Pump Control Panels - Siemens

Pump Control Panels - Siemens

Pump Control Panels - Siemens

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Pump</strong> <strong>Control</strong> <strong>Panels</strong><br />

Class 87, 88<br />

General<br />

Features<br />

▪ Fully Gasketed NEMA 3R Rainproof<br />

Enclosures<br />

▪ 100,000 Amp Interrupting Capacity<br />

with Class R Fuses<br />

▪ Heavy Duty NEMA Starters<br />

▪ Solid State or Ambient Compensated<br />

Bimetal Overload Relays<br />

▪ Heavy Duty Disconnect Handle<br />

▪ Available in Reduced Voltage Versions<br />

▪ Bold Pilot Legend on Front<br />

▪ Generous Accessory Space<br />

▪ Copper Grounding Lug For Three<br />

#6 Wires<br />

▪ UL Listed for Outdoor Use and<br />

Service Equipment File #E14900<br />

8/56<br />

Application<br />

Heavy duty pump control panels are<br />

designed to withstand the most<br />

demanding environments. Typical<br />

applications include irrigation, agriculture,<br />

petrochemical, wastewater treatment<br />

and wherever motor control is<br />

challenged by harsh elements.<br />

Rugged pump control panels utilized<br />

cold forming “tox” process. They are<br />

more rainproof, sleet and ice<br />

resistant than in the past.<br />

Installation is easy. <strong>Panels</strong> are factory<br />

wired to provide flexible control and<br />

protect against short circuits and<br />

overloads. Ample space is provided<br />

for field modifications and installation<br />

of accessories.<br />

The pump control panels feature a full<br />

sized removable auxiliary panel for the<br />

mounting of accessories. The fusible<br />

version features fuse clips for full sized<br />

RK5 or compact class J fuses and<br />

accessory mounting space for the<br />

most commonly used accessories.<br />

Class 87 pump panels become jockey<br />

pump panels with the addition of a<br />

pressure switch (see field modifications).<br />

The jockey pump’s primary function is to<br />

maintain water pressure at a preset level<br />

and thus compensate for possible<br />

shortage of water in the pumping<br />

system. When the water pressure<br />

drops below the preset level, the<br />

pressure switch energizes the starter<br />

which in turn activates the jockey pump.<br />

The water pressure is then brought back<br />

up to the desired level. This insures the<br />

maintenance of proper water pressure<br />

at all times.<br />

Features<br />

Specified by Fortune 500 companies,<br />

ESP100 or thermal starters offer<br />

prolonged service under severe duty<br />

conditions. NEMA rated, these starters<br />

utilize large silver cadmium oxide<br />

contacts and wide copper heat sinks<br />

to ensure rapid heat dissipation and<br />

maximum electrical life.<br />

ESP100 solid state overload<br />

relays provide phase loss protection<br />

for the motor by tripping within three<br />

seconds upon complete loss of one<br />

phase in a three phase circuit. Each<br />

overload has a 2:1 (4:1 in lower ranges)<br />

FLA adjustment range with an<br />

adjustment dial reading out in FLA.<br />

This feature allows for extreme fine<br />

tuning. Their heaterless construction<br />

minimizes energy costs and costs of<br />

cabinet ventilation or cooling. The class<br />

87 pump panel comes with class 10<br />

trip standard.<br />

The ambient compensated bimetal<br />

overload relays are designed to<br />

parallel thermal characteristics of typical<br />

pump motors. They prevent nuisance<br />

trips that may result from operation of<br />

the control in a higher ambient temperature<br />

than that at the pump. These relays<br />

are trip-free, tamperproof and can be set<br />

to reset automatically or manually.<br />

HOA and Start Pushbutton<br />

Every pump panel comes with an HOA<br />

and a start pushbutton.<br />

Half Size Starters<br />

<strong>Siemens</strong> motor matched starters feature<br />

all the rugged performance characteristics<br />

