<strong>CIRCUIT</strong> <strong>BREAKERS</strong> (<strong>ACB</strong>/<strong>MCCB</strong>)<br />

AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

382<br />

MOULDED CASE <strong>CIRCUIT</strong> <strong>BREAKERS</strong>, MC<br />

392<br />

SWITCH DISCONNECTORS MC-PN / MC-N<br />

397<br />

MC ACCESSORIES<br />

398<br />

SELECTIVITY TABLE<br />

410<br />

381<br />

381


382<br />

mo1.eps<br />

mo2.eps<br />

mo3.eps<br />

AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

W AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES PGR 4970<br />

W SHORT-<strong>CIRCUIT</strong> CAPACITY<br />

W STRAIGHTFORWARD RETROFITTING OF ADD-ON PARTS<br />

Retrofitting of add-on is particulary convenient, since it is done from<br />

the front. With this flexibility, changes in requirement of the installation<br />

are easy to cater for.<br />

W CURRENT RATING 630 A - 6300 A<br />

The new MO Air Circuit Breakers fully cover with three frame size a<br />

range from 630 - 6300 A.<br />

The nominal current can be adapted step by step to the requirement<br />

of the plant. The lowest current of the rating plug is 250 A. and all<br />

this with a seting range from 0,4 to 1 x In .<br />

W UNIFORM DIMENSIONS<br />

The MO has a uniform component height and depth over it´s whole<br />

current spectrum. Only the component width varies with the number<br />

of poles and the frame size. Fixed and withdrawable versions have<br />

the same width.<br />

WTERMINATIONS<br />

MO Air Circuit Breakers up to 5000 a come with horizontal connections,<br />

and MO 6300 A with vertikal connections, as standard. The following<br />

termination options are available: vertical connection, front<br />

connections and flanged.<br />

MO1 MO2 MO3<br />

I CU = I CS at 440 V 50, 65 kA 55, 80, 100, 150 kA 100, 150 kA<br />

Current Range, in A 250 - 1600 250 - 3200 1250 - 6300<br />

Number of Poles 3/4 3/4 3/4<br />

Rated Voltage, in V 690 690 690<br />

Service life, max., in endurance CO cycles 20000 15000 10000<br />

Degree of protection with/without cover IP 55/IP 20 IP 55/IP 20 IP 55/IP 20<br />

Dimensions 3/4-pole in mm Width 320/410 460/590 705/915<br />

Height 434 434 434<br />

Depht 291 291 291


AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

W SYSTEM OVERVIEW OF MO AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong><br />

pfeilskizze 2.eps<br />

1. MO Air Circuit Breakers, from 630A to 6300A<br />

2. External expansion modules<br />

3. Communication module for PROFIBUS<br />

4. Positioning indicator contact;<br />

module for withdrawable units<br />

5. Main connection elements:<br />

front, flanged, horizontal or vertical connection<br />

6. Withdrawable unit<br />

7. Control circuit plug<br />

8. Auxiliary contact<br />

9. Motor operator<br />

10.Operating cycle counter<br />

11.Electronic releases (control units)<br />

12.Parametric device<br />

13.Earth-fault protection module<br />

14.4-line LCD display<br />

15.Door sealing frame<br />

16.Rated current module (rating plug)<br />

17.Emergency Stop mushroom push button<br />

18.Closing release, voltage release<br />

383


384<br />

mo_over.eps<br />

AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

W SELECTIVITY MO / MC


AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

W OVERVIEW – OVERCURRENT RELEASE<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

c<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_tab1-2.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

385


386<br />

AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

W FRAME SIZE I, FIXED-MOUNTED VERSION, 3-POLE AND 4-POLE<br />

<br />

<br />

mo_dim1.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_leg1_4.eps<br />

<br />

<br />

<br />

mo_dim3.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_dim4.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_dim2.eps


AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

W FRAME SIZE I, WITHDRAWABLE VERSION, 3-POLE AND 4-POLE<br />

<br />

mo_dim5.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_leg5_8.eps<br />

<br />

<br />

<br />

mo_dim7.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_dim8.eps<br />

mo_dim6.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

387


388<br />

AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

W FRAME SIZE II, FIXED-MOUNTED VERSION, 3-POLE AND 4-POLE<br />

<br />

<br />

<br />

mo_dim9.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_leg9_12.eps<br />

mo_dim11.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_dim10.eps<br />

<br />

<br />

<br />

mo_dim12.eps


AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

W FRAME SIZE II, WITHDRAWABLE VERSION, 3-POLE AND 4-POLE<br />

<br />

<br />

<br />

mo_dim13.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_leg13_16.eps<br />

mo_dim15.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_dim14.eps<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

mo_dim16.eps<br />

<br />

<br />

<br />

<br />

389


390<br />

AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

W <strong>ACB</strong> MO SERIES, SIZE I AND II<br />

W A SEAMLESS RANGE FROM 0,16 A - 6300 A<br />

BE 5/6, MC and MO Circuit Breakers between them, cover a rated current range from 0,16 to 6300 A. They come in<br />

four different classes of switching capacity up to 150 kA, i.e. they provide the safe, as well as the economical solution<br />

in every case, from standard applications to the most sophisticated performance expectations.<br />

W COMPACT STYLE<br />

Their compact size enables the existing mounting space to be optimally utilized, saving precious equipment fitting capacity<br />

in the panel. The MO, up to a rated current of 1600 A for example, can be fitted into a 400 mm wide panel section.<br />

Up to a rated current of 6300 A, a section width of 800 mm suffices.<br />

W SIZE 1, 630 A - 1600 A, 50 kA AND 65 kA WITH<br />

REAR HORIZONTAL CONNECTION<br />

RATED CURRENT ICU POLES TYPE ORDER NO.<br />

800 A 50 kA 3 MO1B-800 MO108232—<br />

1000 A 50 kA 3 MO1B-1000 MO110232—<br />

1250 A 50 kA 3 MO1B-1250 MO112232—<br />

1600 A 50 kA 3 MO1B-1600 MO116232—<br />

800 65 kA 3 MO1N-800 MO108332—<br />

1000 A 65 kA 3 MO1N-1000 MO110332—<br />

1250 A 65 kA 3 MO1N-1250 MO112332—<br />

1600 A 65 kA 3 MO1N-1600 MO116332—<br />

800 A 50 kA 4 MO1B-4-800 MO108242—<br />

1000 A 50 kA 4 MO1B-4-1000 MO110242—<br />

1250 A 50 kA 4 MO1B-4-1250 MO112242—<br />

1600 A 50 kA 4 MO1B-4-1600 MO116242—<br />

800 A 65 kA 4 MO1N-4-800 MO108342—<br />

1000 A 65 kA 4 MO1N-4-1000 MO110342—<br />

1250 A 65 kA 4 MO1N-4-1250 MO112342—<br />

1600 A 65 kA 4 MO1N-4-1600 MO116342—<br />

W SIZE 2, 800 A - 3200 A, 55 kA AND 80 kA WITH<br />

REAR HORIZONTAL CONNECTION<br />

W For withdrawable version replace the last digit of the order no. by a “6”<br />

PGR 4970<br />

PGR 4970<br />

RATED CURRENT ICU POLES TYPE ORDER NO.<br />

2000 A 55 kA 3 MO2B-2000 MO220232—<br />

2500 A 55 kA 3 MO2B-2500 MO225232—<br />

3200 A 55 kA 3 MO2B-3200 MO232232—<br />

800 A 80 kA 3 MO2N-800 MO208332—<br />

1000 A 80 kA 3 MO2N-1000 MO210332—<br />

1250 A 80 kA 3 MO2N-1250 MO212332—<br />

1600 A 80 kA 3 MO2N-1600 MO216332—<br />

2000 A 80 kA 3 MO2N-2000 MO220332—<br />

2500 A 80 kA 3 MO2N-2500 MO225332—<br />

3200 A 80 kA 3 MO2N-3200 MO232332—


AIR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> MO SERIES UP TO 6300 A<br />

RATED CURRENT I CU POLES TYPE ORDER NO.<br />

2000 A 55 kA 4 MO2B-4-2000 MO220242—<br />

2500 A 55 kA 4 MO2B-4-2500 MO225242—<br />

3200 A 55 kA 4 MO2B-4-3200 MO232242—<br />

800 A 80 kA 4 MO2N-4-800 MO208342—<br />

1000 A 80 kA 4 MO2N-4-1000 MO210342—<br />

1250 A 80 kA 4 MO2N-4-1250 MO212342—<br />

1600 A 80 kA 4 MO2N-4-1600 MO216342—<br />

2000 A 80 kA 4 MO2N-4-2000 MO220342—<br />

2500 A 80 kA 4 MO2N-4-2500 MO225342—<br />

3200 A 80 kA 4 MO2N-4-3200 MO232242—<br />

W AUXILLIARY BUILT IN<br />

DESCRIPTION TYPE ORDER NO.<br />

Overcurrent relais LI ETU15 MO890150—<br />

Overcurrent relais LSI ETU25 MO890250—<br />

Overcurrent relais LSNIG ETU27 MO890270—<br />

Overcurrent relais universal ETU45 MO890450—<br />

Overcurrent relais digital ETU76 MO890760—<br />

Motor 208 - 240 V AC, incl. closing coil MO894000—<br />

Voltage release 230 V AC MO890G00—<br />

Voltage release 110 V AC MO890F00—<br />

Voltage release 24 V DC MO890B00—<br />

Undervoltage release 230 V AC MO8900N0—<br />

Undervoltage release 110 V AC O8900M0—<br />

Undervoltage release 24 V DC MO8900J0—<br />

Trip signaling switch MO800K07—<br />

mechanical latching fixed version MO80S550—<br />

mechanical latching withdrawable version MO80R550—<br />

W AUXILLIARY TO ORDER SEPARAT<br />

DESCRIPTION ORDER NO.<br />

Motor 208 - 240 V AC, excl. closing coil (use Voltage release) MO90AF04—<br />

Voltage release 230 V AC MO90AD06—<br />

Voltage release 110 V AC MO90AD05—<br />

Voltage release 24 V DC MO90AD01—<br />

Undervoltage release 230 V AC MO90AE06—<br />

Undervoltage release 110 V AC MO90AE05—<br />

Undervoltage release 24 V DC MO90AE01—<br />

Trip signaling switch MO90AH04—<br />

mechanical latching fixed version MO90S550—<br />

mechanical latching withdrawable version MO90R550—<br />

Door sealing frame IP 40 MO90AP01—<br />

receptacle MO90AB01—<br />

auxilliary connector MO90AB03—<br />

391


392<br />

MOULDED CASE <strong>CIRCUIT</strong> <strong>BREAKERS</strong>, MC<br />

W MOULDED CASE <strong>CIRCUIT</strong> BREAKER, MC<br />

mc_titel.eps<br />

w TECHNICAL DATA<br />

• Protects systems, cables, motors & generators<br />

• Rated uninterrupted current up to 1600A<br />

• 3 and 4-pole design<br />

• Switching capacity 25, 50, 100, 150 kA<br />

• Electrical and thermo-magnetic releases<br />

• Adjustable releases for overload and short-circuit<br />

• Adjustable time selectivity<br />

• Earth fault protection<br />

PGR 4960<br />

w NOTE:<br />

With main switch characteristicsin accordance with IEC/EN 60204 and isolating characteristics in accordance with<br />

