Data Sheet df-51096.pdf - Fire-Lite Alarms
Data Sheet df-51096.pdf - Fire-Lite Alarms
Data Sheet df-51096.pdf - Fire-Lite Alarms
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
GENERAL<br />
HVAC systems supply conditioned air to virtually every area<br />
of a building. Smoke introduced into an air recirculation<br />
system is distributed to occupied areas of a building. The<br />
System Sensor DH400 Series Duct Detector Housing is<br />
designed to sample air currents passing through a duct,<br />
allowing early detection of a developing fire. When sufficient<br />
smoke is sensed, an alarm signal is initiated at the<br />
fire alarm panel monitoring the detector, and appropriate<br />
action can be taken to shut off fans and blowers, change<br />
over air handling systems, etc. This can prevent the rapid<br />
distribution or isolation of toxic smoke and fire gases<br />
throughout the areas served by the duct system.<br />
The System Sensor DH400 duct detector system is easy<br />
to install and maintain.<br />
NOTE: The System Sensor DH400 Duct Detector Housing<br />
is supplied with either the 1451DH Ionization Sensor<br />
(DH400I) or the 2451 Photoelectric Sensor (DH400P).<br />
FEATURES<br />
12/24 VDC operation.<br />
Accommodates ionization or photoelectric heads.<br />
Simple change-out of detectors heads; twist-in, twist-out.<br />
Powered output for remote LED.<br />
Air velocity rating from 500 to 4,000 feet (152.4 to 1219.2<br />
meters) per minute.<br />
UL 268A listed to two-wire control panels.<br />
Clear polycarbonate cover for convenient visual inspection<br />
of sampling tube filters.<br />
Rugged Noryl® housing (mounting portion).<br />
Remote test station option.<br />
Easy and quick mounting to round or rectangular ducts<br />
from 1' to 12' (0.6 to 3.66 meters) wide.<br />
Three-year limited warranty.<br />
APPLICATIONS<br />
Duct smoke detectors have specific limitations.<br />
Duct detectors are:<br />
NOT a substitute for open area smoke detectors.<br />
NOT a substitute for early warning detection.<br />
NOT a replacement for a building’s regular fire detection<br />
system.<br />
System Sensor duct detector “Applications and Installation<br />
Instructions” should be used for reference, as well as<br />
“Guide for Proper Use of System Smoke Detectors” (I56-<br />
407-000). Call <strong>Fire</strong> <strong>Lite</strong> for information.<br />
June 18, 1998<br />
DH400 Series<br />
2-Wire Duct Detector Housings for<br />
Ionization and Photoelectric Sensors<br />
S911<br />
This document is not intended to be used for installation purposes. We try to keep our product<br />
information up-to-date and accurate. We cannot cover all specific applications or anticipate all<br />
requirements. All specifications are subject to change without notice. For more information,<br />
contact <strong>Fire</strong>•<strong>Lite</strong> <strong>Alarms</strong>, One <strong>Fire</strong>-<strong>Lite</strong> Place, Northford, Connecticut 06472. Phone: (800) 627-<br />
3473, Toll Free FAX: (877) 699-4105, FAX Back:(888) 388-3299<br />
WEB: www.firelite.com<br />
Section: Conventional Initiating Devices<br />
CS308<br />
MEA<br />
427-91-E 0V3A0.AY<br />
California<br />
State <strong>Fire</strong><br />
Marshal<br />
F-575<br />
3240-1209:155<br />
DH400 Series Duct Detector Housing<br />
CONSTRUCTION AND INSTALLATION<br />
The twist-in, twist-out detector and base allow the removal<br />
of detectors easily and quickly for cleaning and maintenance.<br />
In addition, detector heads can be changed to fit<br />
the application without removing the duct housing. The<br />
DH400 comes with built-in exhaust tube. Sampling tubes<br />
are available to fit ducts from 1 to 12 feet (0.6 to 3.66 meters)<br />
wide.<br />
SPECIFICATIONS<br />
DIMENSIONS: Width: 14-1/2" (36.83 cm). Height: 5"<br />
(12.70 cm). Depth (installed): 4" (10.16 cm).<br />
Weight: 4 lbs. (1.814 kg.).<br />
OPERATING RANGES: Temperature: 0°C to 49°C (32°F<br />
to 120°F). Humidity: 10% to 93% relative humidity.<br />
Air duct velocity: 500' (152.4 m) to 4,000' (1219.2 m) per<br />
minute.<br />
Reset time: 0.3 seconds (maximum).<br />
UL listed to 268A.<br />
DF-51096 — Page 1 of 2
ELECTRICAL RATINGS<br />
(includes base and detector)<br />
System voltage: 12/24 VDC.<br />
Maximum ripple voltage: 4 volts peak to peak.<br />
Start-up capacitance: 0.02 µF maximum.<br />
Standby ratings: 8.5 VDC minimum, 35 VDC maximum,<br />
120 µA maximum.<br />
Alarm ratings: 4.2 VDC minimum at 10 mA; 6.6 VDC maximum<br />
at 100 mA; alarm current must be limited to 100 mA<br />
or less by the control panel. If used, the RA400Z remote<br />
lamp operates within the specified alarm currents.<br />
Reset voltage: 2.5 VDC minimum.<br />
Reset time: 0.3 seconds maximum.<br />
INLET TUBE SELECTION<br />
Outside Duct Width Inlet Tube Required*<br />
Up to 2 feet<br />
(0.6096 m)<br />
2 to 4 feet<br />
(0.6096 to 1.2192 m)<br />
4 to 8 feet<br />
(1.2192 to 2.4384 m)<br />
8 to 10 feet<br />
(2.4384 to 3.0480 m)<br />
*NOTE: Inlet tube is required and must be purchased<br />
separately. Order one inlet tube for each duct detector<br />
housing ordered.<br />
Page 2 of 2 — DF-51096<br />
ST-1.5<br />
ST-3<br />
ST-5<br />
ST-10<br />
PRODUCT LINE INFORMATION<br />
Model Description<br />
DH400I Duct detector housing with ionization smoke<br />
detector.<br />
1451DH Replacement ionization smoke detector head.<br />
DH400P Duct detector housing with photoelectric<br />
smoke detector.<br />
2451 Replacement photoelectric smoke detector<br />
head.<br />
ST-1.5 Metal sampling tube, duct widths 1' to 2' (see<br />
table at left for metric lengths).<br />
ST-3 Metal sampling tube, duct widths 2' to 4'.<br />
ST-5 Metal sampling tube, duct widths 4' to 8'.<br />
ST-10 Metal sampling tube, duct widths 8' to 12'.<br />
RA400Z Remote annunciator alarm LED.<br />
M02-04-00 Test magnet.<br />
RTS451 Remote test station. Mounts in single-gang<br />
box. Includes red alarm LED and magnet test<br />
switch (separate 24 VDC/VAC is required).<br />
MOD400R Sensitivity test kit.<br />
CRT-400 Ionization cover removal tool.<br />
The RTS451<br />
The RA400Z