of our NEMA rated starter sizes, but are<br />

fractionally sized to more closely match<br />

your exact motor rating. As a result,<br />

significant economic savings are made<br />

possible without sacrificing the reliability<br />

you expect from a heavy duty starter.<br />

These additional starter sizes have the<br />

reserve capacity to handle occasional<br />

plugging and jogging without de-rating<br />

the device.<br />

<strong>Siemens</strong> motor matched can save hundreds,<br />

even thousands of dollars per project.<br />

<strong>Siemens</strong> motor matched starters comply<br />

with NEMA, UL and CSA standards.<br />

<strong>Siemens</strong> Energy & Automation, Inc.<br />

Industrial <strong>Control</strong>s Catalog


<strong>Panels</strong> are predrilled for easy repositioning<br />

of the fuse trailer block to accommodate<br />

250 and 600 volt fuses and full sized RK<br />

or compact J fuses. Circuit breakers are<br />

also available.<br />

New Heavy Duty Fusible<br />

Disconnect Switch<br />

The disconnect switch has been<br />

made even better to give you greater<br />

advantages:<br />

▪ Visible blades for the highest<br />

level of safety.<br />

▪ Double Break Switching Action<br />

to reduce arcing, increase lifetime<br />

and eliminate the “electric hinge”.<br />

▪ Oversized lugs are standard.<br />

▪ Line side shield to help guard<br />

personnel from contact with live parts.<br />

Motor Circuit Protector<br />

The motor circuit protector provides fast,<br />

accurate fault clearing that will minimize<br />

damage to the motor and control<br />

apparatus and protect branch circuit<br />

conductors. Continuous current ratings<br />

and adjustable trip ranges meet NEC<br />

requirements for full load and locked<br />

rotor currents. The adjustable<br />

instantaneous trip point can be set<br />

precisely to assure fault protection<br />

and eliminate nuisance tripping.<br />

Removable Door<br />

Enclosure door may be lifted off to make<br />

wiring easier.<br />

Mounting Flanges<br />

Convenient flanges at top and bottom<br />

of the enclosure provide easy mounting.<br />

They fit pole or flat surfaces using<br />

keyhole slots.<br />

Quarter Turn Latches<br />

Quarter turns are utilized to secure the<br />

door.<br />

Wind Catches<br />

A wind catch is provided to prevent the<br />

door from slamming shut (or open) due<br />

to high wind conditions.<br />

<strong>Siemens</strong> Energy & Automation, Inc.<br />

Industrial <strong>Control</strong>s Catalog<br />

Safety Disconnect Handle<br />

Up to three padlocks can be used to lock<br />

the disconnect in the OFF position.<br />

Maintenance work can be performed<br />

without hazard to personnel.<br />

External Reset<br />

The overload relay may be quickly reset<br />

by means of a button on the front of the<br />

enclosure.<br />

Bold Pilot Legend<br />

Provides positive indication of the<br />

selector switch position for use to<br />

stop the pump motor.<br />

Ground Lugs<br />

Insures proper connecting of ground<br />

wires and lightning arresters.<br />

UL Listed<br />

Assures proper construction throughout<br />

control panel.<br />

Reduced Voltage<br />

Available in part winding, wye delta and<br />

auto transformer types, these controls<br />

may be necessary where the power<br />

company limits the amount of current<br />

drawn from its lines, or where starting<br />

torque must be reduced.<br />

Fully gasketed NEMA 3/12 weatherproof<br />

enclosures are supplied with<br />

Class 88 reduced voltage starters.<br />

Part Winding Starters apply starting<br />

current in timed steps to minimize<br />

voltage fluctuations.<br />

Auto Transformer Starters maintain<br />

a closed circuit during transition and<br />

eliminate voltage or current surges.<br />

They draw less current than part winding<br />

starters and are well suited for starting<br />

motors over 20 Hp.<br />

Wye Delta starters and motors are<br />

