06.01.2014 Views

Halton Cabin Unit HME

Halton Cabin Unit HME

Halton Cabin Unit HME

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>HME</strong> Single Duct <strong>Cabin</strong> <strong>Unit</strong><br />

Sound Attenuator And<br />

Balancing Box<br />

V3M02Y2009/<strong>Halton</strong> Marine reserves the right to alter products without a notice.<br />

The <strong>Halton</strong> <strong>HME</strong> can be used in various applications e.g.<br />

suites and pantries for distribution and sound attenuation.<br />

The unit works like a plenum box with a balancing and<br />

measurement module inside but also fulfils fire safety<br />

requirements as standard cabin unit. The supply volume<br />

flow rate is determined by using the measurement and<br />

adjustment device. The tubes and control spindle can be<br />

accessed through the unit’s outlet. Using the pressure<br />

difference readings between the measurement taps and<br />

the k coefficient, the corresponding volume flow rate can<br />

be calculated. Rotating the control spindle adjusts the<br />

volume flow rate until the desired setting is achieved.<br />

The tubes and spindle are then replaced in the plenum<br />

box. <strong>HME</strong> unit is designed for ductwork pressure up to<br />

200Pa.<br />

• Airflow adjustment with control spindle (MSM module)<br />

• Airflow measurement tubes<br />

• Applicable to B-0 and B-15 installations<br />

Additional features with reheat models<br />

• Reheating coil 400 or 800W<br />

• 90° safety switch with manual reset<br />

• Inbox temperature measurement (NTC sensor) with<br />

overheat limit to cut-off reheater power<br />

• Triac controlled reheating coil, adjustable heating power<br />

• Master/slave functionality: several slave cabin units can<br />

be connected to one master cabin unit. Total IC cable<br />

length from CP unit to last slave cabin unit can be 30 m.<br />

• All parameters can be preset at the factory or set onsite<br />

during commissioning by Palm handheld or laptop<br />

computer with LRC software (D03 model only)<br />

PART MATERIAL PART MATERIAL<br />

Casing Hot galvanised steel Reheat coil AISI 304<br />

Spigots Hot galvanised steel and EPDM rubber Cables Halogen free<br />

Insulation Mineral wool, s = 25 mm, MED approved Measurement and Body; aluminium, Plate; hot galvanized,<br />

I/O unit Aluminium / plastic / electronics adjustment module<br />

(MSM)<br />

Spindle; stainless steel, Tubes;<br />

polypropylene<br />

<strong>HME</strong> - Single Duct <strong>Cabin</strong> <strong>Unit</strong>, Sound Attenuator And Balancing Box<br />

105


GENERAL <strong>HME</strong> drawing<br />

ØD2<br />

H<br />

H/2<br />

40<br />

600<br />

480 60<br />

ØD1<br />

250<br />

500<br />

620<br />

60<br />

40<br />

300<br />

<strong>HME</strong> PRODUCT MODELS<br />

I/O unit (input/output unit, inside a cabin unit)<br />

• 230V power supply connector<br />

• Triac to control reheat coil<br />

• Connector for IC-cable<br />

• Connector for inbox temperature measurement (NTC<br />

sensor)<br />

• Fuses to protect I/O, CP and triac<br />

• Programming connector (model D03)<br />

• Two diagnose LEDs<br />

• Trimmers to set; Temperature offset, Overheating<br />

protection temperature and Max. reheat power<br />

(model K01)<br />

40<br />

DIMENSIONS TABLE<br />

<strong>HME</strong> Dimensions<br />

H ØD1 male/female ØD2 male/female<br />

<strong>HME</strong>-125 200 199/201 124/126<br />

<strong>HME</strong>-160 220 249/251 159/161<br />

Note:<br />

male connection: outer dimension<br />

female connection: inner dimensions<br />

IC-Cable ICx7 (Interconnection cable)<br />

• For CP-unit - I/O unit connection.<br />

• Prefabricated with plugs on both sides<br />

• CP side plug designed to be pulled through standard<br />

installation pipe<br />

• Halogen free and flame retarding<br />

• Standard length is 7 meters<br />

V3M02Y2009/<strong>Halton</strong> Marine reserves the right to alter products without a notice.<br />

