Control valves<br />

Traditionally most larger shell boilers are supplied with<br />

a DN40 valve. The DN40 valve is available with a range<br />

of reduced seats to match the feedrate. Alternatively,<br />

and particularly for new boiler plant, a smaller valve can<br />

be specified. See separate Spirax Sarco literature for<br />

valve dimensions and selection information.<br />

Electric actuators must include a 1 000 ohm feedback<br />

potentiometer.<br />

Pneumatic actuators must include a positioner (E to P).<br />

Steel enclosure with<br />

chassis plate and two<br />

DIN rails for mounting<br />

two or three <strong>level</strong><br />

controllers plus<br />

terminals.<br />

400<br />

300<br />

Electrically actuated<br />

control valve<br />

with feedback<br />

potentiometer<br />

Recommended ancillaries<br />

Enclosures Probe chamber<br />

Plastic enclosure with<br />

DIN mounting rail.<br />

For a single controller.<br />

IP67 rating.<br />

Sequencing purge valve<br />

Type SPV1 with cast iron body, flanged BS 4504<br />

PN16, DN25 for boiler pressures up to 13 bar g.<br />

Type SPV3 with bronze body flanged BS 4504 PN40,<br />

DN25 or BS 10 table F/H, 1" for boiler pressures up to<br />

25 bar g.<br />

83<br />

205 deep<br />

83<br />

288<br />

175<br />

125<br />

150 deep<br />

½" BSP drain<br />

Steel probe chamber<br />

flanged BS 4504<br />

PN40, DN25.<br />

For maximum<br />

boiler pressure<br />

of 32 bar g.<br />

1" BSP<br />

(Reducing<br />

bush<br />

required for<br />

LP20)<br />

Pneumatically<br />

actuated control<br />

valve with<br />

positioner<br />

Disc check valve<br />

Type DCV2/B for fitting between control valve and<br />

boiler to prevent return flow. Will also ensure that<br />

feedtank will not drain into boiler when boiler is<br />

depressurised. See separate literature for full details.<br />

83<br />

65<br />

457<br />