used in areas where the power supply is<br />

inadequate to supply full starting current<br />

without objectionable voltage drop or for<br />

applications where low starting torque is<br />

required. Centrifugal pumps and similar<br />

apparatus requiring a low starting torque<br />

are typical applications. Both ends of all<br />

three windings of the wye delta motor<br />

are brought out so that they may be<br />

accessible for reconnecting from wye<br />

to delta.<br />

<strong>Pump</strong> <strong>Control</strong> <strong>Panels</strong><br />

Class 87, 88<br />

General<br />

Auxiliary Equipment<br />

Pilot Lights are easily installed on the<br />

enclosure. Oil Tight and Heavy Duty, they<br />

meet NEMA A600 requirements.<br />

Lightning Arresters protect the control<br />

panel from lightning induced surges.<br />

Undervoltage and Phase Sensing<br />

Relays protect the pump against low<br />

voltage, voltage imbalance, loss of phase<br />

and phase reversal.<br />

Anti-Backspin Timers prevent the<br />

motor from starting during motor/shaft<br />

backspin.<br />

The TOX Box<br />

<strong>Siemens</strong> uses the TOX process to<br />

manufacture the enclosures for the<br />

pump panels.<br />

Advantages of the TOX process:<br />

▪ Joints are 50-70% stronger.<br />

▪ Since the TOX process compresses<br />

the metal at the joint, it does not<br />

leave the high stresses in the metal.<br />

▪ Increased corrosion resistance.<br />

The protective layer on the metal is<br />

not damaged in the process, but<br />

instead flows with the material.<br />

8/57


Reduced Voltage <strong>Pump</strong> <strong>Panels</strong><br />

Auto Transformer & Part winding [2 step] with Solid State Overload<br />

Selection<br />

Ordering Information<br />

Technical Data see www.sea.siemens.com/controls.<br />

Field Modification Kits see page 8/79.<br />

Factory Modifications see page 8/93.<br />

Dimensions see page 8/110.<br />

Wiring Diagrams see page 8/137.<br />

Replacement Parts see pages 8/152.<br />

Auto Transformer Type<br />

Part Winding 2 Step<br />

8/60<br />

Discount Code: NEMA <strong>Control</strong><br />

Coil and <strong>Control</strong> Voltage<br />

The coil voltage on the contactors will be<br />

the motor voltage. A CPT will be supplied<br />

to provide the control voltage. The control<br />

voltage will be 120V.<br />

To change the control voltage to customer<br />

supplied (no CPT included), change the<br />

9th character to the following:<br />

for 24V , use "J"<br />

for 120V, use "F"<br />

Fusible Disconnect Circuit Breaker<br />

Motor Max OL amp NEMA Half Fuse Clip List Circuit Breaker List<br />

Voltage Hp range Size Size Size Catalog Number Price $ Amps Catalog Number Price $<br />

230 15 22-45 2 — 60A/250V 88FSHT2FG 6402. 50 88FSHT2MG 6487.<br />

20 30-60 — 2 1/2 100A/250V 88GSJT2FG 8659. 100 88GSJT2MG 8836.<br />

30 45-90 3 — 100A/250V 88HSKT2FG 9241. 100 88HSKT2MG 10123.<br />

40 57-115 — 3 1/2 200A/250V 88ISLT2FG 13128. 125 88ISLT2MG 14499.<br />

50 67-135 4 — 200A/250V 88JSMT2FG 13867. 150 88JSMT2MG 15239.<br />

75 100-210 5 — — — — 250 88KSST2MG 23913.<br />

100 100-270 5 — 400A/250V 88KSUT2FG 24013. 400 88KSUT2MG 25670.<br />

200 200-540 6 — — — — 600 88MSXT2MH 42954.<br />

460 25 22-45 2 — 60A/600V 88FSHT4FH 6826. 50 88FSHT4MH 6937.<br />

30 22-45 — 2 1/2 60A/600V 88GSHT4FH 8983. 50 88GSHT4MH 9071.<br />

50 45-90 3 — 100A/600V 88HSKT4FH 9568. 100 88HSKT4MH 10042.<br />

75 57-115 — 3 1/2 200A/600V 88ISLT4FH 13574. 125 88ISLT4MH 14676.<br />

100 67-135 4 — 200A/600V 88JSMT4FH 15146. 150 88JSMT4MH 15601.<br />

150 100-210 5 — — — — 250 88KSST4MH 24560.<br />

200 100-270 5 — 400A/600V 88KSUT4FH 26463. 400 88KSUT4MH 27750.<br />

400 200-540 6 — 600A/600V 88MSXT4FH 38713. 600 88MSXT4MH 42950.<br />

Fusible Disconnect Circuit Breaker<br />

Motor Max OL amp NEMA Half Fuse Clip List Circuit Breaker List<br />

Voltage Hp range Size Size Size Catalog Number Price $ Amps Catalog Number Price $<br />