IEC/EN 60947, VDE 0660.<br />

For 4-pole version and additional technical details, refer to the Special Catalogue K-LEISTMC-3.<br />

Operating instructions and additional measured diagrams are available on our homepage: www.schrack.com


W SYSTEM AND CABLE PROTECTION<br />

W 3-POLE, THERMO-MAGNETIC RELEASE<br />

mc2-a160.eps mc110231.eps<br />

MOULDED CASE <strong>CIRCUIT</strong> <strong>BREAKERS</strong>, MC<br />

w TECHNICAL DATA<br />

• Adjustable overload release Ir:<br />

0.8 – 1 x In (ex-factory 0.8 x In)<br />

• Adjustable short-circuit release Ir:<br />

6 – 10 x In (ex-factory 6 x In) MC.-A40: 8 - 10 x In<br />

• Lift terminals as standard for MC1, screw terminals as accessories<br />

• Screw terminals as standard for MC2, lift terminals as accessories<br />

• Switching capacity 25 / 50 / 100 kA at 415 V 50/60 Hz<br />

w CERTIFICATIONS<br />

IEC/EN 60947-2<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

PGR 4960<br />

RATED CURRENT/SWITCHING CAPACITY DIM. (WxHxD) PU TYPE WEIGHT ORDER NO.<br />

SIZE 1<br />

20 A/25 kA 90x145x84,5 1 MC1B-A20 1,046 MC120131—<br />

25 A/25 kA 90x145x84,5 1 MC1B-A25 1,046 MC125131—<br />

32 A/25 kA 90x145x84,5 1 MC1B-A32 1,046 MC132131—<br />

40 A/25 kA 90x145x84,5 1 MC1B-A40 1,046 MC140131—<br />

50 A/25 kA 90x145x84,5 1 MC1B-A50 1,046 MC150131—<br />

63 A/25 kA 90x145x84,5 1 MC1B-A63 1,046 MC163131—<br />

80 A/25 kA 90x145x84,5 1 MC1B-A80 1,046 MC180131—<br />

100 A/25 kA 90x145x84,5 1 MC1B-A100 1,046 MC110131—<br />

125 A/25 kA 90x145x84,5 1 MC1B-A125 1,046 MC112131—<br />

160 A/50 kA 90x145x84,5 1 MC1B-A160 1,046 MC116131—<br />

20 A/50 kA 90x145x84,5 1 MC1N-A20 1,046 MC120231—<br />

25 A/50 kA 90x145x84,5 1 MC1N-A25 1,046 MC125231—<br />

32 A/50 kA 90x145x84,5 1 MC1N-A32 1,046 MC132231—<br />

40 A/50 kA 90x145x84,5 1 MC1N-A40 1,046 MC140231—<br />

50 A/50 kA 90x145x84,5 1 MC1N-A50 1,046 MC150231—<br />

63 A/50 kA 90x145x84,5 1 MC1N-A63 1,046 MC163231—<br />

80 A/50 kA 90x145x84,5 1 MC1N-A80 1,046 MC180231—<br />

100 A/50 kA 90x145x84,5 1 MC1N-A100 1,046 MC110231—<br />

125 A/50 kA 90x145x84,5 1 MC1N-A125 1,046 MC112231—<br />

160 A/50 kA 90x145x84,5 1 MC1N-A160 1,046 MC116231—<br />

SIZE 2<br />

125 A/25 kA 105x184x149 1 MC2B-A125 2,345 MC212131—<br />

160 A/25 kA 105x184x149 1 MC2B-A160 2,345 MC216131—<br />

200 A/25 kA 105x184x149 1 MC2B-A200 2,345 MC220131—<br />

250 A/25 kA 105x184x149 1 MC2B-A250 2,345 MC225131—<br />

125 A/50 kA 105x184x149 1 MC2N-A125 2,345 MC212231—<br />

160 A/50 kA 105x184x149 1 MC2N-A160 2,345 MC216231—<br />

200 A/50 kA 105x184x149 1 MC2N-A200 2,345 MC220231—<br />

250 A/50 kA 105x184x149 1 MC2N-A250 2,345 MC225231—<br />

80 A/100 kA 105x184x149 1 MC2H-A80 2,345 MC280331—<br />

100 A/100 kA 105x184x149 1 MC2H-A100 2,345 MC210331—<br />

125 A/100 kA 105x184x149 1 MC2H-A125 2,345 MC212331—<br />

160 A/100 kA 105x184x149 1 MC2H-A160 2,345 MC216331—<br />

393


394<br />

W 3-POLE, ELECTRONIC RELEASES<br />

mc3-ae250.eps<br />

RATED CURRENT/SWITCHING CAPACITY DIM. (WxHxD) PU TYPE WEIGHT ORDER NO.<br />

SIZE 3<br />

250 A/50 kA 140x275x166 1 MC3N-AE250 6,34 MC325232—<br />

400 A/50 kA 140x275x166 1 MC3N-AE400 6,34 MC340232—<br />

630 A/50 kA 140x275x166 1 MC3N-AE630 6,34 MC363232—<br />

250 A/100 kA 140x275x166 1 MC3H-AE250 6,34 MC325332—<br />

400 A/100 kA 140x275x166 1 MC3H-AE400 6,34 MC340332—<br />

630 A/100 kA 140x275x166 1 MC3H-AE630 6,34 MC363332—<br />

SIZE 4<br />

MOULDED CASE <strong>CIRCUIT</strong> <strong>BREAKERS</strong>, MC<br />

w TECHNICAL DATA<br />

• RMS value and “thermal memory”<br />

• Adjustable overload release Ir: 0.5 – 1 x In (ex-factory 0.8 x In)<br />

• Adjustable short-circuit release Ir: 2 – 12 x In (ex-factory 6 x In)<br />

• for MC3...-AE250/400: 2 – 11 x In (ex-factory 6 x In)<br />

• for MC3....-AE630: 2 – 8 x In (ex-factory 6 x In)<br />

• Switching capacity 25 / 50 / 100 kA at 415 V 50/60 Hz<br />

• Screw terminals as standard, lift terminals as accessories for MC2/MC3<br />

w CERTIFICATIONS<br />

IEC/EN 60947-2<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

PGR 4960<br />

630 A/50 kA 210x401x207 1 MC4N-AE630 21 MC463232—<br />

800 A/50 kA 210x401x207 1 MC4N-AE800 21 MC480232—<br />

1000 A/50 kA 210x401x207 1 MC4N-AE1000 21 MC410232—<br />

1250 A/50 kA 210x401x207 1 MC4N-AE1250 21 MC412232—<br />

1600 A/50 kA 210x401x207 1 MC4N-AE1600 21 MC416232—<br />

630 A/100 kA 210x401x207 1 MC4H-AE630 21 MC463332—<br />

800 A/100 kA 210x401x207 1 MC4H-AE800 21 MC480332—<br />

1000 A/100 kA 210x401x207 1 MC4H-AE1000 21 MC410332—<br />

1250 A/100 kA 210x401x207 1 MC4H-AE1250 21 MC412332—<br />

1600 A/100 kA 210x401x207 1 MC4H-AE1600 21 MC416332—


w NOTE:<br />

MOULDED CASE <strong>CIRCUIT</strong> <strong>BREAKERS</strong>, MC<br />

W SYSTEM AND CABLE PROTECTION,<br />

SELECTIVE AND GENERATOR PROTECTION<br />

Operating instructions and measured diagrams are available on our homepage: www.schrack.com<br />

W 3-POLE, ELECTRONIC<br />

RELEASE DELAYED<br />

mc216233.eps mc480233.eps<br />

w CERTIFICATIONS<br />

PGR 4960<br />

w TECHNICAL DATA<br />

• RMS value and “thermal memory”<br />

• Adjustable overload release Ir: 0.5 – 1 x In (ex-factory 0.8 x In)<br />

• Adjustable time delay setting to overcome current peaks tr:<br />

2 – 20 s at 6 x Ir as well as infinity<br />

• Adjustable delayed short-circuit release Isd:<br />

2 – 10 x Ir (ex-factory 6 x Ir)<br />

• MC3...-4-VE630: 2 – 7 x Ir (ex-factory 6 x Ir)<br />

• Adjustable delay time tsd: Steps:<br />

0, 20, 60, 100, 200, 300, 500, 750,1000 ms (ex-factory 0)<br />

• Adjustable non-delayed short-circuit release Ii:<br />

2 – 12 x In (ex-factory 12 x In)<br />

• MC2 fixed 12 xIn<br />

• MC3...-VE250/400: 2 – 11 x In (ex-factory 6 x In)<br />

• MC3...-VE630: 2 – 8x In (ex-factory 6 x In)<br />

• Switchable i2t-constant function (ex-factory: OFF) MC3/MC4<br />

• Screw terminals are standard,<br />

lift terminals as accessories for MC2/MC3<br />

RATED CURRENT/SWITCHING CAPACITY DIM. (WxHxD) PU TYPE WEIGHT ORDER NO.<br />

SIZE 3<br />

100 A/50 kA 105x184x149 1 MC2N-VE100 2,345 MC210233—<br />

160 A/50 kA 105x184x149 1 MC2N-VE160 2,345 MC216233—<br />

250 A/50 kA 105x184x149 1 MC2N-VE250 2,345 MC225233—<br />

100 A/100 kA 105x184x149 1 MC2H-VE100 2,345 MC210333—<br />

160 A/100 kA 105x184x149 1 MC2H-VE160 2,345 MC216333—<br />

250 A/100 kA 105x184x149 1 MC2H-VE250 2,345 MC225333—<br />

SIZE 3<br />

250 A/50 kA 140x275x166 1 MC3N-VE250 6,34 MC325233—<br />

400 A/50 kA 140x275x166 1 MC3N-VE400 6,34 MC340233—<br />

630 A/50 kA 140x275x166 1 MC3N-VE630 6,34 MC363233—<br />

250 A/100 kA 140x275x166 1 MC3H-VE250 6,34 MC325333—<br />

400 A/100 kA 140x275x166 1 MC3H-VE400 6,34 MC340333—<br />

630 A/100 kA 140x275x166 1 MC3H-VE630 6,34 MC363333—<br />

SIZE 4<br />

IEC/EN 60947-2<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

630 A/50 kA 210x401x207 1 MC4N-VE630 21 MC463233—<br />

800 A/50 kA 210x401x207 1 MC4N-VE800 21 MC480233—<br />

1000 A/50 kA 210x401x207 1 MC4N-VE1000 21 MC410233—<br />

1250 A/50 kA 210x401x207 1 MC4N-VE1250 21 MC412233—<br />

1600 A/50 kA 210x401x207 1 MC4N-VE1600 21 MC416233—<br />

630 A/100 kA 210x401x207 1 MC4H-VE630 21 MC463333—<br />

800 A/100 kA 210x401x207 1 MC4H-VE800 21 MC480333—<br />

1000 A/100 kA 210x401x207 1 MC4H-VE1000 21 MC410333—<br />

1250 A/100 kA 210x401x207 1 MC4H-VE1250 21 MC412333—<br />

1600 A/100 kA 210x401x207 1 MC4H-VE1600 21 MC416333—<br />

395


396<br />

MOULDED CASE <strong>CIRCUIT</strong> <strong>BREAKERS</strong>, MC<br />

W 4-POLE, THERMO-MAGNETIC RELEASE<br />

w TECHNICAL DATA<br />

• Adjustable overload release Ir: 0.8 – 1 x In (ex-factory 0.8 x In)<br />

• Adjustable short-circuit release Ir: 6 – 10 x In (ex-factory 6 x In); MC..-4-A40 8 - 10 x In<br />

