Dual-Channel <strong>Safety</strong> <strong>Barriers</strong> Polarity: + / -<br />

Series 9002/10<br />

2<br />

Dual-Channel <strong>Safety</strong> <strong>Barriers</strong> Polarity: + / -<br />

Safe area<br />

Control room<br />

equipment<br />

0V<br />

+ve<br />

-ve<br />

U N<br />

Hazardous area<br />

+ve<br />

Intrinsically safe<br />

field device(s)<br />

-ve<br />

• Application specific for use with<br />

strain gauge load cells<br />

• One positive polarity channel and<br />

one negative polarity channel in one unit<br />

• Approved for installation in Division 2<br />

and Zone 2<br />

/PA<br />

05821E02<br />

Selection Table<br />

Channel U N R min R max I max <strong>Safety</strong> Data Order number<br />

U o I o P o IIC IIB<br />

1<br />

2<br />

1+2<br />

1<br />

2<br />

1+2<br />

L o C o L o C o<br />

V O O mA V mA mW mH mF mH mF<br />

6<br />

6<br />

- -<br />

6<br />

6<br />

- -<br />

490<br />

490<br />

- -<br />

42<br />

42<br />

- -<br />

543<br />

543<br />

- -<br />

49<br />

49<br />

- -<br />

11<br />

11<br />

- -<br />

122<br />

122<br />

- -<br />

9.3<br />

9.3<br />

18.7<br />

9.3<br />

9.3<br />

18.7<br />

20<br />

20<br />

20<br />

270<br />

270<br />

270<br />

50<br />

50<br />

90<br />

630<br />

630<br />

1260<br />

90<br />

90<br />

90<br />

0.23<br />

0.23<br />

0.23<br />

3.9<br />

3.9<br />

0.27<br />

3.9<br />

3.9<br />

0.27<br />

330<br />

330<br />

330<br />

2.2<br />

2.2<br />

2.2<br />

29<br />

29<br />

1.64<br />

29<br />

29<br />

1.64<br />

9002/10-187-020-001<br />

9002/10-187-270-001<br />

Note<br />

Application example see General - Standard Applications<br />

Functional and Maximum <strong>Safety</strong> Values<br />

U N Nominal voltage I max Maximum current<br />

through the safety barrier<br />

R min<br />

R max<br />

Minimum resistance<br />

of the safety barrier<br />

Maximum resistance<br />

of the safety barrier<br />

P o<br />

Maximum power<br />

U o Maximum voltage L o Maximum permissible<br />

external inductance<br />

I o Maximum current C o Maximum permissible<br />

external capacity<br />

Automation 03.08.2010<br />