Dual-Channel <strong>Safety</strong> <strong>Barriers</strong> Polarity: - / -<br />

Series 9002/00<br />

Dual-Channel <strong>Safety</strong> <strong>Barriers</strong> Polarity: - / -<br />

Safe area<br />

-ve<br />

Control room<br />

equipment<br />

0V<br />

-ve<br />

U N<br />

Hazardous area<br />

-ve<br />

Intrinsically safe<br />

field device(s)<br />

-ve<br />

• Allows the connection of regulated<br />

power supplies, U N<br />

• Approved for installation in Division 2<br />

and Zone 2<br />

/PA<br />

05822E02<br />

Selection Table<br />

Channel U N R min R max I max <strong>Safety</strong> Data Order number<br />

U o I o P o IIC IIB<br />

1<br />

2<br />

1+2<br />

1<br />

2<br />

1+2<br />

1<br />

2<br />

1+2<br />

L o C o L o C o<br />

V O O mA V mA mW mH mF mH mF<br />

9<br />

9<br />

- -<br />

22.5<br />

17.5<br />

- -<br />

25<br />

25<br />

- -<br />

1043<br />

1043<br />

- -<br />

321<br />

416<br />

- -<br />

321<br />

321<br />

- -<br />

1156<br />

1156<br />

- -<br />

358<br />

463<br />

- -<br />

358<br />

358<br />

- -<br />

7.7<br />

7.7<br />

- -<br />

62<br />

37<br />

- -<br />

69<br />

69<br />

- -<br />

12<br />

12<br />

12<br />

26<br />

20<br />

26<br />

28<br />

28<br />

28<br />

12<br />

12<br />

24<br />

87<br />

51<br />

138<br />

93<br />

93<br />

186<br />

40<br />

40<br />

70<br />

570<br />

260<br />

850<br />

650<br />

650<br />

1300<br />

240<br />

240<br />

63<br />

2.7<br />

14<br />

0.81<br />

2<br />

2<br />

- -<br />

1.41<br />

1.41<br />

1.1<br />

0.099<br />

0.22<br />

0.087<br />

0.083<br />

0.083<br />

- -<br />

850<br />

850<br />

230<br />

15.4<br />

54<br />

5.1<br />

13<br />

13<br />

2.8<br />

9<br />

9<br />

7.1<br />

0.77<br />

1.41<br />

0.67<br />

0.65<br />

0.65<br />

0.551<br />

9002/00-120-024-001<br />

9002/00-260-138-001<br />

9002/00-280-186-001<br />

Note<br />

Application example see General - Standard Applications<br />

Functional and Maximum <strong>Safety</strong> Values<br />

U N Nominal voltage I max Maximum current<br />

through the safety barrier<br />

R min<br />

R max<br />

Minimum resistance<br />

of the safety barrier<br />

Maximum resistance<br />

of the safety barrier<br />

P o<br />

Maximum power<br />

U o Maximum voltage L o Maximum permissible<br />

external inductance<br />

I o Maximum current C o Maximum permissible<br />

external capacity<br />