• Lift terminals as standard for MC1, screw terminals as accessories<br />

• Screw terminals as standard for MC2, lift terminals as accessories<br />

• Switching capacity 25 / 50 / 100 kA at 415 V 50/60 Hz<br />

w CERTIFICATIONS<br />

IEC/EN 60947-2<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

W 4-POLE, ELECTRONIC RELEASES<br />

w TECHNICAL DATA<br />

• RMS value and “thermal memory”<br />

• Adjustable overload releases Ir: 0.5 – 1 x In (ex-factory 0.8 x In)<br />

• Adjustable short-circuit releases li: 2 – 12 x In (ex-factory 6 x In)<br />

• For MC3...-AE250/400: 2 – 11 x In (ex-factory 6 x In)<br />

• For MC3....-AE630: 2 – 8 x In (ex-factory 6 x In)<br />

• Switching capacity 25 / 50 / 100 kA at 415 V 50/60 Hz<br />

• Screw terminals as standard, lift terminals as accessories for MC2/MC3<br />

w CERTIFICATIONS<br />

IEC/EN 60947-2<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

W 4-POLE, ELECTRONIC DELAYED RELEASES<br />

w TECHNICAL DATA<br />

• RMS value and “thermal memory”<br />

• Adjustable overload release Ir: 0.5 – 1 x In (ex-factory 0.8 x In)<br />

• Adjustable time delay setting to overcome current peaks tr: 2 – 20 s at 6 x Ir as well as infinity (without overload<br />

release; ex-factory 10 s)<br />

• Adjustable delayed short-circuit release Isd: 2 – 10 x Ir (ex-factory 6 x Ir)<br />

• MC3...-4-VE630: 2 – 7 x Ir (ex-factory 6 x Ir)<br />

• Adjustable delay time tsd: Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000 ms (ex-factory 0)<br />

• Adjustable non-delayed short-circuit release Ii: 2 – 12 x In (ex-factory 12 x In)<br />

• MC2 fixed 12 xIn<br />

• MC3...-4-VE400: 2 – 11 x In (ex-factory 6 x In)<br />

• MC3...-4-VE630: 2 – 8x In (ex-factory 6 x In)<br />

• Switchable i2t-constant function (ex-factory: OFF) MC3/MC4<br />

• Screw terminals as standard, lift terminals as accessories for MC2/MC3<br />

w CERTIFICATIONS<br />

IEC/EN 60947-2<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4


W SWITCH DISCONNECTORS<br />

mc1-pn.eps<br />

W SWITCH DISCONNECTORS, 3-POLE<br />

RATED CURRENT/MAX. FUSE AGL DIM. (WxHxD) PU TYPE WEIGHT ORDER NO.<br />

63 A/125 A 90x145x84,5 1 MC1-PN-63 1,046 MC163034—<br />

100 A/125 A 90x145x84,5 1 MC1-PN-100 1,046 MC110034—<br />

125 A/125 A 90x145x84,5 1 MC1-PN-125 1,046 MC112034—<br />

160 A/250 A 105x84x149 1 MC2-PN-160 2,345 MC216034—<br />

200 A/250 A 105x84x149 1 MC2-PN-200 2,345 MC220034—<br />

250 A/250 A 105x84x149 1 MC2-PN-250 2,345 MC225034—<br />

400 A/630 A 140x275x166 1 MC3-PN-400 6,34 MC340034—<br />

630 A/630 A 140x275x166 1 MC3-PN-630 6,34 MC363034—<br />

with remote trip<br />

SWITCH DISCONNECTORS MC-PN / MC-N<br />

w TECHNICAL DATA<br />

• Rated uninterrupted current up to 1600A<br />

• Switch disconnectors MC1-PN, two switch positions 0/1, cannot be tripped remotely<br />

• Switch disconnector MC1-N, with trip setting, can be tripped remotely with U/A voltage<br />

release<br />

• 3 and 4-pole design<br />

• Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113<br />

• Isolating characteristics according to IEC/EN 60947-3 and VDE 0660 protection against<br />

accidental contact according to VDE 0160 part 100<br />

• U/A voltage releases and trip-indicating auxillary contacts can also be used with MC...-N<br />

switch disconnectors.<br />

• MC2/3/4-N... can be combined with the MC-XR... remote operator.<br />

• Lift terminals as standard for MC1, screw terminals as accessories<br />

• Screw terminals are standard for MC2/MC3/MC4,<br />

lift terminals are accessories for MC2/MC3<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

w NOTE:<br />

Operating instructions and measured diagrams are available on our homepage:<br />

www.schrack.com<br />

PGR 4960<br />

PGR 4960<br />

63 A/125 A 90x145x84,5 1 MC1-N-63 1,046 MC163035—<br />

100 A/125 A 90x145x84,5 1 MC1-N-100 1,046 MC110035—<br />

125 A/125 A 90x145x84,5 1 MC1-N-125 1,046 MC112035—<br />

160 A/250 A 105x84x149 1 MC2-N-160 2,345 MC216035—<br />

200 A/250 A 105x84x149 1 MC2-N-200 2,345 MC220035—<br />

250 A/250 A 105x84x149 1 MC2-N-250 2,345 MC225035—<br />

400 A/630 A 140x275x166 1 MC3-N-400 6,34 MC340035—<br />

630 A/630 A 140x275x166 1 MC3-N-630 6,34 MC363035—<br />

800 A/1600 A 210x401x207 1 MC4-N-800 21 MC480035—<br />

1000 A/1600 A 210x401x207 1 MC4-N-1000 21 MC410035—<br />

1250 A/1600 A 210x401x207 1 MC4-N-1250 21 MC412035—<br />

1600 A/1600 A 210x401x207 1 MC4-N-1600 21 MC416035—<br />

W SWITCH DISCONNECTORS, 4-POLE<br />

Product information and technical data is available in our Special Catalogue K-<strong>MCCB</strong>MCE4<br />

PGR 4960<br />

397


398<br />

MC ACCESSORIES<br />

W AUXILIARY CONTACTS<br />

mm216378.eps<br />

W STANDARD AUXILIARY CONTACT<br />

w TECHNICAL DATA<br />

Can be clipped onto the main switch:<br />

• MC1 - one standard auxiliary contact<br />

• MC2 - up to 2 standard auxiliary contacts M22-(C)K...<br />

• MC3,4 - up to 3 standard auxiliary contacts M22-(C)K...<br />

Any combination of auxiliary contacts is possible<br />

• Switching capacity: AC15,230 V 4 A<br />

DC13,24 V 3 A<br />

w RANGE OF APPLICATION<br />

Switches with the main contacts. Used for signalling and interlocking circuits.<br />

W TRIP-INDICATING AUXILIARY CONTACT<br />

w TECHNICAL DATA<br />

w TECHNICAL DATA<br />

Can be clipped onto the main switch:<br />

• MC1 - one trip-indicating auxiliary contact<br />

• MC2 - one trip-indicating auxiliary contact M22-(C)K...<br />

• MC3 - one trip-indicating auxiliary contact M22-(C)K...<br />

• MC4 - up to 2 trip-indicating auxiliary contacts M22-(C)K...<br />

Any combination of auxiliary contacts is possible<br />

• Breaking capacity: AC15, 230 V 4 A<br />

w MAXIMUM PERMISSIBLE<br />

Normal auxiliary contact<br />

1 NO oder 1 NC<br />

Trip-indicating contact<br />

1 NO oder 1 NC<br />

Early make<br />

auxiliary contact 2 NO<br />

DC13, 24 V 3 A<br />

w RANGE OF APPLICATION<br />

Indicates trip “+” through voltage release, overload- or short-circuit release<br />

MC 1 MC 2 MC 3 MC 4<br />

1 2 3 3<br />

1 1 1 2<br />

1 1 1 1<br />

PGR 4960<br />

PGR 4811<br />

PGR 4811<br />

DESCRIPTION TYPE WEIGHT ORDER NO.<br />

N/O contact front M22-K10 0,01 MM216376—<br />

N/C contact front M22-K01 0,01 MM216378—


W EARLY MAKE AUXILIARY CONTACTS<br />

w TECHNICAL DATA<br />

MC ACCESSORIES<br />

w TECHNICAL DATA<br />

• Cannot be used in conjunction with XR-MC remote release unit or undervoltage units or shunt trips<br />

w RANGE OF APPLICATION<br />

For interlocking and load-shredding circuits<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Early make auxiliary contact, 2 NO MC1 1 MC1-XHIVL MC199432—<br />

Early make auxiliary contact, 2 NO MC2/MC3 1 MC2/3-XHIV MC299430—<br />

Early make auxiliary contact, 2 NO MC4 1 MC4-XHIV MC496172—<br />

W UNDERVOLTAGE RELEASES<br />

mc199471.eps<br />

PGR 4962<br />

• W/o auxiliary contacts<br />

• Non-delayed disconnection of <strong>MCCB</strong>s or MC-N switch disconnectors when the control<br />

voltage drops below 35 % - 70% Us.<br />

• For use in Emergency Stop units in conjunction with Emergency Stop button<br />