CP unit (control panel)<br />

<strong>Halton</strong> Marine <strong>HME</strong> cabin units with reheater are<br />

available with two different control panels; push buttons<br />

and rotating knob. See picture on the right.<br />

CP unit features<br />

• <strong>Cabin</strong> temperature measurement<br />

• Two push buttons, 18 led bar (model D03), Knob<br />

adjusting (model K01)<br />

• Self diagnose function (model D03)<br />

• Internal fault LED<br />

• Connector for IC-cable<br />

• LED intensity control and auto dimming (model D03)<br />

• Connectors for infrared adapter or PCC cable<br />

(Programming cable) to set cabin parameters (model<br />

D03)<br />

• Programming connector (model D03)<br />

• Palm / laptop software for parameter setting (Palm<br />

handheld / laptop required)<br />

<strong>Halton</strong> IC-Cable<br />

Model D03<br />

Model K01<br />

<strong>Halton</strong> control panels D03 and K01 for <strong>HME</strong> cabin units<br />

<strong>HME</strong> - Single Duct <strong>Cabin</strong> <strong>Unit</strong>, Sound Attenuator And Balancing Box<br />

106


ACCESSORIES FOR <strong>HME</strong> CABIN UNITS<br />

MS-Cable MSx-7 (master-slave cable)<br />

• For master cabin unit - slave cabin unit/units<br />

connection<br />

• Prefabricated with plugs on both sides<br />

• Halogen free and flame retarding<br />

• Standard length is 7 meters<br />

LIA-1 Infrared adapter<br />

• For connection between Palm and CP-unit to set<br />

cabin parameters<br />

• One per Palm handheld needed<br />

PCC-cable (programming cable)<br />

• For connection between laptop and CP-unit to set<br />

cabin parameters<br />

• One per laptop needed<br />

Reheaters available<br />

• 800 W<br />

• 400 W<br />

Practical power level may be software adjusted cabin by cabin. Cable<br />

and power supply design has to be done according to maximum<br />

available heating power.<br />

Airflows for <strong>HME</strong> cabin unit with reheat coil<br />

Reheater Power<br />

(W)<br />

Minimum airflows<br />

<strong>HME</strong>-125<br />

Min. airflows (m 3 /h)<br />

<strong>HME</strong>-160<br />

400 100 100<br />

800 130 130<br />

V3M02Y2009/<strong>Halton</strong> Marine reserves the right to alter products without a notice.<br />

Network adapter<br />

• For LON or Ethernet network (D03)<br />

• Single and double models<br />

FUNCTION<br />

The power supply to CP-unit comes from I/O unit<br />

(installed in cabin unit) via interconnection cable.<br />

LRC-1 system will regulate room temperature regarding<br />

the temperature set point that is set with the CP-unit.<br />

When passenger demands for warmer temperature by<br />

using CP-unit, the controller activates the electric reheater<br />

inside the cabin unit. When the required temperature<br />

in the cabin is achieved, the reference is held until the<br />

temperature demand changes.<br />

Regulation Diagram with reheater<br />

Heating<br />

power<br />

100%<br />

0%<br />

Heating power<br />

Regulation deadband<br />

Set point<br />

Room temp<br />

Operating range for <strong>HME</strong><br />

<strong>HME</strong><br />

<strong>HME</strong>-125<br />

<strong>HME</strong>-160<br />

50 m 3 /h - 350 m 3 /h 50 m 3 /h - 500 m 3 /h<br />

<strong>HME</strong> - Single Duct <strong>Cabin</strong> <strong>Unit</strong>, Sound Attenuator And Balancing Box<br />

107


Performance data<br />

Sound levels, cabin sound absorption 4 dB(A)<br />

<strong>HME</strong>/A-125-200<br />

Ptot<br />

<strong>HME</strong>/A-160-250<br />

Ptot<br />

V3M02Y2009/<strong>Halton</strong> Marine reserves the right to alter products without a notice.<br />

<strong>HME</strong>/D-125-200<br />

<strong>HME</strong>/D-160-250<br />

Ptot<br />

Ptot<br />

Sound attenuation<br />

Sound attenuation (dB)<br />

<strong>HME</strong> 125 (600x500x200)<br />

f(Hz) 63 125 250 500 1000 2000 4000 8000<br />

DL(dB) 6,4 11,3 15,9 25,8 34,8 37,9 35,3 34,7<br />

DL: Sound attenuation not including end reflection<br />

Sound attenuation (dB)<br />

<strong>HME</strong> 160 (600x500x220)<br />

f(Hz) 63 125 250 500 1000 2000 4000 8000<br />

DL(dB) 7,2 7,2 17,2 26,7 36,4 40,7 38,5 34,3<br />

DL: Sound attenuation not including end reflection<br />

<strong>HME</strong> - Single Duct <strong>Cabin</strong> <strong>Unit</strong>, Sound Attenuator And Balancing Box<br />

108

Hooray! Your file is uploaded and ready to be published.