230 20 20-40 — 1 3/4 100A/250V 88ESGP2FG 3829. 100 88ESGP2MG 3590.<br />

25 22-45 2 — 100A/250V 88FSHP2FG 4145. 100 88FSHP2MG 4014.<br />

40 30-60 — 2 1/2 200A/250V 88GSJP2FG 5855. 100 88GSJP2MG 5701.<br />

50 45-90 3 — 200A/250V 88HSKP2FG 6348. 150 88HSKP2MG 6194.<br />

60 57-115 — 3 1/2 200A/250V 88ISLP2FG 11248. 250 88ISLP2MG 12111.<br />

75 67-135 4 — 400A/250V 88JSMP2FG 11872. 250 88JSMP2MG 12727.<br />

125 100-210 5 — — — — 400 88KSSP2MG 22426.<br />

150 100-270 5 — 600A/250V 88KSUP2FG 22958. 600 88KSUP2MG 23505.<br />

460 30 13-27 — 1 3/4 100A/600V 88ESFP4FH 3829. 50 88ESFP4MH 3590.<br />

40 22-45 2 — 100A/600V 88FSHP4FH 4145. 100 88FSHP4MH 4014.<br />

60 30-60 — 2 1/2 200A/600V 88GSJP4FH 5855. 100 88GSJP4MH 5701.<br />

75 30-60 3 — 200A/600V 88HSJP4FH 6348. 125 88HSJP4MH 6194.<br />

100 57-115 — 3 1/2 200A/600V 88ISLP4FH 11248. 150 88ISLP4MH 12111.<br />

150 67-135 4 — 400A/600V 88JSMP4FH 11872. 250 88JSMP4MH 12727.<br />

250 100-210 5 — — — — 400 88KSSP4MH 23505.<br />

350 100-270 5 — 600A/600V 88KSUP4FH 22958. 600 88KSUP4MH 42287.<br />

<strong>Siemens</strong> Energy & Automation, Inc.<br />

Industrial <strong>Control</strong>s Catalog


Ordering Information<br />

Technical Data see www.sea.siemens.com/controls.<br />

Field Modification Kits see page 8/79.<br />

Factory Modifications see page 8/93.<br />

Dimensions see page 8/110.<br />

Wiring Diagrams see page 8/137.<br />

Replacement Parts see pages 8/152.<br />

Wye Delta<br />

<strong>Siemens</strong> Energy & Automation, Inc.<br />

Industrial <strong>Control</strong>s Catalog<br />

Discount Code: NEMA <strong>Control</strong><br />

Reduced Voltage <strong>Pump</strong> <strong>Panels</strong><br />

Wye Delta with Solid State Overload<br />

Open Transition Closed Transition<br />

Coil and <strong>Control</strong> Voltage<br />

Selection<br />

The coil voltage on the contactors will be<br />

the motor voltage. A CPT will be supplied<br />

to provide the control voltage. The control<br />

voltage will be 120V.<br />

To change the control voltage to customer<br />

supplied (no CPT included), change the<br />

9th character to the following:<br />

for 24V , use "J"<br />

for 120V, use "F"<br />

Fusible Disconnect Circuit Breaker Fusible Disconnect Circuit Breaker<br />

Motor NEMA Half<br />

Fuse<br />

Clip MCP Catalog List Catalog List Catalog List Catalog List<br />

Voltage Max Hp Size Size Amps Amps Number Price $ Number Price $ Number Price $ Number Price $<br />

