31.03.2014 Views

Z-TIO Host Communication Quick Instruction ... - rkc instrument inc.

Z-TIO Host Communication Quick Instruction ... - rkc instrument inc.

Z-TIO Host Communication Quick Instruction ... - rkc instrument inc.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Module Type Controller SRZ<br />

Temperature Control Module<br />

[for <strong>Host</strong> <strong>Communication</strong>]<br />

All Rights Reserved, Copyright © 2006, RKC INSTRUMENT INC.<br />

IMS01T02-E3<br />

Thank you for purchasing this RKC product. In order to achieve maximum performance and<br />

ensure proper operation of your new <strong>instrument</strong>, carefully read all the instructions in this<br />

manual. Please place this manual in a convenient location for easy reference.<br />

This manual describes the host communication, module address setting of the Z-<strong>TIO</strong><br />

module. For the address setting of any other module, refer to the <strong>Instruction</strong> Manual for the<br />

respective module. For detailed handling procedures and various function settings, please<br />

refer to separate SRZ <strong>Instruction</strong> Manual (IMS01T04 -E).<br />

The above manuals can be downloaded from our website:<br />

URL: http://www.<strong>rkc</strong>inst.com/english/manual_load.htm<br />

1. COMMUNICA<strong>TIO</strong>N SETTING<br />

Set communication setting before mounting and wiring of the Z-<strong>TIO</strong>.<br />

CAU<strong>TIO</strong>N<br />

Do not separate the module mainframe from the base with the power turned on. If so,<br />

<strong>instrument</strong> failure may result.<br />

1.1 Module Address Setting<br />

Set an address for the module using a small blade screwdriver.<br />

Address setting switch<br />

Setting range: 0 to F [0 to 15: Decimal]<br />

Factory set value: 0<br />

• For Modbus, the value obtained by adding “1” to the set address<br />

corresponds to the address used for the actual program.<br />

• To avoid problems or malfunction, do not duplicate an address on the<br />

same communication line.<br />

1.2 Protocol Selections and <strong>Communication</strong> Speed Setting<br />

Use the DIP switch on the right side of module to select communication speed, data bit<br />

configuration and protocol. The data changes become valid when the power is turned on<br />

again or when changed to RUN/STOP.<br />

Right side view<br />

Module<br />

mainframe<br />

DIP switch<br />

(The above figure is for the terminal type. However, the switch positions are the same for the connector type.)<br />

1 2 <strong>Communication</strong> speed<br />

OFF OFF 4800 bps<br />

ON OFF 9600 bps<br />

OFF ON 19200 bps<br />

ON ON 38400 bps<br />

Factory set value: 19200 bps<br />

1 2 3 4 5 6 7 8<br />

OFF<br />

3 4 5 Data bit configuration<br />

OFF OFF OFF Data 7-bit, without parity, Stop 1-bit *<br />

ON OFF OFF Don't set this one<br />

OFF ON OFF Data 7-bit, Even parity, Stop 1-bit *<br />

ON ON OFF Data 7-bit, Odd parity, Stop 1-bit *<br />

OFF OFF ON Data 8-bit, without parity, Stop 1-bit<br />

ON OFF ON Don't set this one<br />

OFF ON ON Data 8-bit, Even parity, Stop 1-bit<br />

ON ON ON Data 8-bit, Odd parity, Stop 1-bit<br />

* When the Modbus communication protocol is selected, this setting becomes invalid.<br />

Factory set value: Data 8-bit, without parity, Stop 1-bit<br />

6 Protocol<br />

OFF<br />

ON<br />

Factory set value: RKC communication<br />

Z-<strong>TIO</strong><br />

RKC communication<br />

Modbus<br />

<strong>Host</strong> <strong>Communication</strong><br />

<strong>Quick</strong> <strong>Instruction</strong><br />

Manual<br />

• Switch No. 7 and 8 must be always OFF. Do not set to ON.<br />

• When two or more modules are connected on the same communication<br />

line, the DIP switch settings of all modules must be the same.<br />

ON<br />

ON<br />

2. CONNEC<strong>TIO</strong>N TO HOST COMPUTER<br />

! WARNING<br />

To prevent electric shock or <strong>instrument</strong> failure, turn off the<br />

power before connecting or disconnecting the <strong>instrument</strong> and<br />

peripheral equipment.<br />

Connect a termination resistor between the communication terminals (No.3<br />

and No. 4) of the module at the end of the communication line from the host<br />

computer.<br />

The cable must be provided by the customer.<br />

The Z-<strong>TIO</strong> has RS-485 communication terminals for RKC communication or Modbus/RTU<br />

communication protocol. <strong>Communication</strong> terminals are on the base side.<br />