• Built into switch<br />

w TIPS & TRICKS<br />

When the undervoltage release is in a de-energized state, accidental contact with the main<br />

contacts of the switch during attempts to switch on is safely prevented. Undervoltage<br />

releases can not be installed at the same time as the shunt trip.<br />

FOR SIZES VOLTAGE PU TYPE ORDER NO.<br />

MC1 incl. 3m cable 24 VAC 1 MC1-XUL24AC MC199462—<br />

MC2 / MC3 24 VAC 1 MC2/3-XU24AC MC299491—<br />

MC4 24 VAC 1 MC4-XU24AC MC496189—<br />

MC1 incl. 3m cable 24 VAC 1 MC1-XUL24DC MC199481—<br />

MC2 / MC3 24 VDC 1 MC2/3-XU24DC MC299509—<br />

MC1 incl. 3m cable 208-240 VAC 1 MC1XUL208-240AC MC199471—<br />

MC2 / MC3 208-240 VAC 1 MC2/3XU208-240A MC299499—<br />

MC4 208-240 VAC 1 MC4XU208-240AC MC496193—<br />

MC1 incl. 3m cable 380-440 VAC 1 MC1XUL380-440AC MC199473—<br />

MC2 / MC3 380-440 VAC 1 MC2/3XU380-440A MC299501—<br />

MC4 380-440 VAC 1 MC4-XU380-440AC MC496194—<br />

399


400<br />

MC ACCESSORIES<br />

W UNDERVOLTAGE RELEASES<br />

WITH TWO EARLY MAKE AUXILIARY CONTACTS<br />

w TECHNICAL DATA<br />

• With 2 early make auxiliary contacts<br />

• For early make of undervoltage release when using main switches and<br />

for interlocking and load-shredding circuits<br />

• Built into switch<br />

• Other voltages and variants available to order<br />

w TIPS & TRICKS<br />

When the undervoltage release is in a de-energized state, accidental contact with the main contacts of the switch<br />

during attempts to switch on is safely prevented. Early make of contacts also during switch-off. Cannot be used in conjunction<br />

with remote operators. Undervoltage release cannot be installed at the same time as the shunt trip.<br />

FOR SIZES VOLTAGE PU TYPE ORDER NO.<br />

MC1 incl. 3 m cable 208-240 VAC 1 MC1-XUHIV230V MC199565—<br />

MC1 incl. 3 m cable 380-440 VAC 1 MC1-XUHIV400VAC MC199567—<br />

MC2 / MC3 208-240 VAC 1 MC2/3-XUHIV230V MC299591—<br />

MC2 / MC3 380-440 VAC 1 MC2/3-XUHIV400V MC299594—<br />

MC4 208-240 VAC 1 MC4-XUHIV230VAC MC496221—<br />

MC4 380-440 VAC 1 MC4-XUHIV400VAC MC496222—<br />

W SHUNT TRIPS<br />

mc199744.eps<br />

w RANGE OF APPLICATION<br />

• W/o auxiliary contacts<br />

• Switches are tripped by voltage pulse or switch-on of uninterrupted voltage<br />

w NOTE<br />

When the undervoltage release is in a de-energized state, accidental contact with the main<br />

contacts of the switch during attempts to switch on is safely prevented. Shunt trip cannot<br />

be installed at the same time as the undervoltage release.<br />

FOR SIZES VOLTAGE PU TYPE ORDER NO.<br />

MC1 incl. 3 m cable 24 V AC/DC 1 MC1-XAL24AC/DC MC199736—<br />

MC1 incl. 3 m cable 208 - 250 V AC/DC 1 MC1-XAL230AC/DC MC199744—<br />

MC2 / MC3 24 V AC/DC 1 MC2/3-XAL24V MC299754—<br />

MC2 / MC3 208 - 250 V AC/DC 1 MC2/3-XAL230V MC299763—<br />

MC4 24 V AC/DC 1 MC4-XAL24AC/DC MC496447—<br />

MC4 208 - 250 V AC/DC 1 MC4-XAL230AC/DC MC496451—


W ROTARY HANDLES<br />

mc2-xdv.eps<br />

w TECHNICAL DATA<br />

mc3-xdv.eps<br />

W ROTARY HANDLE DIRECT ON SWITCH<br />

MC ACCESSORIES<br />

• Complete with rotary drive<br />

• Sizes 1 and 2 can also be combined with insulating surround<br />

• Rotary handle can be rotated up to 90° for switches in lying position<br />

• Available in the following variants:<br />

Main switch, black/grey:<br />

• Standard MC.-XD<br />

• MC.-XDV switch is lockable in Off position (up to 3 padlocks)<br />

• With door interlock, lockable in Off or On position. MC.-XDTV (up to 3 padlocks)<br />

In the ON position, can be defeated using a 1mm pin, door cannot be defeated in the locked ON and OFF positions.<br />

In the Off position when the door is closed, can be switched on with red/yellow emergency stop switch:<br />

• MC.-XDVR switch is lockable in Off position (up to 3 padlocks)<br />

• With door interlock, lockable in Off or On position. MC.-XDTVR<br />

In the ON position, can be defeated using a 1mm pin, door cannot be defeated in the locked ON and OFF positions.<br />

Can be switched on when door is closed<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

PGR 4960<br />

PGR 4960<br />

FOR SIZES VERSIONS PU TYPE ORDER NO.<br />

MC1 Standard, black/grey 1 MC1-XD MC190116—<br />

MC2 Standard, black/grey 1 MC2-XD MC290121—<br />

MC3 Standard, black/grey 1 MC3-XD MC390123—<br />

MC4 Standard, black/grey 1 MC4-XD MC496606—<br />

MC1 Lockable, black/grey 1 MC1-XDV MC190125—<br />

MC2 Lockable, black/grey 1 MC2-XDV MC290127—<br />

MC3 Lockable, black/grey 1 MC3-XDV MC390129—<br />

MC4 Lockable, black/grey 1 MC4-XDV MC496608—<br />

MC1 With door interlock, black/grey 1 MC1-XDTV MC190131—<br />

MC2 With door interlock, black/grey 1 MC2-XDTV MC290133—<br />

MC1 Red/yellow emergency stop lockable 1 MC1-XDVR MC190135—<br />

MC2 Red/yellow emergency stop lockable 1 MC2-XDVR MC290137—<br />

MC3 Red/yellow emergency stop lockable 1 MC3-XDVR MC390140—<br />

MC4 Red/yellow emergency stop lockable 1 MC4-XDVR MC496610—<br />

MC1 Emergency stop with door interlock 1 MC1-XDTVR MC190142—<br />

MC2 Emergency stop with door interlock 1 MC2-XDTVR MC290144—<br />

401


402<br />

MC ACCESSORIES<br />

W DOOR INTERLOCKING ROTARY HANDLE<br />

w TECHNICAL DATA<br />

PGR 4960<br />

• Complete with rotary drive and interlocking device<br />

• Degree of protection IP66<br />

• MC.-XTD<br />

Standard, non lockable, black/grey<br />

• MC.-XTVD, MC.-XTVDV, MC.-XTVDVR<br />

• Cannot be defeated in locked OFF and ON positions.<br />

• Can be modified such that it can be defeated from the outside using a screwdriver when in the unlocked ON position<br />

• Door can only be opened in OFF position<br />

MC.-XTVD: Can be locked in Off posiiton on handle, can also be modified in On position, black/grey<br />

MC.-XTVDV : Can also be locked on switch in Off position, black/grey<br />

MC.-XTVDVR: Can also be lockable on switch in Off position, emergency stop red/yellow<br />

• Rotary handle can be rotated up to 90° for switches in lying position<br />

• Order extension shafts separately.<br />

FOR SIZES VARIANTS PU TYPE ORDER NO.<br />

MC1 Door interlock, black/grey 1 MC1-XTD MC190160—<br />

MC2 Door interlock, black/grey 1 MC2-XTD MC290162—<br />

MC3 Door interlock, black/grey 1 MC3-XTD MC390164—<br />

MC4 Door interlock, black/grey 1 MC4-XTD MC496612—<br />

MC1 Door interlock, lockable, black/grey 1 MC1-XTVD MC190166—<br />

MC2 Door interlock, lockable, black/grey 1 MC2-XTVD MC290168—<br />

MC3 Door interlock, lockable, black/grey 1 MC3-XTVD MC390170—<br />

MC4 Door interlock, lockable, black/grey 1 MC4-XTVD MC496614—<br />

MC1 Door interlock and on switch, lockable emergency stop 1 MC1-XTVDVR MC190178—<br />

MC2 Door interlock and on switch, lockable emergency stop 1 MC2-XTVDVR MC290180—<br />

MC2 Door interlock and on switch, lockable emergency stop 1 MC3-XTVDVR MC390182—<br />

MC4 Door interlock and on switch, lockable emergency stop 1 MC4-XTVDVR MC496618—<br />

W EXTENSION SHAFT<br />

w TECHNICAL DATA<br />

• Can be cut to required length<br />

• For maximum enclosure depths of 400 or 600 mm<br />

PGR 4960<br />

FOR SIZES DEPTH PU TYPE ORDER NO.<br />

MC1 / MC2 max. 400 mm 1 MC1/2-XV4 MC191232—<br />

MC3 / MC4 max. 400 mm 1 MC3/4-XV4 MC391234—<br />

MC1 / MC2 max. 600 mm 1 MC1/2-XV6 MC190191—<br />

MC3 / MC4 max. 600 mm 1 MC3/4-XV6 MC390193—


W MECHANICAL LOCKING DEVICE<br />

mc_xmv_i.eps<br />

mc_xmv_i2.eps<br />

MC ACCESSORIES<br />

w TECHNICAL DATA<br />

PGR 4960<br />

rotary handle on switch or<br />

additional door interlocking<br />

rotary handle required.<br />

Cannot be combined with<br />

parallel, side panel- and front<br />

drive or insulating frames.<br />

DESCRIPTION VARIANTS PU TYPE ORDER NO.<br />

Mechanical locking device MC 1 1 MC1-XMV MC191581—<br />

Mechanical locking device MC 2 1 MC2-XMV MC291582—<br />

Mechanical locking device MC 3 1 MC3-XMV MC391583—<br />

Mechanical locking device MC 4 1 MC4-XMV MC491584—<br />

Bowden cable 225 mm 1 MC-XBZ225 MC191585—<br />

Bowden cable 600 mm 1 MC-XBZ600 MC191586—<br />

Bowden cable 1,000 mm 1 MC-XBZ1000 MC191587—<br />

403


404<br />

W REMOTE OPERATORS<br />

mc299832.eps<br />

MC ACCESSORIES<br />

w TECHNICAL DATA<br />

• On/off switching and resetting by constant or impulse voltage<br />

• Switching can be synchronised<br />

• Local switching by hand possible<br />

• Switching time On ≤ 60 ms<br />

Switching must not be simultaneous via remote operator and tripped via undervoltage release/shunt trip. Remote<br />

operators can be combined with MC switches and MC-N disconnectors but not with MC-PN disconnectors.<br />

Operating instructions and measured diagrams are available on our homepage: www.schrack.com<br />

