CM-B-UV - Halton Company
CM-B-UV - Halton Company
CM-B-UV - Halton Company
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Reactocell Exhaust Air Volumes &<br />
Collar Sizing Data Chart<br />
200 cfm/ft<br />
(0.094 m3/s per 305mm)<br />
HOOD SIZE<br />
3’-6” - 5’-0”<br />
1067mm - 1524mm<br />
DUCT COLLAR<br />
10” (254mm) x _____<br />
6” (152mm)<br />
CFM<br />
(m 3 /s)<br />
700<br />
(0.33)<br />
300 cfm/ft<br />
(.142 m3/s per 305mm)<br />
HOOD SIZE<br />
3’-6” - 5’-0”<br />
1067mm - 1524mm<br />
DUCT COLLAR<br />
10” (254mm) x _____<br />
10” (254mm)<br />
CFM<br />
(m 3 /s)<br />
1050<br />
(0.496)<br />
20/<strong>CM</strong>-B-<strong>UV</strong>/XXXX/0107/EN<br />
5’-6” to 6’-6”<br />
1676mm - 1981mm<br />
10” (254mm)<br />
1100<br />
(0.519)<br />
5’-6” to 6’-6”<br />
1676mm - 1981mm<br />
16” (406mm)<br />
1650<br />
(0.779)<br />
7’-0” to 8’-6”<br />
2134mm - 2591mm<br />
2 @ 6” (152mm)<br />
1400<br />
(0.66)<br />
7’-0” to 8’-6”<br />
2134mm - 2591mm<br />
2 @ 10” (254mm)<br />
2100<br />
(0.991)<br />
9’-0” to 10’-6”<br />
2743mm - 3200mm<br />
1 @ 6” (152mm)<br />
& 1 @ 10” (254mm)<br />
1800<br />
(1.038)<br />
9’-0” to 10’-6”<br />
2743mm - 3200mm<br />
1 @ 10” (254mm)<br />
& 1 @ 16” (406mm)<br />
2700<br />
(1.274)<br />
11’-0” to 12’-0”<br />
3353mm - 3658mm<br />
2 @ 10” (254mm)<br />
2200<br />
(1.038)<br />
11’-0” to 12’-0”<br />
3353mm - 3658mm<br />
2 @ 16” (406mm)<br />
3300<br />
(1.557)<br />
12’-6” to 14’-0”<br />
3810mm - 4267mm<br />
2 @ 6” (152mm)<br />
& 1 @ 10” (254mm)<br />
2500<br />
(1.18)<br />
12’-6” to 14’-0”<br />
3810mm - 4267mm<br />
2 @ 10” (254mm)<br />
& 1 @ 16” (406mm)<br />
3750<br />
(1.77)<br />
14’-6” to 16’-0”<br />
4420mm - 4877mm<br />
1 @ 6” (152mm)<br />
& 2 @ 10” (254mm)<br />
2900<br />
(1.369)<br />
14’-6” to 16’-0”<br />
4420mm - 4877mm<br />
1 @ 10” (254mm)<br />
& 2 @ 16” (406mm)<br />
4350<br />
(2.053<br />
250 cfm/ft<br />
(.118 m3/s per 305mm)<br />
350 cfm/ft<br />
(.165 m3/s per 305mm)<br />
HOOD SIZE<br />
DUCT COLLAR<br />
10” (254mm) x _____<br />
CFM<br />
(m 3 /s)<br />
HOOD SIZE<br />
DUCT COLLAR<br />
10” (254mm) x _____<br />
CFM<br />
(m 3 /s)<br />
3’-6” - 5’-0”<br />
1067mm - 1524mm<br />
8” (203mm)<br />
875<br />
(0.4130)<br />
3’-6” - 5’-0”<br />
1067mm - 1524mm<br />
12” (305mm)<br />
1225<br />
(0.578)<br />
5’-6” to 6’-6”<br />
1676mm - 1981mm<br />
12” (305mm)<br />
1375<br />
(0.649)<br />
5’-6” to 6’-6”<br />
1676mm - 1981mm<br />
18” (457mm)<br />
1925<br />
(0.909)<br />
7’-0” to 8’-6”<br />
2134mm - 2591mm<br />
2 @ 8” (203mm)<br />
1750<br />
(0.826)<br />
7’-0” to 8’-6”<br />
2134mm - 2591mm<br />
2 @ 12” (305mm)<br />
