yellow<br />

Odor None<br />

Specific Gravity @ 77°F (25°C) 1.12<br />

Density 1.12 kg/l [ 9.3 lb/gal ]<br />

pH (100%) 0.4<br />

Viscosity @ 68°F (20°C) 6 cp<br />

Freezing Point 11°F [-12°C]<br />

Freeze-Thaw Recovery Complete<br />

Boiling Point 212°F [100°C]<br />

Solubility in Water Complete<br />

VOC Content Not Available<br />

Product Viscosity vs. Temperature<br />

Viscosity (cp) Temperature<br />

10 -3°C (26.6°F)<br />

7 9°C (48.2°F)<br />

6 24°C (75.2°F)<br />

REGULATORY APPROVALS<br />

Nalco WT-<strong>222</strong> is intended for industrial use only. It must not be fed to potable water systems.<br />

Refer to the Material Safety Data Sheet (MSDS), SECTION 15 for the most recent information on approvals.<br />

09-07-09/JLM ; NALCO WT-<strong>222</strong> CPP-DPL 1


MATERIALS OF COMPATIBILITY<br />

Compatible Not Compatible<br />

Buna-N Aluminum<br />

Plasite 4005 Brass<br />

Plasite 6000 Carbon Steel<br />

Plasite 7122 Nickel<br />

Hypalon Stainless Steel 304<br />

Neoprene Stainless Steel 316<br />

Polyethylene<br />

Polypropylene<br />

PVC<br />

Teflon<br />

Polyurethane<br />

Vinyl<br />

Viton<br />

DOSAGE AND FEEDING<br />

For complete dosage and feeding recommendations, consult your Nalco Sales Engineer.<br />

DOSAGE REQUIREMENTS<br />

START-UP<br />

Initially, feed Nalco WT-<strong>222</strong> at the target dosage plus 25% based upon system volume. If the system volume<br />

is unknown or uncertain, perform Diagnostic TRASAR® to determine. See Figure 1 "Nalco WT-<strong>222</strong> control<br />

chart " to determine the appropriate dosage of Nalco WT-<strong>222</strong> and see CPP Presection under A-Z -LITE<br />

section for further details regarding proper program control limits. Also, remember that the pH should never<br />

rise above 8.5.<br />

09-07-09/JLM ; NALCO WT-<strong>222</strong> CPP-DPL 2


M-alkalinity M-alkalinity (ppm (ppm CaCo3) CaCo3)<br />

350<br />

300<br />

200<br />

100<br />

0<br />

Figure 1. Nalco WT-<strong>222</strong> Control Chart<br />

CHART TRASAR 23<strong>222</strong><br />

100 ppm<br />

125 ppm<br />

100 200 300 400 500 600 700 800<br />

Ca-Hardness (ppm CaCo3)<br />

PRODUCT FEEDING AND PROGRAM COMPATIBILITY<br />

150 ppm<br />

Nalco WT-<strong>222</strong> should be fed via a closed feed system. A closed feed system is defined as a system in which<br />

fluid is moved from a closed storage vessel into a treated media without exposure to the atmosphere except<br />

through normal venting or pressure relief devices.<br />

Nalco WT-<strong>222</strong> should be fed continuously to assure that adequate zinc residuals are maintained at all times.<br />

Slug feed can cause localized chemical concentrations, and undesirable reactions such as precipitation of<br />

zinc in the bulk water and potential reactions with other chemicals in the cooling water. Low product levels<br />

will result in excessive corrosion.<br />

Nalco WT-<strong>222</strong> should be applied to a point in the system where rapid mixing and adequate distribution will<br />

occur. The suction side of the circulating water pump is recommended.<br />

This product contains anionic materials. Do not feed cationic containing materials with this program.<br />

Periodic testing for zinc or phosphate may be useful. The soluble zinc level (0.45 micron filter) should be at<br />

least 0.3 ppm. The difference between the filtered and unfiltered orthophosphate should be < 2 ppm.<br />

Monitoring the water chemistry will help determine how well the chemical treatment program is working. The<br />

following tests should be conducted on a routine basis to ensure that the water chemistry is kept in an<br />

appropriate range.<br />

09-07-09/JLM ; NALCO WT-<strong>222</strong> CPP-DPL 3


Parameters Range Method or Kit<br />

pH 7.3-8.5 pH meter<br />

Conductivity

Hooray! Your file is uploaded and ready to be published.