SIZES VOLTAGE PU TYPE ORDER NO.<br />

MC2 208 - 240 V AC 1 MC2-XR208-240AC MC299832—<br />

MC3 208 - 240 V AC 1 MC3-XR208-240AC MC399850—<br />

MC4 208 - 240 V AC 1 MC4-XR208-240AC MC496685—<br />

W ACCESSORIES<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

w INSULATING FRAMES:<br />

mc_fern_m.eps<br />

• For toggle lever, rotary handles and remote operator<br />

• Degree of protection IP20<br />

• For oblong cut-outs in doors and enclosures with thicknesses of 1,5-5 mm.<br />

• Identification labels can be clipped in<br />

w SPACERS:<br />

Enables fast and economic mounting of switches of various sizes, with or without rotary handle<br />

• Or remote drive on same grid depth<br />

• Each set contains 4 spacers<br />

• Grid depth increases by 17,5 mm for each spacer set<br />

w CLIP PLATES:<br />

• For mounting MC1/MC2 switches on DIN rail<br />

PGR 4960<br />

PGR 4960<br />

DESCRIPTION FOR SIZES PU TYPE ORDER NO.<br />

Insulating frame MC1 1 MC1-XBR MC190195—<br />

Insulating frame MC2 1 MC2-XBR MC290197—<br />

Insulating frame MC3 1 MC3-XPR MC394645—<br />

Insulating frame MC4 1 MC4-XBR MC494646—<br />

Spacer, M4 thread MC1 / MC2 1 MC1/2-XAB MC190203—<br />

Spacer, M5 thread MC3 1 MC3-XAB MC390211—<br />

Clip plate, 35 mm MC1 1 MC1-XC35 MC190213—


W CONNECTION ACCESSORIES MC1 TO MC4<br />

Technical data with respect to the load rating of rails can be found in the annex.<br />

W BOX TERMINALS<br />

mc190015.eps<br />

w TECHNICAL DATA<br />

W SCREW CONNECTIONS<br />

• Standard equipment with all MC1, MC1-PN and MC1-N switches<br />

• Conversion kit for switches with screw connections<br />

• Type includes parts for 3 or 4-pole switches respectively<br />

• 3/4-pole<br />

• Fitted inside switch housing<br />

• Use MC.-XSKA cover<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

w TECHNICAL DATA<br />

• Type includes parts for one side of switch, top or bottom<br />

3 or 4-pole respectively.<br />

• Fitted outside switch housing<br />

• Standard equipment with sizes MC2, MC3 and MC4<br />

• Use MC.-XSKA cover<br />

MC ACCESSORIES<br />

PGR 4962<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Box terminal up to 160 A.(contains 3 pcs.) for MC2 1 MC2-160-XKC MC292240—<br />

Box terminal up to 250 A.(contains 3 pcs.) for MC2 1 MC2-250-XKC MC292244—<br />

Box terminal up to 500 A.(contains 3 pcs.) for MC3 1 MC3-XKC MC390042—<br />

mc190019.eps<br />

PGR 4962<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Screw connections (contains 3 pcs.) for MC1 1 MC1-XKS MC190019—<br />

W TUNNEL TERMINALS<br />

mc196730.eps mc496836.eps<br />

w TECHNICAL DATA<br />

PGR 4962<br />

• for Cu- and Al cable<br />

• Includes cover<br />

• Includes parts for one side of the switch, top or bottom<br />

for 3-pole switches<br />

• Comes with terminal for control circuit cabling<br />

for 2 x 2,5 mm2 Cu cable<br />

• Fitted outside switch housing<br />

• Round cross-section or section cross-section cables<br />

• For 4-pole model, see Special Catalogue K-<strong>MCCB</strong>MCE4<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Tunnel terminal 95 mm 2 for MC1 1 MC1-XKA MC196730—<br />

Tunnel terminal 185 mm 2 for MC2 1 MC2-XKA MC291457—<br />

Tunnel terminal 185 mm 2 for MC3 1 MC3-XKA1 MC391459—<br />

Tunnel terminal 2x 240 mm 2 for MC3 1 MC3-XKA2 MC391461—<br />

Tunnel terminal 4x 240 mm 2 for MC4 1 MC4-XKA MC496836—<br />

405


406<br />

MC ACCESSORIES<br />

W CABLE LUGS<br />

mc299776.eps<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Cable lug 95 mm 2 1 MC2-XKS95 MC299775—<br />

Cable lug 120 mm 2 1 MC2-XKS120 MC299776—<br />

Cable lug 150 mm 2 1 MC2-XKS150 MC299777—<br />

Cable lug 185 mm 2 1 MC2-XKS185 MC290032—<br />

Cable lug 185 mm 2 , MC3 1 MC3-XKS185 MC390040—<br />

Cable lug 240 mm 2 , MC3 1 MC3-XKS240 MC390041—<br />

W REAR CONNECTIONS<br />

mc196734.eps<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Rear connection, 3-pol. MC1 1 MC1-XKR MC196734—<br />

Rear connection, 3-pol. MC2 1 MC2-XKR MC296765—<br />

Rear connection, 3-pol. MC3 1 MC3-XKR MC396792—<br />

Rear connection, 3-pol. MC4 1 MC4-XKR MC496842—<br />

W CONNECTION WIDTH EXTENSIONS<br />

w TECHNICAL DATA<br />

mc299775.eps<br />

w TECHNICAL DATA<br />

• Use MC.-XSKA cover or phase separator<br />

• Includes parts for one side of switch, top or bottom for 3-pole switch<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

w TECHNICAL DATA<br />

• Special cable lugs with narrow profile<br />

PGR 4962<br />

PGR 4962<br />

PGR 4962<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Connection width extension, MC4 3-pol. 1600 A 1 MC4-XKM2S-1600 MC494473—<br />

Connection width extension, MC4 4-pol. 1600 A 1 MC4-4XKM2S-1600 MC494474—


W CONTROL <strong>CIRCUIT</strong> TERMINAL<br />

mc196739.eps<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Control circuit terminal for box terminal MC1 / MC2 / MC3 1 MC1-XSTK MC196739—<br />

Control circuit terminal for screw terminal MC1 1 MC1-XSTS MC190150—<br />

Control circuit terminal for screw terminal MC2 1 MC2-XSTS MC290156—<br />

Control circuit terminal for screw terminal MC3/MC4 1 MC3/4-XSTS MC396797—<br />

W COVER<br />

mc290038.eps<br />

w TECHNICAL DATA<br />

w TECHNICAL DATA<br />

• Includes parts for two terminals, top or bottom for 3-pole or 4-pole switch<br />

• Supplied as standard with tunnel terminals<br />

w TECHNICAL DATA<br />

• Protection against accidental contact when using cable lugs, rails or<br />

tunnel terminals<br />

• Type includes parts for one side of switch, top or bottom<br />

for 3 or 4-pole switch respectively.<br />

• IP4X degree of protection front, side and rear on the connection side when using<br />

insulated conductor material IP1X<br />

• Cover already included for tunnel terminals<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

W PLUG-IN/WITHDRAWABLE UNITS<br />

W WITHDRAWABLE UNITS<br />

MC ACCESSORIES<br />

For technical data and ordering information, please refer to our Special Catalogue K-<strong>MCCB</strong>MCE4.<br />

Always order plug-in units together with switch.<br />

PGR 4962<br />

PGR 4962<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Terminal cover size MC1 1 MC1-XKSA MC190021—<br />

Terminal cover size MC2 1 MC2-XKSA MC290038—<br />

Terminal cover size MC3 1 MC3-XKSA MC390045—<br />

Terminal cover size MC4 1 MC4-XKSA MC496846—<br />

Includes auxiliary plug-in adaptor<br />

• Mounting position: vertical<br />

• 3 positions: Connected, test, disconnected as well as removed. The 3 positions are indicated mechanically.<br />

• The auxiliary contacts can also be used for remote signalling. Either an NC M22-K01 or NO M22-K10 depending on<br />

the position<br />

w ALSO REFER TO THE SPECIAL CATALOGUE<br />

K-<strong>MCCB</strong>MCE4<br />

PGR 4962<br />

PGR 4962<br />

407


408<br />

MC ACCESSORIES<br />

W ADAPTOR ELEMENTS FOR <strong>CIRCUIT</strong> <strong>BREAKERS</strong> &<br />

DISCONNECTORS FOR 60MM COMBINED RAIL SYSTEM<br />

w TECHNICAL DATA<br />

• For use on flat Cu rails 12 - 30 - x 5 - 10<br />

• Double-T and triple T profile<br />

• Mounting using terminal and screw fastenings<br />

• Rated operating voltage Ue: 690 V<br />

W MC 1 TO 125 A<br />

w TECHNICAL DATA<br />

• For switches with standard box terminal connection<br />

• Connection to system through connection cable supplied above<br />

• in conjunction with IP2X finger protection<br />

• Increase in protection against accidental contact is possible on output side of switch<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Combined rail adaptor 125 A, 60 mm 1 32570 MC195700—<br />

W MC 2 TO 250 A<br />

w TECHNICAL DATA<br />

• Connection to system possible top or bottom<br />

• A cover is required for adaptor elements and switches with rear connection<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Combined rail adaptor 250 A, 60 mm 1 32140 MC291400—<br />

Cover for adaptor element 1 MC2-XKR4 MC291666—<br />

W MC 3 TO 630 A<br />

w TECHNICAL DATA<br />

• Top connection to system<br />

• A cover is required for adaptor elements and switches with rear connection<br />

PGR 4962<br />

PGR 4962<br />

PGR 4962<br />

PGR 4962<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Combined rail adaptor 630 A, 60 mm 1 32170 MC391700—<br />

Cover for adaptor element 1 MC3-XKR13 MC391668—


W ACCESSORIES<br />

W RESIDUAL CURRENT RELEASES, 4-POLE<br />

w TECHNICAL DATA<br />

• For 4-pole MCCCbs MC2-4 and switch disconnectors MC2-N-4<br />

• Independent of mains and auxiliary power Ue = 200 V – 690 V 50/60 Hz<br />

• Auxillary switches: 1 N/O, 1 N/C<br />

• XFI30: Rated fault current ln = 0,03 A, suitable for personnel protection according to IEC/EN 60947-2 Annex B<br />

and VDE 664 parts 2 and 3<br />

• XFI: Rated fault current ln = 0,1-0,3-1-3 A, delay time tv = 60-150-300-450 ms,<br />

Core-balance principle with pulse current sensitivity and peak withstand current<br />

For technical data and ordering information, please refer to our Special Catalogue K-<strong>MCCB</strong>MCE4.<br />

