5CSL0-04B<br />

AUUW426D[UU42W U3D] (Synchro-Duo, Trio, Quartet simultaneous operation)<br />

• Cooling<br />

Simultaneous<br />

Operation<br />

Combination of indoor units<br />

(kBtu/h)<br />

Possiblity Total<br />

Combination table<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

(A)<br />

(kW)<br />

Btu/h kW Btu/h kW Btu/h kW Min Rated Max Min Rated Max<br />

Duo 24+24 48 19,110 5.60 47,770 14.00 47,770 14.00 8.20 20.50 20.50 1.84 4.60 4.60<br />

Trio 18+18+18 54 20,470 6.00 51,180 15.00 51,180 15.00 9.00 22.60 22.60 2.08 5.20 5.20<br />

Quartet 12+12+12+12 48 19,110 5.60 47,770 14.00 47,770 14.00 8.20 20.50 20.50 1.84 4.60 4.60<br />

• Heating<br />

Simultaneous<br />

Operation<br />

Duo 24+24 48 21,840 6.40 54,600 16.00 60,050 16.00 8.20 20.50 20.50 1.84 4.60 4.60<br />

Trio 18+18+18 54 23,200 6.80 58,000 17.00 58,000 17.00 8.70 21.70 21.70 2.08 5.00 5.00<br />

Quartet 12+12+12+12 48 21,840 6.40 54,600 16.00 60,050 16.00 8.20 20.50 20.50 1.84 4.60 4.60<br />

Simultaneous<br />

Operation<br />

• Notes<br />

Combination of indoor units<br />

(kBtu/h)<br />

Possiblity Total<br />

Combination of indoor units<br />

(kBtu/h)<br />

Possiblity Total<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

(A)<br />

(kW)<br />

Btu/h kW Btu/h kW Btu/h kW Min Rated Max Min Rated Max<br />

AUUW486D[UU48W U3D] (Synchro-Duo, Trio, Quartet simultaneous operation)<br />

• Cooling<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

(A)<br />

(kW)<br />

Btu/h kW Btu/h kW Btu/h kW Min Rated Max Min Rated Max<br />

Duo 24+24 48 19,110 5.60 47,770 14.00 52,550 15.40 8.20 20.50 22.60 1.84 4.60 5.06<br />

Trio 18+18+18 54 20,470 6.00 51,180 15.00 56,300 16.50 9.00 22.60 24.90 2.08 5.20 5.72<br />

Quartet 12+12+12+12 48 19,110 5.60 47,770 14.00 52,550 15.40 8.20 20.50 22.60 1.84 4.60 5.06<br />

• Heating<br />

Simultaneous<br />

Operation<br />

Combination of indoor units<br />

(kBtu/h)<br />

Possiblity Total<br />

Cooling Capacity<br />

Current<br />

Input<br />

Min Rated Max<br />

(A)<br />

(kW)<br />

Btu/h kW Btu/h kW Btu/h kW Min Rated Max Min Rated Max<br />

Duo 24+24 48 21,840 6.40 54,600 16.00 60,050 17.60 8.20 20.50 22.60 1.84 4.60 5.06<br />

Trio 18+18+18 54 23,200 6.80 58,000 17.00 58,000 18.70 8.70 21.70 23.90 2.08 5.00 5.50<br />

Quartet 12+12+12+12 48 21,840 6.40 54,600 16.00 60,050 17.60 8.20 20.50 22.60 1.84 4.60 5.06<br />

1. Individual indoor capacities are not given because the combinations are for simultaneous operation.<br />

2. Rated cooling capacities are based on the following conditions:<br />

Indoor air temperature: 27°CDB, 19.0°CWB, outdoor temperature 35°CDB.<br />

Rated heating capacities are based on the following conditions:<br />

Indoor air temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB.<br />