• Connection to the RS-485 port of the host computer (master)<br />

Module type controller SRZ<br />

Z-<strong>TIO</strong> module<br />

(Slave)<br />

(−)<br />

(+)<br />

(−)<br />

(+)<br />

•<br />

•<br />

•<br />

T/R (A) 3<br />

T/R (B)<br />

4<br />

SG 5<br />

Z-<strong>TIO</strong> module<br />

(Slave)<br />

T/R (A) 3<br />

T/R (B)<br />

4<br />

SG 5<br />

RS-485<br />

Pair wire<br />

Shielded twisted<br />

Connected by pair wire<br />

the internal<br />

communication line<br />

R<br />

R<br />

<strong>Host</strong> computer (Master)<br />

T/R (A)<br />

T/R (B)<br />

Up to 16 Z-<strong>TIO</strong> modules can be connected.<br />

The maximum number of SRZ modules (<strong>inc</strong>luding other function modules) on the same communication line is 31.<br />

SG<br />

R: Termination resistor (Example: 120 Ω 1/2 W)<br />

• Connection to the RS-232C port of the host computer (master)<br />

Module type controller SRZ<br />

(−)<br />

(+)<br />

(−)<br />

(+)<br />

•<br />

•<br />

•<br />

Z-<strong>TIO</strong> module<br />

(Slave)<br />

T/R (A) 3<br />

T/R (B)<br />

4<br />

SG 5<br />

Z-<strong>TIO</strong> module<br />

(Slave)<br />

T/R (A) 3<br />

T/R (B)<br />

4<br />

SG 5<br />

RS-485<br />

Shielded twisted<br />

pair wire<br />

Connected by<br />

the internal<br />

communication line<br />

R<br />

Pair wire<br />

(−)<br />

(+)<br />

<strong>Host</strong> computer (Master)<br />

R<br />

T/R (A)<br />

T/R (B)<br />

SG<br />

RS-232C<br />

RS-232C/RS-485 converter *<br />

* When the host computer (master) uses<br />

Windows95/98/Me/NT/2000/XP, use a<br />

RS-232C/RS-485 converter with an<br />

automatic send/receive transfer function.<br />

Recommended RS-232C/RS-485 converter:<br />

R: Termination resistor<br />

CD485, CD485/Vmanufactured by Data Link,<br />

(Example: 120 Ω 1/2 W)<br />

Inc. or equivalent<br />

Up to 16 Z-<strong>TIO</strong> modules can be connected.<br />

The maximum number of SRZ modules (<strong>inc</strong>luding other function modules) on the same communication line is 31.<br />

• Connection to the USB of the host computer (master)<br />

Module type controller SRZ<br />

(−)<br />

(+)<br />

(−)<br />

(+)<br />

•<br />

•<br />

•<br />

(Base)<br />

3 4 5<br />

Z-<strong>TIO</strong> module<br />

(Slave)<br />

T/R (A) 3<br />

T/R (B)<br />

4<br />

SG 5<br />

Z-<strong>TIO</strong> module<br />

(Slave)<br />

T/R (A) 3<br />

T/R (B)<br />

4<br />

SG 5<br />

<strong>Communication</strong> terminals (RS-485)<br />

Terminal No. Signal name<br />

3 Send data/Receive data<br />

4 Send data/Receive data<br />

5<br />

Signal ground<br />

RS-485<br />

Pair wire<br />

Shielded twisted<br />

pair wire<br />

Connected by<br />

the internal<br />

communication line<br />

R<br />

<strong>Host</strong> computer (Master)<br />

1 SG<br />

2 T/R (A)<br />

3 T/R(B)<br />

4<br />

Unused<br />

5<br />

USB communication<br />

converter COM-K *<br />

Symbol<br />

T/R (A)<br />

T/R (B)<br />

SG<br />

Connected to USB port<br />

of a personal computer<br />

USB cable<br />

(COM-K<br />

accessory)<br />

Connected to<br />

USB connector<br />

* The termination resistor is built-in to<br />

the COM-K.<br />

R: Termination resistor<br />

(Example: 120 Ω 1/2 W)<br />

Up to 16 Z-<strong>TIO</strong> modules can be connected.<br />

The maximum number of SRZ modules (<strong>inc</strong>luding other function modules) on the same communication line is 31.<br />

3. COMMUNICA<strong>TIO</strong>N REQUIREMENTS<br />

• Processing times during data send/receive<br />

When the host computer is using either the polling or selecting procedure for communication,<br />

the following processing times are required for controller to send data:<br />

- Response wait time after controller sends BCC in polling procedure<br />

- Response wait time after controller sends ACK or NAK in selecting procedure<br />

