06.06.2013 Views

Product Data

Product Data

Product Data

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

223A<br />

DETAILED COOLING CAPACITIES # CONTINUED<br />

CONDENSER ENTERING AIR TEMPERATURES ° F (° C)<br />

EVAPORATOR AIR<br />

75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)<br />

CFM<br />

EWB<br />

Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total<br />

Sys.<br />

Sys.<br />

Sys.<br />

Sys.<br />

Sys.<br />

Sys.<br />

°F(°C) Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW** Total Sens‡ KW**<br />

223A*A060---B Outdoor Section With FY4ANF060 Indoor Section<br />

72 (22.2) 71.08 36.09 4.41 67.69 34.77 4.86 64.09 33.39 5.36 60.33 31.96 5.90 56.30 30.45 6.50 51.84 28.81 7.14<br />

67 (19.4) 65.19 45.05 4.36 62.05 43.69 4.81 58.73 42.27 5.30 55.30 40.82 5.85 51.61 39.29 6.44 47.57 37.62 7.09<br />

1750 63 (17.2)†† 60.79 43.67 4.31 57.85 42.31 4.76 54.78 40.90 5.26 51.57 39.45 5.81 48.15 37.91 6.40 44.41 36.26 7.05<br />

62 (16.7) 59.61 53.90 4.30 56.75 52.49 4.75 53.77 51.00 5.25 50.69 49.41 5.80 47.50 47.50 6.40 45.90 45.90 6.36<br />

57 (13.9) 57.48 57.48 4.28 55.20 55.20 4.74 52.79 52.79 5.24 50.24 50.24 5.79 47.49 47.49 6.40 44.42 44.42 7.06<br />

72 (22.2) 72.12 37.62 4.54 68.55 36.26 4.99 64.87 34.89 5.48 60.98 33.44 6.03 56.80 31.91 6.62 52.19 30.25 7.26<br />

67 (19.4) 66.24 47.72 4.48 62.96 46.34 4.93 59.50 44.89 5.43 55.93 43.42 5.97 52.11 41.85 6.57 47.93 40.14 7.21<br />

2000 63 (17.2)†† 61.83 46.19 4.44 58.77 44.80 4.89 55.56 43.36 5.38 52.22 41.88 5.93 48.67 40.31 6.53 44.80 38.60 7.18<br />

62 (16.7) 60.73 57.58 4.43 57.79 56.05 4.88 54.77 54.33 5.38 51.88 51.88 5.93 48.94 48.94 6.53 47.37 47.37 6.51<br />

57 (13.9) 59.63 59.63 4.42 57.18 57.18 4.87 54.60 54.60 5.38 51.89 51.89 5.93 48.94 48.94 6.53 45.66 45.66 7.19<br />

72 (22.2) 72.83 39.05 4.66 69.16 37.69 5.11 65.40 36.31 5.61 61.39 34.85 6.15 57.10 33.30 6.74 52.35 31.61 7.37<br />

67 (19.4) 66.96 50.26 4.61 63.58 48.86 5.06 60.01 47.39 5.55 56.35 45.89 6.09 52.43 44.28 6.69 48.14 42.52 7.33<br />

2250 63 (17.2)†† 62.58 48.57 4.56 59.40 47.16 5.01 56.09 45.69 5.51 52.66 44.18 6.05 49.01 42.56 6.65 45.05 40.80 7.30<br />

62 (16.7) 61.68 60.83 4.56 58.79 58.79 5.01 56.05 56.05 5.51 53.19 53.19 6.06 50.08 50.08 6.66 46.62 46.62 7.31<br />

57 (13.9) 61.37 61.37 4.55 58.79 58.79 5.01 56.06 56.06 5.51 53.19 53.19 6.06 50.08 50.08 6.66 46.62 46.62 7.31<br />

COOLING INDOOR<br />

COOLING INDOOR<br />

COOLING INDOOR<br />

CAPACITY POWER FURNACE MODEL<br />

CAPACITY POWER FURNACE MODEL<br />

CAPACITY POWER FURNACE MODEL<br />

MODEL<br />

MODEL<br />

MODEL<br />

*FY4ANB060 1.00 1.00<br />

CNPH*6024A** 0.98 0.95 315(A,J)AV066135<br />

CNPH*6024A** 0.97 0.92 353AAV060120<br />

FE4ANB006 1.01 0.95<br />

CNPV*6024A** 0.98 0.95 315(A,J)AV066135<br />

CNPV*6024A** 0.97 0.92 353AAV060120<br />

FV4BNB006 1.01 0.95<br />

CSPH*6012A** 0.99 0.93 315(A,J)AV066135<br />

CSPH*6012A** 0.98 0.92 353AAV060120<br />

FX4CN(B,F)060 1.01 0.91<br />

CAP**6024A** 0.99 0.93 315(A,J)AV066155<br />

CAP**6021A** 0.98 0.92 313*AV048090<br />

CAP**6021A** 0.99 0.99<br />

CNPH*6024A** 0.99 0.93 315(A,J)AV066155<br />

CNPH*6024A** 0.98 0.92 313*AV048090<br />

CAP**6024A** 1.01 1.01<br />

CNPV*6024A** 0.99 0.93 315(A,J)AV066155<br />

CSPH*6012A** 0.99 0.93 313*AV048090<br />

CNPH*6024A** 1.00 1.00<br />

CSPH*6012A** 0.99 0.93 315(A,J)AV066155<br />

CAP**6021A** 0.99 0.93 313*AV060110<br />

CNPV*6024A** 1.00 1.00<br />

CNPH*6024A** 0.97 0.91 353AAV048080<br />

CNPH*6024A** 0.98 0.92 313*AV060110<br />

CSPH*6012A** 1.01 1.01<br />

CSPH*6012A** 0.97 0.92 353AAV048080<br />

CSPH*6012A** 0.99 0.93 313*AV060110<br />

CAP**6021A** 0.97 0.94 315(A,J)AV060110<br />

CAP**6021A** 0.97 0.92 353AAV060100<br />

CAP**6024A** 0.98 0.92 313*AV060135<br />

CNPH*6024A** 0.98 0.95 315(A,J)AV060110<br />

CNPH*6024A** 0.97 0.92 353AAV060100<br />

CNPH*6024A** 0.98 0.92 313*AV060135<br />

CSPH*6012A** 0.99 0.96 315(A,J)AV060110<br />

CSPH*6012A** 0.98 0.92 353AAV060100<br />

CNPV*6024A** 0.98 0.92 313*AV060135<br />

CAP**6024A** 0.99 0.93 315(A,J)AV066135<br />

CAP**6024A** 0.97 0.92 353AAV060120<br />

CSPH*6012A** 0.99 0.93 313*AV060135<br />

46<br />

{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.<br />

} Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh<br />

(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F (27_C).<br />

# Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240---94. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may<br />

occur.