25.10.2012 Views

SERVICE TIP DF1 to DH+ Passthru using WinLinx or RSLinx

SERVICE TIP DF1 to DH+ Passthru using WinLinx or RSLinx

SERVICE TIP DF1 to DH+ Passthru using WinLinx or RSLinx

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>SERVICE</strong> <strong>TIP</strong><br />

<strong>DF1</strong> <strong>to</strong> <strong>DH+</strong> <strong>Passthru</strong> <strong>using</strong> <strong>WinLinx</strong> <strong>or</strong> <strong>RSLinx</strong><br />

SLC 5/04 process<strong>or</strong>s (OS401 and greater) supp<strong>or</strong>t <strong>DF1</strong> <strong>to</strong> <strong>DH+</strong> <strong>Passthru</strong>. With this feature, you can connect <strong>to</strong> a<br />

5/04 process<strong>or</strong> through Channel 0 <strong>using</strong> the <strong>DF1</strong> pro<strong>to</strong>col and access any node on the <strong>DH+</strong> netw<strong>or</strong>k, regardless<br />

of the baud rate of the <strong>DH+</strong> netw<strong>or</strong>k. It is also possible <strong>to</strong> connect a modem <strong>to</strong> Channel 0 and connect <strong>to</strong> any<br />

node on the <strong>DH+</strong> netw<strong>or</strong>k via modems.<br />

At this time only PanelView devices at FRN 3.3 <strong>or</strong> higher can be accessed <strong>using</strong> the SLC 5/04 passthru.<br />

Pre FRN 3.3 PanelViews do not recognize PCCC messaging which is the pro<strong>to</strong>col used on the <strong>DH+</strong> side<br />

of the SLC. An alternate bridge solution would be a 1770-KF2. The cus<strong>to</strong>mer should consult their local<br />

distribu<strong>to</strong>r f<strong>or</strong> other hardware, serial <strong>to</strong> <strong>DH+</strong> bridge, solutions <strong>or</strong> firmware upgrades.<br />

To use this functionality with the RSLogix 500 software, you need <strong>to</strong> use the following procedure:<br />

PROCESSOR SETTINGS:<br />

RSLogix500<br />

1) Configure Channel 0 of the 5/04 process<strong>or</strong> f<strong>or</strong> System Mode <strong>using</strong> Full-Duplex. This can be done by<br />

accessing the Channel Configuration Window and choosing the appropriate settings.<br />

**Note the <strong>Passthru</strong> Link ID setting f<strong>or</strong> Channel 1 (which is 2) and Channel 0 (which is 1). If channel’s 1 and 0<br />

have the same link ID’s then <strong>RSLinx</strong>/RSWho will not see through <strong>to</strong> the <strong>DH+</strong> netw<strong>or</strong>k.


2) You must then access the Chan 0 Tab on the Process<strong>or</strong> Status File and disable the DH485 <strong>to</strong> <strong>DH+</strong><br />

<strong>Passthru</strong> and enable <strong>DF1</strong> <strong>to</strong> <strong>DH+</strong> <strong>Passthru</strong> by setting both S:34/0 AND S:34/5 high. Note: If you want <strong>to</strong><br />

view active <strong>DH+</strong> nodes in the 5/04 status table, S:34/1 must also be set.


The above settings must then be downloaded <strong>to</strong> the process<strong>or</strong> <strong>using</strong> either Winlinx <strong>or</strong> <strong>RSLinx</strong>. Once the program<br />

has been downloaded, comms drivers must be altered as detailed below <strong>to</strong> see the entire <strong>DH+</strong> netw<strong>or</strong>k.<br />

Also note that the driver verification in Winlinx and Au<strong>to</strong>-Configure in <strong>RSLinx</strong> will no longer function c<strong>or</strong>rectly<br />

since <strong>DF1</strong> packets are being passed through Chan 1. Both functions will still determine the baud rate, but<br />

acknowledgements will no longer be received ca<strong>using</strong> the err<strong>or</strong> checking <strong>to</strong> fail.<br />

COMMUNICATION SETTINGS:<br />

<strong>WinLinx</strong><br />

The uLogic/KF3/CH0 driver was initially used <strong>to</strong> download the project <strong>to</strong> the 5/04. This driver must be deleted<br />

from Winlinx and the KF2/KE driver must be used instead. Be sure <strong>to</strong> set the c<strong>or</strong>rect baud rate and turn on the<br />

Don’t Verify Settings radio but<strong>to</strong>n. Click OK <strong>to</strong> accept the driver changes. The SuperWho screen will poll address<br />

1-77 and display any active <strong>DH+</strong> nodes.<br />

<strong>RSLinx</strong> v1.7<br />

To download the program, recall that the Device Type option was initially set <strong>to</strong> SLC-CH0. Change this <strong>to</strong><br />

KF2/KE and click on OK.


Select Communications > SuperWho and ‘right-click’ anywhere inside the Who screen and choose Configure<br />

SuperWho. In the dialog box, change the Station Update Mode from Graphical (default) <strong>to</strong> N<strong>or</strong>mal and click<br />

OK. The resulting Who screen will begin polling from node 1 thru 77 octal and display all devices connected<br />

<strong>to</strong> the <strong>DH+</strong> netw<strong>or</strong>k.


Remember, the RSLogix500 Who configuration is separate from the <strong>RSLinx</strong> Who configuration. Be sure that<br />

the N<strong>or</strong>mal mode is chosen in both configurations.<br />

Note: <strong>RSLinx</strong> 1.7 requires that one of the nodes on the <strong>DH+</strong> netw<strong>or</strong>k be set <strong>to</strong> station 1. If none of the nodes are<br />

set <strong>to</strong> 1 nothing will appear in the SuperWho. This is not a requirement f<strong>or</strong> <strong>RSLinx</strong> revision 2.1.<br />

<strong>RSLinx</strong> v2.0<br />

Once the program has been downloaded, in the driver configuration dialog, change the Device Type <strong>to</strong><br />

1770-KF2/1785-KE and click OK. Click Close <strong>to</strong> save the change. If Au<strong>to</strong>browsing is enabled, the RSWho will<br />

au<strong>to</strong>matically poll the <strong>DH+</strong> netw<strong>or</strong>k <strong>using</strong> your AB_<strong>DF1</strong> driver.<br />

Note: <strong>RSLinx</strong> 2.0 requires that one of the nodes on the <strong>DH+</strong> netw<strong>or</strong>k be set <strong>to</strong> station 1. If none of the<br />

nodes are set <strong>to</strong> 1 nothing will appear in the RSWho. This is not a requirement f<strong>or</strong> <strong>RSLinx</strong> revision 2.1<br />

(<strong>or</strong> higher).

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!