RKC communication (Polling procedure)<br />

Procedure details<br />

Response send time after controller receives ENQ<br />

Response send time after controller receives ACK<br />

Response send time after controller receives NAK<br />

Response send time after controller sends BCC<br />

RKC communication (Selecting procedure)<br />

Procedure details<br />

Response send time after controller receives BCC<br />

Response wait time after controller sends ACK<br />

Response wait time after controller sends NAK<br />

Modbus<br />

Procedure details<br />

Read holding registers [03H]<br />

Response send time after the slave receives the query message<br />

Preset single register [06H]<br />

Response send time after the slave receives the query message<br />

Diagnostics (loopback test) [08H]<br />

Response send time after the slave receives the query message<br />

Preset multiple registers [10H]<br />

Response send time after the slave receives the query message<br />

• RS-485 (2-wire system) send/receive timing<br />

Time<br />

50 ms max.<br />

50 ms max.<br />

50 ms max.<br />

2 ms max.<br />

Time<br />

50 ms max.<br />

2 ms max.<br />

2 ms max.<br />

Time<br />

50 ms max.<br />

30 ms max.<br />

30 ms max.<br />

100 ms max.<br />

RS-485 communication is conducted through two wires, therefore the transmission and<br />

reception of data requires precise timing.<br />

Polling procedure<br />

<strong>Host</strong><br />

computer<br />

SRZ<br />

Send data Possible<br />

(Possible/Impossible) Impossible<br />

Sending status<br />

Send data Possible<br />

(Possible/Impossible) Impossible<br />

Sending status<br />

a: Response send time after the controller receives [ENQ] + Interval time<br />

b: Response send time after the controller sends BCC<br />

c: Response send time after the controller receives [ACK] + Interval time or<br />

Response send time after the controller receives [NAK] + Interval time<br />

Selecting procedure<br />

<strong>Host</strong><br />

computer<br />

Send data Possible<br />

(Possible/Impossible) Impossible<br />

Sending status<br />

E<br />

O<br />

T<br />

E<br />

A<br />

- - - - - N<br />

C or<br />

Q<br />

K<br />

a<br />

S<br />

TX<br />

S<br />

TX<br />

B<br />

CC<br />

or<br />

- - - - -<br />

- - - - -<br />

Send data Possible<br />

a b<br />

(Possible/Impossible) Impossible<br />

SRZ<br />

Sending status<br />

A N<br />

C AK<br />

K<br />

a: Response send time after the controller receives BCC + Interval time<br />

b: Response wait time after the controller sends ACK or Response wait time after the controller sends NAK<br />

To switch the host computer from transmission to reception, send data must be on<br />

line.<br />

The following processing times are requires for the controller to process data.<br />

- In Polling procedure, Response wait time after the controller sends BCC<br />

- In Selecting procedure, Response wait time after the controller sends ACK or NAK<br />

• Fail-safe<br />

A transmission error may occur with the transmission line disconnected, shorted or set to the<br />

high-impedance state. In order to prevent the above error, it is recommended that the<br />

fail-safe function be provided on the receiver side of the host computer. The fail-safe function<br />

can prevent a framing error from its occurrence by making the receiver output stable to the<br />

MARK (1) when the transmission line is in the high-impedance state.<br />

• Modbus data processing precautions<br />

• Data with decimal point is treated as data without decimal point on the Modbus protocol.<br />

• With Modbus protocol, the maximum number of channels per slave address is 4.<br />

• Do not write data to any address which is not described in a list of data maps.<br />

• If data range or address error occurs during data writing, the data written before error is in<br />

effect.<br />

• When communication data is sent to the controller that does not correctly match the<br />

connected module or selected functions on the modules, the data will be invalid. If the<br />

data is within a setting range, no error message is sent from the controller. The read data<br />

is “0”.<br />

• Send the next command message at time intervals of 24 bits after the master receives the<br />