DESCRIPTION PU TYPE ORDER NO.<br />

FI personnel protection 30 mA 1 MC2-4-XFI30 MC296719—<br />

FI 0,1-3 A 1 MC2-4-XFI MC296720—<br />

W EARTH FAULT RELEASES, 3/4-POLE<br />

w TECHNICAL DATA<br />

• Independent of mains and auxiliary supply<br />

• Ig = 0,3 x 1,0 x Iu<br />

• tg = 0 – 20 – 60 –100 – 200 – 500 – 750 – 1000 ms<br />

• Can only be used in conjunction with <strong>MCCB</strong>s with electronic releases<br />

• Earth fault can be displayed in optional DMI communicaiton module<br />

MC ACCESSORIES<br />

For technical data and ordering information, please refer to our Special Catalogue K-<strong>MCCB</strong>MCE4.<br />

PGR 4962<br />

PGR 4962<br />

PGR 4962<br />

DESCRIPTION PU TYPE ORDER NO.<br />

Earth fault release, 3-pole 1 MC3-XT MC390756—<br />

Earth fault release, 4-pole 1 MC3-4-XT MC390757—<br />

Earth fault release, 3-pole 1 MC4-XT MC496721—<br />

Earth fault release, 4-pole 1 MC4-4-XT MC496722—<br />

409


410<br />

SELECTIVITY TABLE MC TO MO<br />

Selectivity table MC MO 415 V AC<br />

In:<br />

Iu:<br />

Ii:<br />

1<br />

2 3 4<br />

rated current<br />

rated continuous<br />

current<br />

Instananeous tripping of<br />

undelayed short circuit<br />

protection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

As long as the short circuit current does not exceed<br />

the indicated values (Icc eff in kA) in the table,<br />

the downstream devices and upstream devices are<br />

selective. The indicated values show the<br />

selectivity limit.<br />

With ETU 25, 45, 76 the off-delay t sd must be<br />

at least 100 ms longer than the off-delay of<br />

the subordinated levels (2, 3, 4).<br />

Typ MO1-. upstream device with standard trip unit ETU15 MO1-. upstream device with selective trip unit ETU25<br />

In = Iu [A] 630 800 1000 1250 1600 630 800 1000 1250 1600<br />

Ii [A] 5040 6400 8000 10000 12800 12600 16000 20000 25000 32000<br />

Icu [kA] 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65<br />

down stream device selectivity limit (kA)<br />

Iu [A] Icu [kA] B N B N B N B N B N B N B N B N B N B N<br />

MC1-A.. . 40 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T<br />

50 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T<br />

63 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T<br />

80 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T<br />

100 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T<br />

125 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T<br />

MC2-A.. . 40 100(150) 5 5 6 6 8 8 12 12 20 20 20 20 40 40 T T T T T T<br />

50 100(150) 5 5 6 6 8 8 12 12 20 20 20 20 40 40 T T T T T T<br />

63 100(150) 5 5 6 6 8 8 12 12 20 20 20 20 40 40 T T T T T T<br />

80 100(150) 5 5 6 6 8 8 12 12 20 20 20 20 40 40 T T T T T T<br />

100 100(150) 5 5 6 6 8 8 12 12 20 20 20 20 40 40 T T T T T T<br />

125 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T<br />

160 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T<br />

200 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T<br />

250 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T<br />

MC1-M.. . 40 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T<br />

50 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T<br />

63 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T<br />

80 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T<br />

MC2-M.. 125 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T<br />

160 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T<br />

200 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T<br />

MC2-VE.. . 100 50...150 5 5 6 6 8 8 12 12 20 20 20 20 16 16 T T T T T T<br />

160 50...150 5 5 6 6 8 8 12 12 20 20 20 20 16 16 T T T T T T<br />

250 50...150 5 5 6 6 8 8 12 12 20 20 20 20 16 16 T T T T T T<br />

MC3-.E . 250 50...150 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 T T<br />

400 50...150 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 T T<br />

630 50...150 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 T T<br />

MC4-.E . 630 50...100 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 32 32<br />

800 50...100 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 32 32<br />

1000 50...100 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 32 32<br />

1250 50...100 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 32 32<br />

1600 50...100 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 32 32<br />

notice T: full selectivity<br />

mo_sel1.eps


Selectivity table MC MO 415 V AC<br />

In:<br />

Iu:<br />

Ii:<br />

1<br />

2 3 4<br />

rated current<br />

rated continuous<br />

current<br />

Instananeous tripping of<br />

undelayed short circuit<br />

protection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

SELECTIVITY TABLE MC TO MO<br />

Typ MO1-. upstream device with universal trip unit ETU45 MO1-. upstream device with digital trip unit ETU76<br />

In = Iu [A] 630 800 1000 1250 1600 630 800 1000 1250 1600<br />

Ii [kA] 40 52 40 52 40 52 40 52 40 52 40 52 40 52 40 52 40 52 40 52<br />

Icu [kA] 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65<br />

OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON<br />

down stream device selectivity limit (kA)<br />

Iu<br />

[A]<br />

Icu [kA] B N B N B N B N B N B N B N B N B N B N<br />

MC1-A.. . 40 25(50) T T T T T T T T T T T T T T T T T T T T<br />

50 25(50) T T T T T T T T T T T T T T T T T T T T<br />

63 25(50) T T T T T T T T T T T T T T T T T T T T<br />

80 25(50) T T T T T T T T T T T T T T T T T T T T<br />

100 25(50) T T T T T T T T T T T T T T T T T T T T<br />

125 25(50) T T T T T T T T T T T T T T T T T T T T<br />

MC2-A.. . 40 100(150) T T T T T T T T T T T T T T T T T T T T<br />

50 100(150) T T T T T T T T T T T T T T T T T T T T<br />

63 100(150) T T T T T T T T T T T T T T T T T T T T<br />

80 100(150) T T T T T T T T T T T T T T T T T T T T<br />

100 100(150) T T T T T T T T T T T T T T T T T T T T<br />

125 25...100 T T T T T T T T T T T T T T T T T T T T<br />

160 25...100 T T T T T T T T T T T T T T T T T T T T<br />

200 25...100 T T T T T T T T T T T T T T T T T T T T<br />

250 25...100 T T T T T T T T T T T T T T T T T T T T<br />

MC1-M.. . 40 25(50) T T T T T T T T T T T T T T T T T T T T<br />

50 25(50) T T T T T T T T T T T T T T T T T T T T<br />

63 25(50) T T T T T T T T T T T T T T T T T T T T<br />

80 25(50) T T T T T T T T T T T T T T T T T T T T<br />

100 25(50) T T T T T T T T T T T T T T T T T T T T<br />

MC2-M.. . 125 25...100 T T T T T T T T T T T T T T T T T T T T<br />

160 25...100 T T T T T T T T T T T T T T T T T T T T<br />

200 25...100 T T T T T T T T T T T T T T T T T T T T<br />

MC2-VE.. . 100 50...150 T T T T T T T T T T T T T T T T T T T T<br />

160 50...150 T T T T T T T T T T T T T T T T T T T T<br />

250 50...150 T T T T T T T T T T T T T T T T T T T T<br />

MC3-.E . 250 50...150 T T T T T T T T T T T T T T T T T T T T<br />

400 50...150 T T T T T T T T T T T T T T T T T T T T<br />

630 50...150 T T T T T T T T T T T T T T T T T T T T<br />

MC4-.E . 630 50(100)<br />

800 50(100)<br />

1000 50(100)<br />

1250 50(100)<br />

1600 50(100)<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

notice T: full selectivity<br />

mo_sel2.eps<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

<br />

As long as the short circuit current does not exceed<br />

the indicated values (Icc ef in kA) in the table,<br />

the downstream devices and upstream devices are<br />

selective. The indicated values show the<br />

selectivity limit.<br />

With ETU 25, 45, 76 the off-delay t sd must be<br />

at least 100 ms longer than the off-delay of<br />

the subordinated levels (2, 3, 4).<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

T/40T/52<br />

411


412<br />

SELECTIVITY TABLE MC TO MO<br />

Selectivity table MC MO 415 V AC<br />

In: Iu: I i:<br />

1<br />

2 3 4<br />

rated current<br />

rated continuous<br />

current<br />

Instananeous tripping of<br />

undelayed short circuit<br />

protection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Typ MO2-. upstream device with standard trip unit ETU15 Ii= 8 x I n<br />

<br />

As long as the short circuit current does not exceed<br />

the indicated values (Icc eff in kA) in the table,<br />

the downstream devices and upstream devices are<br />

selective. The indicated values show the<br />

selectivity limit.<br />

In = Iu [A] 800 1000 1250 1600 2000 2500 3200<br />

I i [A] 6400 8000 10000 12800 16000 20000 25600<br />

I cu [kA] 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100<br />

down stream device selectivity limit (kA)<br />

I u [A] I cu [kA] B N H B N H B N H B N H B N H B N H B N H<br />

MC1-A.. 40 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

50 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

63 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

80 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

100 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

125 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

MC2-A.. 40 100(150) 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 55 65 65 T T T<br />

50 100(150) 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 55 65 65 T T T<br />

63 100(150) 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 55 65 65 T T T<br />

80 100(150) 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 55 65 65 T T T<br />

100 100(150) 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 55 65 65 T T T<br />

125 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T<br />

160 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T<br />

200 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T<br />

250 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T<br />

MC1-M.. 40 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

50 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

63 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

80 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

100 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T<br />

MC2-M.. 125 25(50) 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T<br />

160 25(50) 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T<br />

200 25(50) 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T<br />

MC2-VE.. 100 50...150 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 T(55) T(65) T(65) T T T<br />

160 50...150 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 T(55) T(65) T(65) T T T<br />

250 50...150 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 T(55) T(65) T(65) T T T<br />

MC3-.E 250 50...150 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 30 30 30<br />

400 50...150 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 30 30 30<br />

630 50...150 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 30 30 30<br />

MC4-.E 630 50(100) 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 25 25 25<br />

800 50(100) 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 25 25 25<br />

1000 50(100) 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 25 25 25<br />

1250 50(100) 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 25 25 25<br />

1600 50(100) 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 25 25 25<br />

notice T: full selectivity<br />

mo_sel3.eps


Selectivity table MC MO 415 V AC<br />

In:<br />

Iu:<br />

Ii:<br />

1<br />

2 3 4<br />

rated current<br />

rated continuous<br />

current<br />

Instananeous tripping of<br />

undelayed short circuit<br />

protection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Typ MO2-. upstream device with standard trip unit ETU15 I = 8 x In<br />

