List of <strong>Instruction</strong>s List of <strong>Instruction</strong>s<br />
<strong>Instruction</strong>s Directly Affecting the RLO<br />
The following instructions have a direct effect on the RLO.<br />
<strong>Instruction</strong><br />
Address<br />
Identifier<br />
Description<br />
Length<br />
in<br />
Words<br />
Typical Execution Time in s<br />
312*/313 314/314* 315/315/316 318-2<br />
CLR Set RLO to ”0” 1 0.7 0.2 0.3 0.1<br />
Status word <strong>for</strong>: CLR BR CC 1 CC 0 OV OS OR STA RLO FC<br />
<strong>Instruction</strong> depends on: – – – – – – – – –<br />
<strong>Instruction</strong> affects: – – – – – 0 0 0 0<br />
SET Set RLO to ”1” 1 0.7 0.2 0.3 0.1<br />
Status word <strong>for</strong>: SET BR CC 1 CC 0 OV OS OR STA RLO FC<br />
<strong>Instruction</strong> depends on: – – – – – – – – –<br />
<strong>Instruction</strong> affects: – – – – – 0 1 1 0<br />
NOT Negate RLO 1 0.7 0.2 0.3 0.1<br />
Status word <strong>for</strong>: NOT BR CC 1 CC 0 OV OS OR STA RLO FC<br />
<strong>Instruction</strong> depends on: – – – – – Yes – Yes –<br />
<strong>Instruction</strong> affects: – – – – – – 1 Yes –<br />
SAVE Save RLO to the BR bit 1 0.7 0.2 0.3 0.1<br />
Status word <strong>for</strong>: SAVE BR CC 1 CC 0 OV OS OR STA RLO FC<br />
<strong>Instruction</strong> depends on: – – – – – – – Yes –<br />
<strong>Instruction</strong> affects: Yes – – – – – – – –<br />
70<br />
<strong>S7</strong>-<strong>300</strong> <strong>Instruction</strong> List <strong>S7</strong>-<strong>300</strong> <strong>Instruction</strong> List<br />
EWA 4NEB 710 6087-02 EWA 4NEB 710 6087-02<br />
71