10 1 — 60 50 88DSF06FD 4815. 88DSF06MD 5115. 88DSFC6FD 6209. 88DSFC6MD 6510.<br />

15 — 1 3⁄4 100 100 88ESG06FD 5408. 88ESG06MD 5385. 88ESGC6FD 6564. 88ESGC6MD 6818.<br />

20 2 — 100 100 88FSH06FD 6163. 88FSH06MD 5909. 88FSHC6FD 7303. 88FSHC6MD 7350.<br />

30 — 2 1⁄2 200 125 88GSJ06FD 7727. 88GSJ06MD 7820. 88GSJC6FD 9091. 88GSJC6MD 9491.<br />

200V 40 3 — 200 150 88HSK06FD 8320. 88HSK06MD 8721. 88HSKC6FD 10077. 88HSKC6MD 10477.<br />

50 — 3 1⁄2 200 250 88ISL06FD 14622. 88ISL06MD 15616. 88ISLC6FD 16802. 88ISLC6MD 18181.<br />

60 4 — 400 250 88ISL06FD 15161. 88JSM06MD 16540. 88ISLC6FD 18097. 88JSMC6MD 19476.<br />

75 5 — 400 400 88KSS06FD 22808. 88KSS06MD 26667. 88KSSC6FD 30458. 88KSSC6MD 30381.<br />

150 5 — 600 600 88KSU06FD 27573. 88KSU06MD 27080. 88KSUC6FD 31425. 88KSUC6MD 30932.<br />

300 6 — — 800 — — 88MSX06MD 50276. — — 88MSXC6MD 59706.<br />

10 1 — 60 50 88DSF02FG 4815. 88DSF02MG 5115. 88DSFC2FG 6209. 88DSFC2MG 6510.<br />

15 — 1 3⁄4 60 50 88ESG02FG 5323. 88ESG02MG 5385. 88ESGC2FG 6479. 88ESGC2MG 6818.<br />

25 2 — 100 100 88FSH02FG 6163. 88FSH02MG 5909. 88FSHC2FG 7303. 88FSHC2MG 7350.<br />

30 — 2 1⁄2 200 100 88GSJ02FG 7727. 88GSJ02MG 7820. 88GSJC2FG 9091. 88GSJC2MG 9491.<br />

230V 50 3 — 200 150 88HSK02FG 8320. 88HSK02MG 8721. 88HSKC2FG 10077. 88HSKC2MG 10477.<br />

60 — 3 1⁄2 200 250 88ISL02FG 14622. 88ISL02MG 15616. 88ISLC2FG 16802. 88ISLC2MG 18181.<br />

75 4 — 400 250 88JSM02FG 15161. 88JSM02MG 16540. 88JSMC2FG 18097. 88JSMC2MG 19476.<br />

100 5 — 400 400 88KSS02FG 22808. 88KSS02MG 26667 88KSSC2FG 30458. 88KSSC2MG 30381.<br />

150 5 — 600 600 88KSU02FG 27573. 88KSU02MG 27080. 88KSUC2FG 31425. 88KSUC2MG 30932.<br />

350 6 — — 1200 — — 88MSX02MG 50276. — — 88MSXC2MG 59706.<br />

15 1 — 60 30 88DSE04FH 4815. 88DSE04MH 5115. 88DSEC4FH 6209. 88DSEC4MH 6510.<br />

30 — 1 3⁄4 60 50 88ESF04FH 5339. 88ESF04MH 5385. 88ESFC4FH 6494. 88ESFC4MH 6818.<br />

40 2 — 100 100 88FSH04FH 5855. 88FSH04MH 5909. 88FSHC4FH 7465. 88FSHC4MH 7519.<br />

60 — 2 1⁄2 200 100 88GSJ04FH 7419. 88GSJ04MH 7820. 88GSJC4FH 9260. 88GSJC4MH 9661.<br />

460V 75 3 — 200 125 88GSJ04FH 8320. 88HSK04MH 8721. 88GSJC4FH 10901. 88HSKC4MH 11302.<br />

100 — 3 1⁄2 200 150 88ISL04FH 12727. 88ISL04MH 15616. 88ISLC4FH 17373. 88ISLC4MH 19044.<br />

150 4 — 400 250 88JSM04FH 15161. 88JSM04MH 16540. 88JSMC4FH 18775. 88JSMC4MH 20154.<br />

200 5 — 400 400 88KSS04FH 22808. 88KSS04MH 26667. 88KSSC4FH 31151. 88KSSC4MH 31074.<br />

300 5 — 600 600 88KSU04FH 27573. 88KSU04MH 27080. 88KSUC4FH 33096. 88KSUC4MH 32603.<br />

700 6 — — 1200 — — 88MSX04MH 50276. — — 88MSXC4MH 59706.<br />

15 1 — 60 30 88DSE05FE 4815. 88DSE05ME 5115. 88DSEC5FE 6209. 88DSEC5ME 6510.<br />

30 — 1 3⁄4 60 50 88ESF05FE 5339. 88ESF05ME 5385. 88ESFC5FE 6494. 88ESFC5ME 6818.<br />

40 2 — 60 50 88FSF05FE 5855. 88FSF05ME 5909 88FSFC5FE 7465. 88FSFC5ME 7519.<br />

60 — 2 1⁄2 100 100 88GSH05FE 7419. 88GSH05ME 7820. 88GSHC5FE 9260. 88GSHC5ME 9661.<br />

575V 75 3 — 200 125 88HSJ05FE 8320. 88HSJ05ME 8721. 88HSJC5FE 10901. 88HSJC5ME 11302.<br />

100 — 3 1⁄2 200 150 88ISK05FE 12727. 88ISK05ME 15616. 88ISKC5FE 17373. 88ISKC5ME 19044.<br />

150 4 — 400 250 88ISK05FE 15161. 88JSM05ME 16540 88ISKC5FE 18775. 88JSMC5ME 20154.<br />