SELECTIVITY TABLE MC TO MO<br />

<br />

As long as the short circuit current does not exceed<br />

the indicated values (Icceff in kA) in the table,<br />

the downstream devices and upstream devices are<br />

selective. The indicated values show the<br />

selectivity limit.<br />

With ETU 25, 45, 76 the off-delay t sd must be<br />

at least 100 ms longer than the off-delay of<br />

the subordinated levels (2, 3, 4).<br />

In = Iu [A] 800 1000 1250 1600 2000 2500 3200 400050006300<br />

Ii [A] 50000 50000 50000 50000 50000 50000 50000 50000<br />

Icu [kA] 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 100 100 100<br />

down stream device selectivity limit (kA)<br />

Iu [A] Icu [kA] B N H B N H B N H B N H B N H B N H B N H B N H<br />

MC1-A...<br />

40 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

50 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

63 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

80 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

100 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

125 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

MC2-A...<br />

40 100(150) 40 40 40 T T T T T T T T T T T T T T T T T T T T T<br />

50 100(150) 40 40 40 T T T T T T T T T T T T T T T T T T T T T<br />

63 100(150) 40 40 40 T T T T T T T T T T T T T T T T T T T T T<br />

80 100(150) 40 40 40 T T T T T T T T T T T T T T T T T T T T T<br />

100 100(150) 40 40 40 T T T T T T T T T T T T T T T T T T T T T<br />

125 25...150 T(40)T(40)T(40) T T T T T T T T T T T T T T T T T T T T T<br />

160 25...150 T(40)T(40)T(40) T T T T T T T T T T T T T T T T T T T T T<br />

200 25...150 T(40)T(40)T(40) T T T T T T T T T T T T T T T T T T T T T<br />

250 25...150 T(40)T(40)T(40) T T T T T T T T T T T T T T T T T T T T T<br />

MC1-M...<br />

40 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

50 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

63 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

80 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

100 25(50) T(35)T(35)T(35) T T T T T T T T T T T T T T T T T T T T T<br />

MC2-M...<br />

125 25...150 T(40)T(40)T(40) T T T T T T T T T T T T T T T T T T T T T<br />

160 25...150 T(40)T(40)T(40) T T T T T T T T T T T T T T T T T T T T T<br />

200 25...150 T(40)T(40)T(40) T T T T T T T T T T T T T T T T T T T T T<br />

MC2-E...<br />

100 50...150 16 16 16 T T T T T T T T T T T T T T T T T T T T T<br />

160 50...150 16 16 16 T T T T T T T T T T T T T T T T T T T T T<br />

250 50...150 16<br />

MC3-.E...<br />

16 16 T T T T T T T T T T T T T T T T T T T T T<br />

250 50...150 16 16 16 20 20 20 30 30 30 T T T T T T T T T T T T T T T<br />

400 50...150 16 16 16 20 20 20 30 30 30 T T T T T T T T T T T T T T T<br />

630 50...150 16 16 16 20 20 20 30 30 30 T T T T T T T T T T T T T T T<br />

MC4-.E...<br />

630 50...100 16 16 16 20 20 20 30 30 30 32 32 32 40 40 40 T(50)T(50)T(50)T(50)T(50)T(50) T(50)T(50)T(50)<br />

800 50...100 16 16 16 20 20 20 30 30 30 32 32 32 40 40 40 T(50)T(50)T(50)T(50)T(50)T(50) T(50)T(50)T(50)<br />

100050...100 16 16 16 20 20 20 30 30 30 32 32 32 40 40 40 T(50)T(50)T(50)T(50)T(50)T(50) T(50)T(50)T(50)<br />

125050...100 16 16 16 20 20 20 30 30 30 32 32 32 40 40 40 T(50)T(50)T(50)T(50)T(50)T(50) T(50)T(50)T(50)<br />

160050...100 16 16 16 20 20 20 30 30 30 32 32 32 40 40 40 T(50)T(50)T(50)T(50)T(50)T(50) T(50)T(50)T(50)<br />

notice T: full selectivity<br />

mo_sel4.eps<br />

max<br />

413


414<br />

SELECTIVITY TABLE MC TO MO<br />

Selectivity table MC MO 415 V AC<br />

In:<br />

Iu:<br />

Ii:<br />

1<br />

2 3 4<br />

rated current<br />

rated continuous<br />

current<br />

Instananeous tripping of<br />

undelayed short circuit<br />

protection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Typ MO2(3)-. upstream device with universal trip unit ETU45 I i = 0.8 x I cu(= 0.8 x I cs)<br />

<br />

As long as the short circuit current does not exceed<br />

the indicated values (Icceff in kA) in the table,<br />

the downstream devices and upstream devices are<br />

selective. The indicated values show the<br />

selectivity limit.<br />

With ETU 25, 45, 76 the off-delay t sd must be<br />

at least 100 ms longer than the off-delay of<br />

the subordinated levels (2, 3, 4).<br />

In = Iu [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300<br />

Ii [kA] 44 64 80 44 64 80 44 64 80 44 64 80 44 64 80 44 64 80 44 64 80 80<br />

Icu [kA] 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 100 100 100<br />

down stream device selectivity limit (kA)<br />

Iu<br />

[A]<br />

Icu<br />

[kA]<br />

B N<br />

OFF/ON<br />

H B N<br />

OFF/ON<br />

H B N<br />

OFF/ON<br />

H B N<br />

OFF/ON<br />

H B N<br />

OFF/ON<br />

H B N<br />

OFF/ON<br />

H B N<br />

OFF/ON<br />

H B N<br />

OFF/ON<br />

H<br />

MC1-A...<br />

40 25(25) T T T T T T T T T T T T T T T T T T T T T T T T<br />

50 25(25) T T T T T T T T T T T T T T T T T T T T T T T T<br />

63 25(25) T T T T T T T T T T T T T T T T T T T T T T T T<br />

80 25(25) T T T T T T T T T T T T T T T T T T T T T T T T<br />

100 25(25) T T T T T T T T T T T T T T T T T T T T T T T T<br />

125 25(25) T T T T T T T T T T T T T T T T T T T T T T T T<br />

MC2-A..<br />

40 100(150)T T T T T T T T T T T T T T T T T T T T T T T T<br />

50 100(150)T T T T T T T T T T T T T T T T T T T T T T T T<br />

63 100(150)T T T T T T T T T T T T T T T T T T T T T T T T<br />

80 100(150)T T T T T T T T T T T T T T T T T T T T T T T T<br />

100 100(150)T T T T T T T T T T T T T T T T T T T T T T T T<br />

125 25...150 T T T T T T T T T T T T T T T T T T T T T T T T<br />

160 25...150 T T T T T T T T T T T T T T T T T T T T T T T T<br />

200 25...150 T T T T T T T T T T T T T T T T T T T T T T T T<br />

250 25...150 T T T T T T T T T T T T T T T T T T T T T T T T<br />

MC1-M..<br />

40 25(50) T T T T T T T T T T T T T T T T T T T T T T T T<br />

50 25(50) T T T T T T T T T T T T T T T T T T T T T T T T<br />

63 25(50) T T T T T T T T T T T T T T T T T T T T T T T T<br />

80 25(50) T T T T T T T T T T T T T T T T T T T T T T T T<br />

100 25(50) T T T T T T T T T T T T T T T T T T T T T T T T<br />

MC2-M..<br />

125 25...150 T T T T T T T T T T T T T T T T T T T T T T T T<br />

160 25...150 T T T T T T T T T T T T T T T T T T T T T T T T<br />

250 25...150 T T T T T T T T T T T T T T T T T T T T T T T T<br />

MC2-.E..<br />

100 50...150 T T T T T T T T T T T T T T T T T T T T T T T T<br />

160 50...150 T T T T T T T T T T T T T T T T T T T T T T T T<br />

250 50...150 T T T T T T T T T T T T T T T T T T T T T T T T<br />

MC3-.E...<br />

250 50...150 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) T(80)T(80)T(80)<br />

400 50...150 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) T(80)T(80)T(80)<br />

630 50...150 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) T(80)T(80)T(80)<br />

MC4-.E<br />

630 50(100) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) T(80)T(80)T(80)<br />

800 50(100) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) T(80)T(80)T(80)<br />

1000 50(100) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) T(80)T(80)T(80)<br />

1250 50(100) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) T(80)T(80)T(80)<br />

1600 50(100) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) 45 T(64)T(80) T(80)T(80)T(80)<br />

notice T: full selectivity<br />

mo_sel5.eps


Selectivity table MC MO 415 V AC<br />

In:<br />

Iu:<br />

Ii:<br />

1<br />

2 3 4<br />

rated current<br />

rated continuous<br />

current<br />

Instananeous tripping of<br />

undelayed short circuit<br />

protection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

SELECTIVITY TABLE MC TO MO<br />

<br />

As long as the short circuit current does not exceed<br />

the indicated values (Icceff in kA) in the table,<br />

the downstream devices and upstream devices are<br />

selective. The indicated values show the<br />

selectivity limit.<br />

With ETU 25, 45, 76 the off-delay t sd must be<br />

at least 100 ms longer than the off-delay of<br />

the subordinated levels (2, 3, 4).<br />

Typ MO2-. upstream device with digital trip unit ETU76 I i = 0,8 x I cu =0,8x I cs<br />

In = Iu [A] 800 1000 1250 1600<br />

Ii [A] 44000 64000 80000 44000 64000 80000 44000 64000 80000 44000 64000 80000<br />

Icu [kA] 55 80 100 55 80 100 55 80 100 55 80 100<br />

down stream device selectivity limit (kA)<br />

Iu [A] Icu [kA] B N H B N H B N H B N H<br />

MC1-A.. 40 25(50) T T T T T T T T T T T T<br />

50 25(50) T T T T T T T T T T T T<br />

63 25(50) T T T T T T T T T T T T<br />

80 25(50) T T T T T T T T T T T T<br />

100 25(50) T T T T T T T T T T T T<br />

125 25(50) T T T T T T T T T T T T<br />

MC2-A.. 40 100(150) T T T T T T T T T T T T<br />

50 100(150) T T T T T T T T T T T T<br />

63 100(150) T T T T T T T T T T T T<br />

80 100(150) T T T T T T T T T T T T<br />

100 100(150) T T T T T T T T T T T T<br />

125 25...150 T T T T T T T T T T T T<br />

160 25...150 T T T T T T T T T T T T<br />

200 25...150<br />

250 25...150 T T T T T T T T T T T T<br />

MC1-M.. 40 25(50) T T T T T T T T T T T T<br />

50 25(50) T T T T T T T T T T T T<br />

63 25(50) T T T T T T T T T T T T<br />

80 25(50) T T T T T T T T T T T T<br />

100 25(50) T T T T T T T T T T T T<br />

MC2-M.. 125 25...150 T T T T T T T T T T T T<br />

160 25...150 T T T T T T T T T T T T<br />

200 25...150 T T T T T T T T T T T T<br />

MC2-E.. 100 50...150 T T T T T T T T T T T T<br />

160 50...150 T T T T T T T T T T T T<br />

250 50...150 T T T T T T T T T T T T<br />

MC3-.E.. 250 50...150 T T T T T T T T T T T T<br />

400 50...150 T T T T T T T T T T T T<br />

630 50...150 T T T T T T T T T T T T<br />

MC4-.E.. 630 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80)<br />

800 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80)<br />

1000 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80)<br />

1250 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80)<br />

1600 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80)<br />

notice T: full selectivity<br />

mo_sel6.eps<br />

415


416<br />

SELECTIVITY TABLE MC TO MO<br />

Selectivity table MC MO 415 V AC<br />

In:<br />

Iu:<br />

Ii:<br />

1<br />

2 3 4<br />

rated current<br />

rated continuous<br />

current<br />

Instananeous tripping of<br />

undelayed short circuit<br />

protection<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

As long as the short circuit current does not exceed<br />

the indicated values (Icceff in kA) in the table,<br />

the downstream devices and upstream devices are<br />

selective. The indicated values show the<br />

selectivity limit.<br />

With ETU 25, 45, 76 the off-delay t sd must be<br />

at least 100 ms longer than the off-delay of<br />

the subordinated levels (2, 3, 4).<br />

Typ MO2(3)-. upstream device with digital trip unit (ETU76) Ii = 0,8 x Icu = 0,8 x Ics<br />

