Background Gain Control (BGC)<br />

Infrared <strong>Flame</strong> Scanners Type 45RM2<br />

The self-checking 45RM2 <strong>Flame</strong> Scanner incorporates<br />

design features uniquely suited to detecting individual<br />

flames and discriminating between flame envelopes. They<br />

are similar to the Type 45RM1 scanners but operate further<br />

into the infrared region with a much broader spectral<br />

response. <strong>Flame</strong>s monitored by the 45RM2 may be those<br />

of pulverized coal, oil, natural gas, and flames of other<br />

sources of methane, propane, butane, and other gases.<br />

Fiber optic version and explosion proof housing versions<br />

available.<br />

Refer to Bulletin CU-26.<br />

TYPE/MODEL<br />

FREQ.<br />

HZ.<br />

WAVELENGTH<br />

(nanometers)<br />

Replacement Parts<br />

61-4468-1 Shutter and bracket assembly<br />

61-2275-3 Glass lens assembly<br />

60-1622 Long Range Lens Assembly (for use when scanner is greater<br />

than 12 feet from flame, e.g. kiln applications).<br />

60-2366 Quick disconnect kit, includes 1/2" flexible conduit adapter.<br />

<strong>Inc</strong>ludes both male and female connectors.<br />

Recommended Scanner Cable<br />

59-470 6-Wire shielded scanner cable.<br />

14 FIREYE ® System Components<br />

MOUNT<br />

THREADS<br />

AMBIENT<br />

TEMP. MAX.,<br />

MIN.<br />

SAFETY<br />

APPROVALS<br />

NOTES<br />

45RM2-1000<br />

700-2,500 1" NPT 150°F (65°C) FM, APAVE —<br />

45RM2-1001 50/60<br />

1" BSP<br />

- 40°F (-40°C)<br />

FM, DIN<br />

SCANNERS WITH EXPLOSION-PROOF HOUSINGS<br />

45RM2-1000EX<br />

700-2,500 1" NPT 150°F (65°C) — Class I, Div. 1 and 2, Goups C, D; Class<br />

50/60<br />

-40°F (-40°C)<br />

FIBER OPTIC SCANNERS<br />

II, Div. 1 and 2, Groups E, F, G: Class<br />

III approved housing.<br />

61-5234 50/60 700-2,500 Fiber Optic 150°F (65°C) — For use with glass or quartz fiber optic<br />

Mounting -40°F (-40°C)<br />

assemblies.<br />

All controls in this table are compatible with all <strong>Fireye</strong> amplifiers listed in Table 2.<br />

When these scanners are used with 25SU3-2100, a 19UVPS-2120 or -2220, or 19MPS-2000 power supply is required.