200 5 — 400 400 88KSS05FE 22808. 88KSS05ME 26667. 88KSSC5FE 31151. 88KSSC5ME 31074.<br />

300 5 — 600 400 88KSU05FE 27573. 88KSU05ME 27080. 88KSUC5FE 33096. 88KSUC5ME 32603.<br />

700 6 — — 1200 — — 88MSX05ME 50276. — — 88MSXC5ME 59706.<br />

8/61


<strong>Pump</strong> <strong>Control</strong> <strong>Panels</strong><br />

Standard <strong>Pump</strong> Panel with Solid State Overload<br />

Selection<br />

Coil Table<br />

60Hz Voltage Letter<br />

24 Separate <strong>Control</strong><br />

120 Separate <strong>Control</strong><br />

110–120/220–240<br />

J<br />

F<br />

A 200–208<br />

220–240<br />

220–240/440–480<br />

D<br />

G<br />

C 277<br />

440–480<br />

550–600<br />

L<br />

H<br />

E<br />

Fusible Disconnect<br />

200V 230V 460V 575V NEMA Size Half Size Overload Amp Range Fuse Clip Amps Catalog Number List Price $<br />

— — 1 1 1 — 0.75-3 Ordering Information<br />

Technical Data see www.sea.siemens.com/controls.<br />

<br />

<br />

<br />

Field Modification Kits see page 8/79.<br />

Factory Modifications see page 8/93.<br />

Dimensions see page 8/110.<br />

<br />

<br />

Wiring Diagrams see page 8/137.<br />

Replacement Parts see pages 8/152.<br />

Sizes 1-4 will be supplied standard with a 240/480 volt coil.<br />

To change the coil voltage, change the 8th character in the catalog<br />

number to the letter shown in the coil table.<br />

Sizes 5&6 will be supplied standard with a 480 volt coil. To change<br />

the coil voltage, change the 8th character in the catalog number to<br />

the letter shown in the coil table.<br />

30 87DSB6FC 1017.<br />

— — 5 5 1 — 2.5-10 30 87DSD6FC 1017.<br />

— — 7 1/2 10 1 — 9-18 30 87DSE6FC 1017.<br />

— — 7 1/2 10 1 — 9-18 60 87DSE60C 1032.<br />

— — 15 15 — 1 3/4 13-27 30 87ESF6FC 1194.<br />

— — 15 15 — 1 3/4 13-27 60 87ESF60C 1210.<br />

— — 15 20 2 — 13-27 60 87FSF6FC 1371.<br />

— — 25 25 2 — 22-45 60 87FSH6FC 1371.<br />

— — 25 25 2 — 22-45 100 87FSH60C 1456.<br />

— — 30 30 — 2 1/2 22-45 60 87GSH6FC 1957.<br />

— — 30 30 — 2 1/2 22-45 100 87GSH60C 2042.<br />

— — 50 50 3 — 45-90 100 87HSK6FC 2211.<br />

— — 50 50 3 — 45-90 200 87HSK60C 2373.<br />

— — 75 75 — 3 1/2 57-115 200 87ISL6FC 3760.<br />

— — 100 100 4 — 67-135 200 87JSM6FC 4068.<br />

— — 200 200 5 — 100-270 400 87KSU6FH 8844.<br />

— — 250 — 6 — 200-540 600 87MSW6FH 22330.<br />

2 2 — — 1 — 2.5-10 30 87DSD6LC 1002.<br />

3 3 — — 1 — 9-18 30 87DSE6LC 1002.<br />

7 1/2 7 1/2 — — 1 — 13-27 30 87DSF6LC 1002.<br />

7 1/2 7 1/2 — — 1 — 13-27 60 87DSF6PC 1017.<br />

10 10 — — — 1 3/4 20-40 60 87ESG6LC 1194.<br />

10 15 — — 2 — 22-45 60 87FSH6LC 1348.<br />

10 15 — — 2 — 22-45 100 87FSH6PC 1441.<br />

15 20 — — — 2 1/2 30-60 60 87GSJ6LC 1903.<br />

15 20 — — — 2 1/2 30-60 100 87GSJ6PC 1995.<br />

25 30 — — 3 — 45-90 100 87HSK6LC 2165.<br />

25 30 — — 3 — 45-90 200 87HSK6PC 2342.<br />

30 40 — — — 3 1/2 57-115 200 87ISL6LC 3729.<br />

40 50 — — 4 — 67-135 200 87JSM6LC 4037.<br />

75 100 — — 5 — 100-270 400 87KSU6LH 8659.<br />

Circuit Breaker<br />

200V 230V 460V 575V NEMA Size Half Size Overload Amp Range Motor Circuit Catalog Number List Price $<br />