2450<br />
(1.156)<br />
9’-0” to 10’-6”<br />
2743mm - 3200mm<br />
1 @ 8” (203mm)<br />
& 1 @ 12” (305mm)<br />
2250<br />
(1.062)<br />
9’-0” to 10’-6”<br />
2743mm - 3200mm<br />
1 @ 12” (305mm)<br />
& 1 @ 18” (457mm)<br />
3150<br />
(1.487)<br />
11’-0” to 12’-0”<br />
3353mm - 3658mm<br />
2 @ 12” (305mm)<br />
2750<br />
(1.298)<br />
11’-0” to 12’-0”<br />
3353mm - 3658mm<br />
2 @ 18” (457mm)<br />
3850<br />
(1.817)<br />
12’-6” to 14’-0”<br />
3810mm - 4267mm<br />
2 @ 8” (203mm)<br />
& 1 @ 12” (305mm)<br />
3125<br />
(1.475)<br />
12’-6” to 14’-0”<br />
3810mm - 4267mm<br />
2 @ 12” (305mm)<br />
& 1 @ 18” (457mm)<br />
4375<br />
(2.065)<br />
14’-6” to 16’-0”<br />
4420mm - 4877mm<br />
1 @ 8” (203mm)<br />
& 2 @ 12” (305mm)<br />
3625<br />
(1.711)<br />
14’-6” to 16’-0”<br />
4420mm - 4877mm<br />
1 @ 12” (305mm)<br />
& 2 @18” (457mm)<br />
5075<br />
(2.395)<br />
Note: For hoods with multiple collars please contact the factory to confirm<br />
location. Please contact factory to confirm static pressure.<br />
Exhaust Hood Static Pressure Chart<br />
Exhaust Air Volumes<br />
150 cfm/ft<br />
(0.071 m 3 /s per 305mm)<br />
200 cfm/ft<br />
(0.094 m 3 /s per 305mm)<br />
250 cfm/ft<br />
(.118 m 3 /s per 305mm)<br />
300 cfm/ft<br />
(.142 m 3 /s per 305mm)<br />
350 cfm/ft<br />
(.165 m 3 /s per 305mm)<br />
Static Pressure<br />
0.5” (.125kPa)<br />
0.75” (.187kPa)<br />
1.0” (.248kPa)<br />
1.35” (.336kPa)<br />
1.75” (.436kPa)<br />
Ventilator exhaust air volume requirements depend on type of equipment,<br />
model of ventilator, location of ventilator in relation to adjacent walls and the<br />
make-up air velocity and balance within the cooking area. Each kitchen’s<br />
air system must becalculated individually and engineerd to meet these<br />
conditions. It is essential that all air, ventilator and cooking equipment<br />
factors be established and co-ordinated by the design team to achieve proper<br />
ventilator exhausting of cooking equipment. Contact <strong>Halton</strong> for assistance<br />
to determine proper cooking equipment and ventilator exhaust air volumes.<br />
EXHAUST AIR VOLUME AND DUCT COLLAR SIZE CHART.<br />
- Duct collar sized to move air at a minimum velocity of<br />
1500 fpm (7.62 m/s)<br />
SUPPLY AIR VOLUME AND DUCT COLLAR SIZE CHART.<br />
- Duct collar sized to move air at a minimum velocity of<br />
1000 fpm (5.08 m/s)<br />
Continuous product improvement is a <strong>Halton</strong> policy, therefore specifications and designs are subject to change without notice.<br />
<strong>CM</strong>-B-<strong>UV</strong> - <strong>UV</strong> Exhaust Hood<br />
4