SPECIFICATIONS<br />
PUMPSAVER 111 / 233<br />
Order No. ① HP Volts Phase Hertz Reset Time Delay Enclosure Comparable to<br />
1113RL 1 ⁄3 to 1 115 1 50 – 60 2-225 minutes NEMA 3R AW150<br />
233153RL 1 ⁄3 to 1½ 230 1 50 – 60 2-225 minutes NEMA 3R AW150<br />
2333RL 1 ⁄3 to 3 230 1 50 – 60 2-225 minutes NEMA 3R AW500<br />
① Individual <strong><strong>Pump</strong>Saver</strong>s without a NEMA 3R enclosure available upon request.<br />
<strong><strong>Pump</strong>Saver</strong> is a registered trademark of SymCom, Inc.<br />
CentriPro is a brand of ITT Water Technology, Inc. –<br />
a subsidiary of ITT Industries, Inc.<br />
CentriPro and the ITT Engineered Blocks Symbol are<br />
registered trademarks and tradenames of ITT Industries.<br />
© 2005 ITT Water Technology, Inc.<br />
Effective April, 2005<br />
BCPSAVER<br />
PUMPSAVER 235<br />
SPECIFICATIONS<br />
Order No. ①② HP Volts Phase Hertz Reset Time Delay Enclosure Comparable to<br />
2353RL50 5 to 7.5 230 1 50 – 60 2-225 minutes NEMA 3R AW500<br />
2353RL75<br />
2353RL100<br />
10<br />
15<br />
230<br />
230<br />
1<br />
1<br />
50 – 60<br />
50 – 60<br />
2-225 minutes<br />
2-225 minutes<br />
NEMA 3R<br />
NEMA 3R<br />
AW201A1015<br />
① Includes appropriate current transformer<br />
② Individual 235 <strong><strong>Pump</strong>Saver</strong>s without enclosures, and individual current<br />
transformers available upon request.<br />
ELECTRICAL<br />
PUMP PROTECTION<br />
<strong><strong>Pump</strong>Saver</strong> by SymCom<br />
APPLICATIONS – SINGLE PHASE ONLY<br />
• All submersible pumps, regardless of motor<br />
manufacturer<br />
• Centrifugal pumps<br />
• Circulating pumps<br />
• Cooling pumps<br />
• Environmental pumps<br />
• Residential water wells<br />
• Commercial water wells<br />
• Irrigation wells<br />
• Golf course systems<br />
Protects From:<br />
• Dry well (run dry condition)<br />
• Flow restrictions (dead head)<br />
• Over current (jammed impeller)<br />
• Over voltage<br />
• Under voltage<br />
• Rapid cycling<br />
FEATURES<br />
• Can be calibrated to specific pump / motor<br />
combinations and various conditions<br />
• Will work with destaged pump models ending in 05R<br />
• Infrared LED communication with the INFORMER<br />
makes diagnostics simple<br />
• “Run Light” indicates the unit is functioning<br />
• “Run Light” and “Cal. Light” used as diagnostic<br />
indicators<br />
• Restart delay can be set up to 225 minutes or placed<br />
in manual reset mode<br />
• Micro-controller provides better accuracy and higher<br />
reliability than analog designs<br />
• 5 year warranty<br />
CentriPro<br />
ITT Industries
ELECTRICAL<br />
PUMP PROTECTION<br />
<strong><strong>Pump</strong>Saver</strong> by SymCom<br />
PUMPSAVER 111 INSIDER AND 231 INSIDER<br />
SPECIFICATIONS<br />
Order No. HP Volts Phase Hertz Reset Time Delay Comparable to<br />
111Insider<br />
231Insider<br />
1 ⁄3 to 1<br />
1 ⁄3 to 1<br />
115<br />
230<br />
1<br />
1<br />
60<br />
60<br />
2-225 Minutes<br />
2-225 Minutes<br />
AWQDP<br />
APPLICATION<br />
FEATURES<br />
• <strong>Submersible</strong> pump with • Fits inside a 3 wire quick<br />
a quick disconnect style disconnect style control box<br />
control box<br />
• Can be calibrated to specific<br />
Protects From:<br />
• Dry well (run dry condition)<br />
• Flow restrictions<br />