response message.<br />

B<br />

CC<br />

b<br />

c<br />

N<br />

A<br />

K<br />

4. HOST COMMUNICA<strong>TIO</strong>N DATA MAP<br />

Explanation of items shown in the communication data maps are as follows.<br />

• Modbus register address (HEX: Hexadecimal DEC: Decimal)<br />

For a 4CH type, follow the chart exactly. For the 2CH type, the register<br />

addresses for Channel 3 and 4 are unused. For communication parameters for<br />

heat/cool control, the register addresses for Channel 2 and 4 are unused.<br />

Example: The register addresses of 0092 (HEX) to 0095 (HEX)<br />

CH# Address<br />

・<br />

・<br />

CH1 0092<br />

CH2 0093 (This address is unused with heat/cool control.)<br />

CH3 0094 (This address is unused with 2CH type.)<br />

CH4 0095 (This address is unused with heat/cool control or 2CH type.)<br />

・<br />

・<br />

• Digits<br />

The number of communication data digits in RKC communication<br />

• Attribute<br />

RO: Read only data (<strong>Host</strong> computer The controller)<br />

R/W: Read and Write data (<strong>Host</strong> computer The controller)<br />

• Data<br />

RKC communication<br />

Modbus<br />

ASCII code data (Example: 7 digits) 16-bit data<br />

Most significant<br />

digit<br />

…… Least significant b15 …………….…………………… b0<br />

digit<br />

Symbols used in MAP<br />

♣: Parameters only used for heat/cool control or position proportioning control,<br />

therefore data for CH2 and CH4 are unused.<br />

: Parameters which can be used in multi-memory area function.<br />

♦: Data for each module ♠: Data for each channel<br />

For details on the data, see the SRZ <strong>Instruction</strong> Manual (IMS01T04-E).<br />

• <strong>Communication</strong> data (RKC communication/Modbus)<br />

RKC Modbus<br />

Name Iden- register address Digits Attribute<br />

Factory<br />

Data range<br />

set value<br />

tifier HEX DEC<br />

Model code ♦ ID ⎯ ⎯ 32 RO Model code (character) ⎯<br />

ROM version ♦ VR ⎯ ⎯ 8 RO ROM version ⎯<br />

Measured value<br />

(PV)<br />

♠<br />

Comprehensive<br />

event state<br />

♠<br />

Operation mode<br />

state monitor<br />

♠<br />

Error code<br />

♦<br />

M1 0000<br />

・<br />

0003<br />

AJ 0004<br />

・<br />

0007<br />

L0 0008<br />

・<br />

000B<br />

0<br />

・<br />

3<br />

4<br />

・<br />

7<br />

8<br />

・<br />

11<br />

7 RO Input scale low to<br />

Input scale high<br />

7 RO RKC communication<br />

Least significant digit to 4th digit:<br />

Event 1 state<br />

to Event 4 state<br />

5th digit: Heater break alarm<br />

state<br />

6th digit: Temperature rise<br />

completion<br />

7th digit: Burnout<br />

Data 0: OFF 1: ON<br />

Modbus<br />

b0 to b3: Event 1 state<br />

to Event 4 state<br />

b4: Heater break alarm<br />

state<br />

b5: Temperature rise<br />

completion<br />

b6: Burnout<br />

b7 to b15: Unused<br />

Data 0: OFF 1: ON<br />

[Decimal number: 0 to 127]<br />

7 RO RKC communication<br />

Least significant digit:<br />

Control STOP<br />

2nd digit: Control RUN<br />

3rd digit: Manual mode<br />

4th digit: Remote mode<br />

5th digit to Most significant digit:<br />

Unused<br />

Data 0: OFF 1: ON<br />

Modbus<br />

b0: Control STOP<br />

b1: Control RUN<br />

b2: Manual mode<br />

b3: Remote mode<br />

b4 to b15: Unused<br />

Data 0: OFF 1: ON<br />

[Decimal number: 0 to 15]<br />

ER 000C 12 7 RO RKC communication<br />

1: Adjustment data error<br />

2: Data back-up error<br />

4: A/D conversion error<br />

32: Logic output data error<br />

Modbus<br />

b0: Adjustment data error<br />

b1: Data back-up error<br />

b2: A/D conversion error<br />

b3: Unused<br />

b4: Unused<br />

b5: Logic output data error<br />

b6 to b15: Unused<br />

Data 0: OFF 1: ON<br />

[Decimal number: 0 to 63]<br />

⎯<br />

⎯<br />

⎯<br />

⎯<br />

⎯<br />

⎯<br />

⎯<br />

(Continued on the next page )


