Climate Control Walk-In Unit Coolers - Medium Profile
Climate Control Walk-In Unit Coolers - Medium Profile
Climate Control Walk-In Unit Coolers - Medium Profile
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Performance Data<br />
Model CMA Air Defrost | 60 Hz<br />
4<br />
Model<br />
10°F TD<br />
25°F SST<br />
Capacity Fan Data Air Throw* †<br />
6°C TD<br />
- 4°C SST No. CFM m 3 h<br />
Diameter<br />
Diffused<br />
(Standard)<br />
Extended<br />
(Optional)<br />
BTUH Watts in. mm ft. m ft. m<br />
CMA130 13,000 3,810 1 2,300 3,910 18 457 50 15 65 20<br />
CMA155 15,500 4,540 1 2,200 3,740 18 457 50 15 65 20<br />
CMA245 24,500 7,180 2 4,600 7,820 18 457 50 15 65 20<br />
CMA300 30,000 8,790 2 4,400 7,480 18 457 50 15 65 20<br />
CMA365 36,500 10,690 3 6,900 11,730 18 457 50 15 65 20<br />
CMA450 45,000 13,180 3 6,600 11,220 18 457 50 15 65 20<br />
CMA510 51,000 14,940 4 9,200 15,640 18 457 50 15 65 20<br />
CMA600 60,000 17,570 4 8,800 14,960 18 457 50 15 65 20<br />
CMA710 71,000 20,790 5 10,500 17,850 18 457 50 15 65 20<br />
Model CMA Air Defrost | 50 Hz ‡<br />
Model<br />
10°F TD<br />
25°F SST<br />
Capacity Fan Data Air Throw* †<br />
6°C TD<br />
- 4°C SST No. CFM m 3 h<br />
Diameter<br />
Diffused<br />
(Standard)<br />
Extended<br />
(Optional)<br />
BTUH Watts in. mm ft. m ft. m<br />
CMA130 11,960 3,500 1 2,070 3,520 18 457 45 13.5 60 18.5<br />
CMA155 14,260 4,180 1 1,980 3,370 18 457 45 13.5 60 18.5<br />
CMA245 22,540 6,600 2 4,140 7,040 18 457 45 13.5 60 18.5<br />
CMA300 27,600 8,080 2 3,960 6,730 18 457 45 13.5 60 18.5<br />
CMA365 33,580 9,840 3 6,210 10,560 18 457 45 13.5 60 18.5<br />
CMA450 41,400 12,130 3 5,940 10,100 18 457 45 13.5 60 18.5<br />
CMA510 46,920 13,740 4 8,280 14,080 18 457 45 13.5 60 18.5<br />
CMA600 55,200 16,170 4 7,920 13,460 18 457 45 13.5 60 18.5<br />
CMA710 65,320 19,130 5 9,450 16,070 18 457 45 13.5 60 18.5<br />
* Optional molded fan guards allow for extended air throw; standard wire guards promote air diffusion<br />
† Air throw data based on 12-ft. high ceilings with no obstructions where velocity drops to 50 FPM<br />
‡ For EC motors, use 60 Hz capacity and airflow values (<strong>Unit</strong>s with EC motors operating at 50 Hz will not see a reduction in performance due to the<br />
electronic control of the motor)