(dead head)<br />
• Over current<br />
(jammed impeller)<br />
• Over voltage<br />
• Under voltage<br />
pump / motor combinations<br />
and various conditions<br />
• Will work with destaged<br />
pump models ending in 05R<br />
• Infrared LED communication<br />
with the INFORMER makes<br />
diagnostics simple<br />
• Quick and easy installation<br />
– less than 30 seconds<br />
• “Run Light” indicates the<br />
unit is functioning<br />
• “Run Light” and “Cal. Light”<br />
used as diagnostic indicators<br />
• Restart delay can be set up<br />
to 225 minutes or placed in<br />
manual reset mode<br />
• 5 year warranty<br />
FEATURES<br />
• The Informer is a handheld diagnstic tool designed for use with<br />
single-phase <strong><strong>Pump</strong>Saver</strong> models.<br />
• The Informer uses an infrared receiver to access data sent from<br />
the <strong><strong>Pump</strong>Saver</strong>, which can be helpful for troubleshooting the<br />
system.<br />
The Informer displays parameters including:<br />
• Real-time voltage, current and power<br />
• Dry-well and overload trip points<br />
• Calibration voltage<br />
• Last fault condition<br />
• Voltage, current and power at last fault condition<br />
• Highest/lowest voltage and current since last calibration<br />
INFORMER<br />
SPECIFICATIONS<br />
Order No. Description<br />
INFORMER<br />
Hand Held<br />
Diagnostic Tool<br />
PRINTED IN U.S.A. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.<br />
CentriPro<br />
ITT Industries
INSIDER MOUNTED IN<br />
SUBMERSIBLE CONTROL BOX<br />
ORANGE<br />
SOLID-STATE<br />
SWITCH<br />
BLK<br />
RED<br />
B(MAIN) Y(COMM)<br />
To install in control box<br />
YEL<br />
CAPACITOR<br />
ELECTRICAL<br />
PUMP PROTECTION<br />
<strong><strong>Pump</strong>Saver</strong> by SymCom<br />
111/231<br />
INSIDER<br />
BLUE<br />
R(START) L2 L1<br />
• Remove blue wire from terminal strip and solid<br />
state switch (blue relay) and set aside.<br />
• Remove yellow jumper wire from terminal L2.<br />
• Install Insider by aligning tabs with upper L2 & L1<br />
tabs and pushing onto tabs.<br />
• Connect yellow wire onto L2 terminal on Insider.<br />
• Connect blue wire attached to Insider to solid state<br />
switch (blue relay).<br />
FUSED DISCONNECT<br />
OR CIRCUIT BREAKER<br />
GND<br />
PUMPSAVER 111 / 233<br />
TYPICAL WIRING DIAGRAM<br />
GND L1 L2<br />
L2<br />
L1<br />
PRESSURE<br />
SWITCH<br />
OR OTHER<br />
CONTROL<br />
PRESSURE SWITCH MAY BE INSTALLED<br />
AHEAD OF THE PUMPSAVER WHEN<br />
RAPID CYCLE PROTECTION IS<br />
NOT REQUIRED<br />
L1<br />
L2<br />
GND<br />
L1<br />
IN<br />
CentriPro<br />
PUMPSAVER<br />
111 / 233<br />
L1<br />
OUT<br />
L1<br />
L2 L2<br />
IN OUT<br />
PRESSURE SWITCH<br />
OR OTHER CONTROL<br />
L1<br />
L2<br />
L2<br />
GND<br />
GND<br />
TO MOTOR OR CONTROL BOX<br />
ITT Industries
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.<br />
ELECTRICAL<br />
PUMP PROTECTION<br />
<strong><strong>Pump</strong>Saver</strong> by SymCom<br />
PUMPSAVER 235 TYPICAL WIRING DIAGRAM WITH DELUXE CONTROL BOX<br />
GND L2 L1<br />
FUSED DISCONNECT<br />
OR CIRCUIT BREAKER<br />
L1<br />
L2<br />
PRESSURE SWITCH<br />
OR OTHER CONTROL<br />
L1 CT1 CT2 L2 IN L2 OUT<br />
CT<br />
SW L1 L2 YEL BLK RED<br />
DELUXE CONTROL BOX<br />
PUMP<br />
PUMP<br />
MOTOR<br />
CentriPro<br />
ITT Industries