Interrupter<br />

ETI Amps<br />

1/2 1/2 1 1 1 — 0.75-3 3 87DSB6MC 1279.<br />

1 1 3 3 1 — 2.5-10 10 87DSC6MC 1279.<br />

2 2 5 5 1 — 2.5-10 10 87DSD6MC 1279.<br />

3 3 7 1/2 10 1 — 9-18 25 87DSE6MC 1279.<br />

7 1/2 7 1/2 10 — 1 — 13-27 30 87DSF6MC 1279.<br />

— — 15 15 — 1 3/4 13-27 30 87ESF6MC 1433.<br />

10 10 — — — 1 3/4 20-40 50 87ESG6MC 1433.<br />

— — 15 20 2 — 13-27 30 87FSF6MC 1587.<br />

10 15 25 25 2 — 22-45 50 87FSH6MC 1587.<br />

— — 30 30 — 2 1/2 22-45 50 87GSH6MC 2072.<br />

15 20 — — — 2 1/2 30-60 100 87GSJ6MC 2072.<br />

25 30 50 50 3 — 45-90 100 87HSK6MC 2242.<br />

30 40 75 75 — 3 1/2 57-115 125 87ISL6MC 4438.<br />

40 50 100 100 4 — 67-135 150 87JSM6MC 4746.<br />

50 75 150 200 5 — 100-270 250 87KST6MH 10793.<br />

75 100 200 200 5 — 100-270 400 87KSU6MH 10793.<br />

100 125 250 300 6 — 200-540 400 87MSW6MH 23401.<br />

150 200 400 400 6 — 200-540 600 87MSX6MH 26902.<br />

Not available on Size 5 and larger.<br />

8/58<br />

For an overload amp range of 0.25-1A, change the 5th<br />

character from a 'B' to an 'A'.<br />

Discount Code: NEMA <strong>Control</strong><br />

<strong>Siemens</strong> Energy & Automation, Inc.<br />

Industrial <strong>Control</strong>s Catalog


Ordering Information<br />

Order 3 heater elements by code number at 11.60 each see page 8/145.<br />

Technical Data see www.sea.siemens.com/controls<br />

Field Modification Kits see page 8/79.<br />

Factory Modifications see page 8/93.<br />

Dimensions see page 8/110.<br />

Wiring Diagrams see page 8/137.<br />

Replacement Parts see pages 8/152.<br />

Sizes 1-4 will be supplied standard with a 230/480 volt coil. To change the coil<br />

voltage, change the 8th character in the catalog number to the letter shown in<br />

the coil table.<br />

Sizes 5&6 will be supplied standard with a 480 volt coil. To change the coil<br />

voltage, change the 8th character in the catalog number to the letter shown<br />

in the coil table.<br />

Fusible Disconnect<br />

<strong>Siemens</strong> Energy & Automation, Inc.<br />

Industrial <strong>Control</strong>s Catalog<br />

<strong>Pump</strong> <strong>Control</strong> <strong>Panels</strong><br />

<strong>Pump</strong> Panel with Ambient Compensated Bimetal Overload<br />

Discount Code: NEMA <strong>Control</strong><br />

Coil Table<br />

Selection<br />

60Hz Voltage Letter<br />

24 Separate <strong>Control</strong> J<br />

120 Separate <strong>Control</strong> F<br />

110–120/220–240 A <br />

200–208 D<br />

220–240 G<br />

220–240/440–480 C <br />

277 L<br />

440–480 H<br />

550–600 E<br />

200V 230V 460V 575V NEMA Size Half Size Fuse Clip Amps Catalog Number List Price $<br />

