Halton Cabin Unit HME
Halton Cabin Unit HME
Halton Cabin Unit HME
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>HME</strong> Single Duct <strong>Cabin</strong> <strong>Unit</strong><br />
Sound Attenuator And<br />
Balancing Box<br />
V3M02Y2009/<strong>Halton</strong> Marine reserves the right to alter products without a notice.<br />
The <strong>Halton</strong> <strong>HME</strong> can be used in various applications e.g.<br />
suites and pantries for distribution and sound attenuation.<br />
The unit works like a plenum box with a balancing and<br />
measurement module inside but also fulfils fire safety<br />
requirements as standard cabin unit. The supply volume<br />
flow rate is determined by using the measurement and<br />
adjustment device. The tubes and control spindle can be<br />
accessed through the unit’s outlet. Using the pressure<br />
difference readings between the measurement taps and<br />
the k coefficient, the corresponding volume flow rate can<br />
be calculated. Rotating the control spindle adjusts the<br />
volume flow rate until the desired setting is achieved.<br />
The tubes and spindle are then replaced in the plenum<br />
box. <strong>HME</strong> unit is designed for ductwork pressure up to<br />
200Pa.<br />
• Airflow adjustment with control spindle (MSM module)<br />
• Airflow measurement tubes<br />
• Applicable to B-0 and B-15 installations<br />
Additional features with reheat models<br />
• Reheating coil 400 or 800W<br />
• 90° safety switch with manual reset<br />
• Inbox temperature measurement (NTC sensor) with<br />
overheat limit to cut-off reheater power<br />
• Triac controlled reheating coil, adjustable heating power<br />
• Master/slave functionality: several slave cabin units can<br />
be connected to one master cabin unit. Total IC cable<br />
length from CP unit to last slave cabin unit can be 30 m.<br />
• All parameters can be preset at the factory or set onsite<br />
during commissioning by Palm handheld or laptop<br />
computer with LRC software (D03 model only)<br />
PART MATERIAL PART MATERIAL<br />
Casing Hot galvanised steel Reheat coil AISI 304<br />
Spigots Hot galvanised steel and EPDM rubber Cables Halogen free<br />
Insulation Mineral wool, s = 25 mm, MED approved Measurement and Body; aluminium, Plate; hot galvanized,<br />
I/O unit Aluminium / plastic / electronics adjustment module<br />
(MSM)<br />
Spindle; stainless steel, Tubes;<br />
polypropylene<br />
<strong>HME</strong> - Single Duct <strong>Cabin</strong> <strong>Unit</strong>, Sound Attenuator And Balancing Box<br />
105
GENERAL <strong>HME</strong> drawing<br />
ØD2<br />
H<br />
H/2<br />
40<br />
600<br />
480 60<br />
ØD1<br />
250<br />
500<br />
620<br />
60<br />
40<br />
300<br />
<strong>HME</strong> PRODUCT MODELS<br />
I/O unit (input/output unit, inside a cabin unit)<br />
• 230V power supply connector<br />
• Triac to control reheat coil<br />
• Connector for IC-cable<br />
• Connector for inbox temperature measurement (NTC<br />
sensor)<br />
• Fuses to protect I/O, CP and triac<br />
• Programming connector (model D03)<br />
• Two diagnose LEDs<br />
• Trimmers to set; Temperature offset, Overheating<br />
protection temperature and Max. reheat power<br />
(model K01)<br />
40<br />
DIMENSIONS TABLE<br />
<strong>HME</strong> Dimensions<br />
H ØD1 male/female ØD2 male/female<br />
<strong>HME</strong>-125 200 199/201 124/126<br />
<strong>HME</strong>-160 220 249/251 159/161<br />
Note:<br />
male connection: outer dimension<br />
female connection: inner dimensions<br />
IC-Cable ICx7 (Interconnection cable)<br />
• For CP-unit - I/O unit connection.<br />
• Prefabricated with plugs on both sides<br />
• CP side plug designed to be pulled through standard<br />
installation pipe<br />
• Halogen free and flame retarding<br />
• Standard length is 7 meters<br />
V3M02Y2009/<strong>Halton</strong> Marine reserves the right to alter products without a notice.<br />
CP unit (control panel)<br />
<strong>Halton</strong> Marine <strong>HME</strong> cabin units with reheater are<br />
available with two different control panels; push buttons<br />
