GENERAL<br />

HVAC systems supply conditioned air to virtually every area<br />

of a building. Smoke introduced into an air recirculation<br />

system is distributed to occupied areas of a building. The<br />

System Sensor DH400 Series Duct Detector Housing is<br />

designed to sample air currents passing through a duct,<br />

allowing early detection of a developing fire. When sufficient<br />

smoke is sensed, an alarm signal is initiated at the<br />

fire alarm panel monitoring the detector, and appropriate<br />

action can be taken to shut off fans and blowers, change<br />

over air handling systems, etc. This can prevent the rapid<br />

distribution or isolation of toxic smoke and fire gases<br />

throughout the areas served by the duct system.<br />

The System Sensor DH400 duct detector system is easy<br />

to install and maintain.<br />

NOTE: The System Sensor DH400 Duct Detector Housing<br />

is supplied with either the 1451DH Ionization Sensor<br />

(DH400I) or the 2451 Photoelectric Sensor (DH400P).<br />

FEATURES<br />

12/24 VDC operation.<br />

Accommodates ionization or photoelectric heads.<br />

Simple change-out of detectors heads; twist-in, twist-out.<br />

Powered output for remote LED.<br />

Air velocity rating from 500 to 4,000 feet (152.4 to 1219.2<br />

meters) per minute.<br />

UL 268A listed to two-wire control panels.<br />

Clear polycarbonate cover for convenient visual inspection<br />

of sampling tube filters.<br />

Rugged Noryl® housing (mounting portion).<br />

Remote test station option.<br />

Easy and quick mounting to round or rectangular ducts<br />

from 1' to 12' (0.6 to 3.66 meters) wide.<br />

Three-year limited warranty.<br />

APPLICATIONS<br />

Duct smoke detectors have specific limitations.<br />

Duct detectors are:<br />

NOT a substitute for open area smoke detectors.<br />

NOT a substitute for early warning detection.<br />

NOT a replacement for a building’s regular fire detection<br />

system.<br />

System Sensor duct detector “Applications and Installation<br />

Instructions” should be used for reference, as well as<br />

“Guide for Proper Use of System Smoke Detectors” (I56-<br />

407-000). Call <strong>Fire</strong> <strong>Lite</strong> for information.<br />

June 18, 1998<br />

DH400 Series<br />

2-Wire Duct Detector Housings for<br />

Ionization and Photoelectric Sensors<br />

S911<br />

This document is not intended to be used for installation purposes. We try to keep our product<br />

information up-to-date and accurate. We cannot cover all specific applications or anticipate all<br />

requirements. All specifications are subject to change without notice. For more information,<br />

contact <strong>Fire</strong>•<strong>Lite</strong> <strong>Alarms</strong>, One <strong>Fire</strong>-<strong>Lite</strong> Place, Northford, Connecticut 06472. Phone: (800) 627-<br />

3473, Toll Free FAX: (877) 699-4105, FAX Back:(888) 388-3299<br />

WEB: www.firelite.com<br />

Section: Conventional Initiating Devices<br />

CS308<br />

MEA<br />

427-91-E 0V3A0.AY<br />

California<br />

State <strong>Fire</strong><br />

Marshal<br />

F-575<br />

3240-1209:155<br />

DH400 Series Duct Detector Housing<br />

CONSTRUCTION AND INSTALLATION<br />

The twist-in, twist-out detector and base allow the removal<br />

of detectors easily and quickly for cleaning and maintenance.<br />

In addition, detector heads can be changed to fit<br />

the application without removing the duct housing. The<br />

DH400 comes with built-in exhaust tube. Sampling tubes<br />

are available to fit ducts from 1 to 12 feet (0.6 to 3.66 meters)<br />

wide.<br />

SPECIFICATIONS<br />

DIMENSIONS: Width: 14-1/2" (36.83 cm). Height: 5"<br />

(12.70 cm). Depth (installed): 4" (10.16 cm).<br />

Weight: 4 lbs. (1.814 kg.).<br />

OPERATING RANGES: Temperature: 0°C to 49°C (32°F<br />

to 120°F). Humidity: 10% to 93% relative humidity.<br />

Air duct velocity: 500' (152.4 m) to 4,000' (1219.2 m) per<br />

minute.<br />

Reset time: 0.3 seconds (maximum).<br />

UL listed to 268A.<br />

DF-51096 — Page 1 of 2


ELECTRICAL RATINGS<br />

(includes base and detector)<br />

System voltage: 12/24 VDC.<br />

Maximum ripple voltage: 4 volts peak to peak.<br />

Start-up capacitance: 0.02 µF maximum.<br />

Standby ratings: 8.5 VDC minimum, 35 VDC maximum,<br />

120 µA maximum.<br />

Alarm ratings: 4.2 VDC minimum at 10 mA; 6.6 VDC maximum<br />

at 100 mA; alarm current must be limited to 100 mA<br />

or less by the control panel. If used, the RA400Z remote<br />

lamp operates within the specified alarm currents.<br />

Reset voltage: 2.5 VDC minimum.<br />

Reset time: 0.3 seconds maximum.<br />

INLET TUBE SELECTION<br />

Outside Duct Width Inlet Tube Required*<br />

Up to 2 feet<br />

(0.6096 m)<br />

2 to 4 feet<br />

(0.6096 to 1.2192 m)<br />

4 to 8 feet<br />

(1.2192 to 2.4384 m)<br />

8 to 10 feet<br />

(2.4384 to 3.0480 m)<br />

*NOTE: Inlet tube is required and must be purchased<br />

separately. Order one inlet tube for each duct detector<br />

housing ordered.<br />

Page 2 of 2 — DF-51096<br />

ST-1.5<br />

ST-3<br />

ST-5<br />

ST-10<br />

PRODUCT LINE INFORMATION<br />

Model Description<br />

DH400I Duct detector housing with ionization smoke<br />

detector.<br />

1451DH Replacement ionization smoke detector head.<br />

DH400P Duct detector housing with photoelectric<br />

smoke detector.<br />

2451 Replacement photoelectric smoke detector<br />

head.<br />

ST-1.5 Metal sampling tube, duct widths 1' to 2' (see<br />

table at left for metric lengths).<br />

ST-3 Metal sampling tube, duct widths 2' to 4'.<br />

ST-5 Metal sampling tube, duct widths 4' to 8'.<br />

ST-10 Metal sampling tube, duct widths 8' to 12'.<br />

RA400Z Remote annunciator alarm LED.<br />

M02-04-00 Test magnet.<br />

RTS451 Remote test station. Mounts in single-gang<br />

box. Includes red alarm LED and magnet test<br />

switch (separate 24 VDC/VAC is required).<br />

MOD400R Sensitivity test kit.<br />

CRT-400 Ionization cover removal tool.<br />