— — 10 10 1 — 30 87DAE6FC 982.<br />

— — 10 10 1 — 60 87DAE60C 998.<br />

— — 15 15 — 1 3/4 30 87EAF6FC 1159.<br />

— — 15 15 — 1 3/4 60 87EAF60C 1175.<br />

— — 25 25 2 — 60 87FAJ6FC 1337.<br />

— — 25 25 2 — 100 87FAJ60C 1421.<br />

— — 30 30 — 2 1/2 60 87GAK6FC 1922.<br />

— — 30 30 — 2 1/2 100 87GAK60C 2007.<br />

— — 50 50 3 — 100 87HAN6FC 2176.<br />

— — 50 50 3 — 200 87HAN60C 2338.<br />

— — 75 75 — 3 1/2 200 87IAP6FC 3725.<br />

— — 100 100 4 — 200 87JAR6FC 4033.<br />

7 1/2 7 1/2 — — 1 — 30 87DAE6LC 967.<br />

7 1/2 7 1/2 — — 1 — 60 87DAE6PC 982.<br />

10 10 — — — 1 3/4 60 87EAG6LC 1159.<br />

10 15 — — 2 — 60 87FAJ6LC 1314.<br />

10 15 — — 2 — 100 87FAJ6PC 1406.<br />

15 20 — — — 2 1/2 100 87GAL6LC 1961.<br />

25 30 — — 3 — 100 87HAN6LC 2130.<br />

25 30 — — 3 — 200 87HAN6PC 2307.<br />

30 40 — — — 3 1/2 200 87IAP6LC 3694.<br />

40 50 — — 4 — 200 87JAR6LC 4002.<br />

Circuit Breaker<br />

200V 230V 460V 575V NEMA Size Half Size Motor Circuit Catalog Number List Price $<br />

Interrupter<br />

ETI<br />

1/2 1/2 1 1 1 — 3 87DAA6MC 1244.<br />

1 1 3 3 1 — 10 87DAB6MC 1244.<br />

3 3 7 1/2 7 1/2 1 — 25 87DAD6MC 1244.<br />

7 1/2 7 1/2 10 10 1 — 30 87DAE6MC 1244.<br />

7 1/2 7 1/2 15 15 — 1 3/4 30 87EAF6MC 1398.<br />

10 10 — — — 1 3/4 50 87EAG6MC 1538.<br />

— — 15 20 2 — 40 87FAH6MC 1552.<br />

10 15 25 25 2 — 50 87FAJ6MC 1552.<br />

— — 30 30 — 2 1/2 50 87GAK6MC 2038.<br />

15 20 — — — 2 1/2 100 87GAL6MC 2038.<br />

25 30 50 50 3 — 100 87HAN6MC 2207.<br />

30 40 75 75 — 3 1/2 125 87IAP6MC 4403.<br />

40 50 100 100 4 — 150 87JAR6MC 4711.<br />

Not available on Size 5 or larger.<br />

8/59


Vacuum Starter <strong>Pump</strong> <strong>Panels</strong><br />

With Solid-State Overload Relay<br />

Selection<br />

Ordering Information<br />

Technical Data see www.sea.siemens.com/controls.<br />

Field Modification Kits see page 8/79.<br />

Factory Modifications see page 8/93.<br />

Dimensions see page 8/110.<br />

Wiring Diagrams see page 8/137.<br />

Replacement Parts see pages 8/152.<br />

Sizes 1-4 will be supplied standard with a 240/480 volt coil. To<br />

change the coil voltage, change the 8th character in the catalog<br />

number to the letter shown in the coil table.<br />

Sizes 5&6 will be supplied standard with a 480 volt coil. To change<br />

the coil voltage, change the 8th character in the catalog number to<br />

the letter shown in the coil table.<br />

Fusible Disconnect<br />

8/62<br />

Discount Code: NEMA <strong>Control</strong><br />

Coil Table<br />

60Hz Voltage ***<br />

024 Separate <strong>Control</strong> 024<br />

120 120<br />

208 208<br />

277 277<br />

480 480<br />

600 600<br />

Max Hp<br />

460 Volts 575 Volts NEMA Size Overload Range Fuse Clip Amps Catalog Number List Price $<br />

100 100 4 55-250A 200A/600V 87JCM4F 7059.<br />

200 200 5 55-250A 400A/600V 87KCU4F* 11363.<br />

Circuit Breaker<br />

Max Hp<br />

460 Volts 575 Volts NEMA Size Overload Range Circuit Breaker Rating Catalog Number List Price $<br />

100 100 4 55-250A 250A 87JCM4M* 7810.<br />

200 200 5 55-250A 250A 87KCT4M* 13416.<br />

250 300 6 200-540A 400A 87MCW4M* 29928.<br />

400 400 6 200-540A 600A 87MCX4M* 29928.<br />

<strong>Siemens</strong> Energy & Automation, Inc.<br />

Industrial <strong>Control</strong>s Catalog