and rotating knob. See picture on the right.<br />
CP unit features<br />
• <strong>Cabin</strong> temperature measurement<br />
• Two push buttons, 18 led bar (model D03), Knob<br />
adjusting (model K01)<br />
• Self diagnose function (model D03)<br />
• Internal fault LED<br />
• Connector for IC-cable<br />
• LED intensity control and auto dimming (model D03)<br />
• Connectors for infrared adapter or PCC cable<br />
(Programming cable) to set cabin parameters (model<br />
D03)<br />
• Programming connector (model D03)<br />
• Palm / laptop software for parameter setting (Palm<br />
handheld / laptop required)<br />
<strong>Halton</strong> IC-Cable<br />
Model D03<br />
Model K01<br />
<strong>Halton</strong> control panels D03 and K01 for <strong>HME</strong> cabin units<br />
<strong>HME</strong> - Single Duct <strong>Cabin</strong> <strong>Unit</strong>, Sound Attenuator And Balancing Box<br />
106
ACCESSORIES FOR <strong>HME</strong> CABIN UNITS<br />
MS-Cable MSx-7 (master-slave cable)<br />
• For master cabin unit - slave cabin unit/units<br />
connection<br />
• Prefabricated with plugs on both sides<br />
• Halogen free and flame retarding<br />
• Standard length is 7 meters<br />
LIA-1 Infrared adapter<br />
• For connection between Palm and CP-unit to set<br />
cabin parameters<br />
• One per Palm handheld needed<br />
PCC-cable (programming cable)<br />
• For connection between laptop and CP-unit to set<br />
cabin parameters<br />
• One per laptop needed<br />
Reheaters available<br />
• 800 W<br />
• 400 W<br />
Practical power level may be software adjusted cabin by cabin. Cable<br />
and power supply design has to be done according to maximum<br />
available heating power.<br />
Airflows for <strong>HME</strong> cabin unit with reheat coil<br />
Reheater Power<br />
(W)<br />
Minimum airflows<br />
<strong>HME</strong>-125<br />
Min. airflows (m 3 /h)<br />
<strong>HME</strong>-160<br />
400 100 100<br />
800 130 130<br />
V3M02Y2009/<strong>Halton</strong> Marine reserves the right to alter products without a notice.<br />
Network adapter<br />
• For LON or Ethernet network (D03)<br />
• Single and double models<br />
FUNCTION<br />
The power supply to CP-unit comes from I/O unit<br />
(installed in cabin unit) via interconnection cable.<br />
LRC-1 system will regulate room temperature regarding<br />
the temperature set point that is set with the CP-unit.<br />
When passenger demands for warmer temperature by<br />
using CP-unit, the controller activates the electric reheater<br />
inside the cabin unit. When the required temperature<br />
in the cabin is achieved, the reference is held until the<br />
temperature demand changes.<br />
Regulation Diagram with reheater<br />
Heating<br />
power<br />
100%<br />
0%<br />
Heating power<br />
Regulation deadband<br />
Set point<br />
Room temp<br />
Operating range for <strong>HME</strong><br />
<strong>HME</strong><br />
<strong>HME</strong>-125<br />
<strong>HME</strong>-160<br />
50 m 3 /h - 350 m 3 /h 50 m 3 /h - 500 m 3 /h<br />
<strong>HME</strong> - Single Duct <strong>Cabin</strong> <strong>Unit</strong>, Sound Attenuator And Balancing Box<br />
107
Performance data<br />
Sound levels, cabin sound absorption 4 dB(A)<br />
<strong>HME</strong>/A-125-200<br />
Ptot<br />
<strong>HME</strong>/A-160-250<br />
Ptot<br />
V3M02Y2009/<strong>Halton</strong> Marine reserves the right to alter products without a notice.<br />
<strong>HME</strong>/D-125-200<br />
<strong>HME</strong>/D-160-250<br />
Ptot<br />
Ptot<br />
Sound attenuation<br />
Sound attenuation (dB)<br />
<strong>HME</strong> 125 (600x500x200)<br />
f(Hz) 63 125 250 500 1000 2000 4000 8000<br />
DL(dB) 6,4 11,3 15,9 25,8 34,8 37,9 35,3 34,7<br />
DL: Sound attenuation not including end reflection<br />
Sound attenuation (dB)<br />
<strong>HME</strong> 160 (600x500x220)<br />
f(Hz) 63 125 250 500 1000 2000 4000 8000<br />
DL(dB) 7,2 7,2 17,2 26,7 36,4 40,7 38,5 34,3<br />
DL: Sound attenuation not including end reflection<br />
<strong>HME</strong> - Single Duct <strong>Cabin</strong> <strong>Unit</strong>, Sound Attenuator And Balancing Box<br />
108