High Voltage<br />

Denmark - Sweden: The Sequence of Events<br />

2<br />

23.9.03<br />

3<br />

Oskarshamm<br />

1<br />

1<br />

2<br />

3<br />

12.30 Outage of NPP<br />

1200 MW (faulty Valve)<br />

12.35 Double Busbar Fault<br />

Outage of 2 NPP 1800 MW<br />

The Consequences: <strong>Power</strong> Oscillations, Load-Shedding,<br />

Voltage Collapse - Restoration of the System at 19.05<br />

Source: EURELECTRIC External Reports 2003<br />