In = Iu [A] 2000 2500 3200 4000 5000 6300<br />

Ii [A] 44000 64000 80000 44000 64000 80000 44000 64000 80000 80000 80000 80000<br />

Icu[kA] 55 80 100 55 80 100 55 80 100 100 100 100<br />

down stream device selectivity limit (kA)<br />

Iu<br />

[A]<br />

Icu<br />

[kA]<br />

B N H B N H B N H B N H<br />

MC1-A.. 40 25(50) T T T T T T T T T T T T<br />

50 25(50) T T T T T T T T T T T T<br />

63 25(50) T T T T T T T T T T T T<br />

80 25(50) T T T T T T T T T T T T<br />

100 25(50) T T T T T T T T T T T T<br />

125 25(50) T T T T T T T T T T T T<br />

MC2-A.. 40 100(150) T T T T T T T T T T T T<br />

50 100(150) T T T T T T T T T T T T<br />

63 100(150) T T T T T T T T T T T T<br />

80 100(150) T T T T T T T T T T T T<br />

100 100(150) T T T T T T T T T T T T<br />

125 25...150 T T T T T T T T T T T T<br />

160 25...150 T T T T T T T T T T T T<br />

200 25...150 T T T T T T T T T T T T<br />

250 25...150 T T T T T T T T T T T T<br />

MC1-M.. 40 25(50) T T T T T T T T T T T T<br />

50 25(50) T T T T T T T T T T T T<br />

63 25(50) T T T T T T T T T T T T<br />

80 25(50) T T T T T T T T T T T T<br />

100 25(50) T T T T T T T T T T T T<br />

MC2-M.. 125 25...150 T T T T T T T T T T T T<br />

160 25...150 T T T T T T T T T T T T<br />

250 25...150 T T T T T T T T T T T T<br />

MC2-E.. 100 50...150 T T T T T T T T T T T T<br />

160 50...150 T T T T T T T T T T T T<br />

250 50...150 T T T T T T T T T T T T<br />

MC2-E.. 250 50...150 T T T T T T T T T T T T<br />

400 50...150 T T T T T T T T T T T T<br />

630 50...150 T T T T T T T T T T T T<br />

MC4-.E.. 63 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)<br />

800 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)<br />

1000 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)<br />

1250 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)<br />

1600 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)<br />

notice T: full selectivity<br />

mo_sel7.eps


MC.<br />

BM<br />

mc_seltab1.eps<br />

mc_seltab2.eps<br />

mc_seltab3.eps<br />

short circuit selectivity BM-B to MC 1/2<br />

Selectivity limiting current IS [kA] for selectivity between BM - B... und MC...<br />

(Set overload- and short circuit protection device MC to max. value)<br />

MC1- A...<br />

Icu = 25 (50) kA<br />

SELECTIVITY TABLE BM TO MC<br />

MC 2- A...<br />

Icu = 25 (50)(100)(150) kA<br />

BM - B.. 40 50 63 80 100 125 40 50 63 80 100 125 160 200 250<br />

1 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15<br />

2 1.7 10 15 15 15 15 2.5 10 15 15 15 15 15 15 15<br />

3 1 1.7 2.5<br />

2.5 8.5 10 1.3 1.3 3 4.3 15 15 15 15 15<br />

4 1 1.7 2.5 2.5 6.5 10 1.1 1.3 3 3.5 10 10 10 10 10<br />

6 1 1.7 2.1 2.5 4.3 8.5 1.1 1.3 2.5 2.5 10 10 10 10 10<br />

10 1 1.3 1.7 1.7 3.5 8.5 0.9 1.3 2.5 2.5 10 10 10 10 10<br />

13 0.9 1.3 1.7 1.7 3.5 8.5 0.9 1 1.7 2.5 10 10 10 10 10<br />

16 0.9 1 1.5 1.7 2.5 6.5 0.9 1 1.3 2.1 10 10 10 10 10<br />

20 0.7 1 1.3 1.3 2.5 6.5 0.9 1 1.3 1.3 10 10 10 10 10<br />

25 0.6 1 1.3 1.3 2.5 6 0.7 0.9 1.3 1.7 8 8 8 8 10<br />

32 - 1 0.9 1.3 1.7 5 - 0.9 1.3 1.7 7 7 7 7 8.5<br />

40 - - 0.9 1.3 1.7 4.3 - - 1 1.3 5 5 5 5 8.5<br />

50 - - - 1 1.3 3.5 - - - 1.3 5 5 5 5 8.5<br />

63 - - - - 1.3 2.5 - - - - 5 5 5 5 8.5<br />

MC.<br />

BM<br />

BM - C..<br />

1<br />

2<br />

3<br />

4<br />

6<br />

10<br />

13<br />

16<br />

20<br />

25<br />

32<br />

40<br />

50<br />

63<br />

MC<br />

BM<br />

short circuit selectivity BM-C to MC 1/2<br />

Selectivity limiting current IS [kA] for selectivity between BM - C... und MC...<br />

(Set overload- and short circuit protection device MC to max. value)<br />

MC1- A...<br />

Icu = 25 (50) kA<br />

MC 2- A...<br />

Icu = 25 (50)(100)(150) kA<br />

40 50 63 80 100 125 40 50 63 80 100 125 160 200 250<br />

15 15 15 15 15 15 15 15 15 15 15 15 15 15 15<br />

10 10 15 15 15 15 2.5 10 15 15 15 15 15 15 15<br />

1 1.7 2.5<br />

2.5 8.5 10 1.3 1.3 3 4.3 15 15 15 15 15<br />

1 1.7 2.5 2.5 6.5 10 1.1 1.3 3 3.5 10 10 10 10 10<br />

1 1.7 2.1 2.5 4.3 8.5 1.1 1.3 2.5 2.5 10 10 10 10 10<br />

1 1.3 1.7 1.7 3.5 8.5 0.9 1.3 2.5 2.5 10 10 10 10 10<br />

0.9 1.3 1.7 1.7 3.5 8.5 0.9 1 1.7 2.5 10 10 10 10 10<br />

0.9 1 1.5 1.7 2.5 6.5 0.9 1 1.3 2.1 10 10 10 10 10<br />

0.7 1 1.3 1.3 2.5 6.5 0.9 1 1.3 1.3 10 10 10 10 10<br />

0.6 1 1.3 1.3 2.5 6 0.7 0.9 1.3 1.7 8 8 8 8 10<br />

- 1 0.9 1.3 1.7 5 - 0.9 1.3 1.7 7 7 7 7 8.5<br />

- - 0.9 1.3 1.7 4.3 - - 1 1.3 5 5 5 5 8.5<br />

- - - 1 1.3 3.5 - - - 1.3 5 5 5 5 8.5<br />

- - - - 1.3 2.5 - - - - 5 5 5 5 8.5<br />

short circuit selectivity BM-D to MC 1/2<br />

Selectivity limiting current IS [kA] for selectivity between BM - D... und MC...<br />

(Set overload- and short circuit protection device MC to max. value)<br />

MC1- A...<br />

Icu = 25 (50) kA<br />

MC2- A...<br />

Icu = 25 (50)(100)(150) kA<br />

BM-D.. 40 50 63 80 100 125 40 50 63 80 100 125 160 200 250<br />

0.5 7.5 15 15 15 15 15 9 15 15 15 15 15 15 15 15<br />

1 0.4 0.6 0.8 1.6 3.5 15 0.4 0.6 0.9 1.6 3.5 10 15 15 15<br />

1.5 0.2 0.5 0.7 0.9 1.4 2.2 0.2 0.5 0.7 0.9 1.4 2.2 4.3 15 15<br />

2 0.2 0.4 0.7 0.8 1.2 2.0 0.2 0.4 0.7 0.8 1.2 2.0 3.8 8.5 10<br />

2.5 0.2 0.4 0.7 0.8 1.1 2.0 0.2 0.4 0.7 0.8 1.1 2.0 3.6 7.7 10<br />

3 0.2 0.4 0.6 0.75 1.1 1.8 0.2 0.4 0.6 0.8 1.1 1.8 3.1 6.0 10<br />

3.5 0.2 0.4 0.6 0.75 1.1 1.7 0.2 0.4 0.6 0.8 1.1 1.7 2.8 4.8 8.5<br />

4 0.2 0.4 0.6 0.75 1.1 1.6 0.2 0.4 0.6 0.8 1.1 1.6 2.6 4.0 6.8<br />

5 0.2 0.4 0.6 0.75 1.1 1.6 0.2 0.4 0.6 0.8 1.1 1.6 2.6 3.7 6.0<br />

6 0.2 0.4 0.5 0.75 1.1 1.5 0.2 0.4 0.5 0.8 1.1 1.5 2.4 3.4 5.1<br />

8 0.2 0.2 0.5 0.7 0.85 1.1 0.2 0.2 0.5 0.7 0.9 1.1 1.5 2.3 3.4<br />

10 0.2 0.2 0.5 0.7 0.8 1.0 0.2 0.2 0.5 0.7 0.9 1.0 1.4 2.0 3.1<br />

13 0.2 0.2 0.4 0.6 0.75 0.9 0.2 0.2 0.4 0.6 0.8 0.9 1.4 1.9 2.7<br />

16 - 0.2 0.4 0.55 0.7 0.9 - 0.2 0.4 0.55 0.7 0.9 1.3 1.8 2.6<br />

20 - - 0.4 0.55 0.7 0.9 - - 0.4 0.55 0.7 0.9 1.2 1.8 2.6<br />

25 - - 0.4 0.55 0.7 0.9 - - 0.4 0.55 0.7 0.9 1.2 1.6 2.3<br />

32 - - - - 0.7 0.9 - - - - 0.7 0.9 1.2 1.6 2.3<br />

40 - - - - - 0.85<br />

- - - - - 0.9 1.2 1.6 2.2<br />