Name<br />

Manipulated<br />

output value<br />

(MV) monitor<br />

[heat-side] ♣<br />

Manipulated<br />

output value<br />

(MV) monitor<br />

[cool-side] ♣<br />

Current<br />

transformer (CT)<br />

input value<br />

monitor ♠<br />

Set value (SV)<br />

monitor ♠<br />

Remote setting<br />

(RS) input value<br />

monitor ♠<br />

Burnout state<br />

monitor ♠<br />

Event 1 state<br />

monitor ♠<br />

Event 2 state<br />

monitor ♠<br />

Event 3 state<br />

monitor ♠<br />

Event 4 state<br />

monitor ♠<br />

Heater break<br />

alarm (HBA)<br />

state monitor ♠<br />

Output state<br />

monitor<br />

♦<br />

Memory area<br />

soak time<br />

monitor ♠<br />

Integrated<br />

operating time<br />

monitor ♦<br />

Holding peak<br />

value ambient<br />

temperature<br />

monitor ♠<br />

Backup memory<br />

state monitor ♦<br />

RKC<br />

Iden-<br />

Modbus<br />

register address<br />

tifier HEX DEC<br />

O1 000D 13<br />

・<br />

・<br />

0010 16<br />

O2 0011<br />

・<br />

0014<br />

M3 0015<br />

・<br />

0018<br />

17<br />

・<br />

20<br />

21<br />

・<br />

24<br />

Digits Attri-<br />

bute<br />

Data range<br />

Factory<br />

set value<br />

7 RO PID control or heat/cool PID<br />

control: −5.0 to +105.0 %<br />

Position proportioning control<br />

⎯<br />

(FBR input): 0.0 to 100.0 %<br />

7 RO −5.0 to +105.0 % ⎯<br />

7 RO CTL-6-P-N: 0.0 to 30.0 A<br />

CTL-12-S56-10L-N:<br />

0.0 to 100.0 A<br />

MS 0019 25 7 RO Setting limiter (low) to<br />

・<br />

・<br />

Setting limiter (high)<br />

⎯<br />

001C 28<br />

S2 001D 29 7 RO Setting limiter (low) to<br />

・<br />

・<br />

Setting limiter (high)<br />

⎯<br />

0020 32<br />

B1 0021 33 1 RO 0: OFF<br />

・<br />

・<br />

1: ON<br />

⎯<br />

0024 36<br />

AA 0025 37 1 RO 0: OFF<br />

・<br />

・<br />

1: ON<br />

⎯<br />

0028 40<br />

AB 0029 41<br />

・<br />

・<br />

1 RO ⎯<br />

002C 44<br />

AC 002D 45<br />

・<br />

・<br />

1 RO ⎯<br />

0030 48<br />

AD 0031 49<br />

・<br />

・<br />

1 RO ⎯<br />

0034 52<br />

AE 0035 53 1 RO 0: OFF<br />

・<br />

・<br />

1: ON<br />

⎯<br />

0038 56<br />

Q1 0039 57 7 RO RKC communication<br />

⎯<br />

Least significant digit to 4th digit:<br />

OUT1 to OUT4<br />

5th digit to Most significant digit:<br />

Unused<br />

Data 0: OFF 1: ON<br />

Modbus<br />

⎯<br />

b0 to b3: OUT1 to OUT4<br />

b4 to b15: Unused<br />

Data 0: OFF 1: ON<br />

TR<br />

003A<br />

・<br />

003D<br />

58<br />

・<br />

61<br />

[Decimal number: 0 to 15]<br />

7 RO 0 minutes 00 seconds to<br />

199 minutes 59 seconds:<br />

RKC communication:<br />

0:00 to 199:59 (min:sec)<br />

Modbus: 0 to 11999 seconds<br />

0 hours 00 minutes to<br />

99 hours 59 minutes:<br />

RKC communication:<br />

0:00 to 99:59 (hrs:min)<br />

Modbus: 0 to 5999 minutes<br />

UT 003E 62 7 RO 0 to 19999 hours ⎯<br />

Hp<br />

003F<br />

・<br />

0042<br />

63<br />

・<br />

66<br />

7 RO −10.0 to +100.0 °C or<br />

14 to 212 °F<br />

EM 0043 67 1 RO 0: The content of the backup ⎯<br />

memory does not co<strong>inc</strong>ide with<br />

that of the RAM.<br />

1: The content of the backup<br />

memory co<strong>inc</strong>ides with that of<br />

the RAM.<br />

Logic output ED ⎯ ⎯ 7 RO RKC communication<br />

monitor 1<br />

Least significant digit to 4th digit:<br />

♦<br />

Logic output 1 to 4<br />

5th digit to Most significant digit:<br />

Unused<br />

Data 0: OFF 1: ON<br />

Logic output EE ⎯ ⎯ 7 RO RKC communication<br />

monitor 2<br />

Least significant digit to 4th digit:<br />

♦<br />

Logic output 5 to 8<br />

5th digit to Most significant digit:<br />

Unused<br />

Data 0: OFF 1: ON<br />

Logic output ⎯ 0044 68 ⎯ RO Modbus<br />

monitor<br />

b0 to b7: Logic output 1 to 8<br />

♦<br />

b8 to b15: Unused<br />

Data 0: OFF 1: ON<br />

[Decimal number: 0 to 255]<br />

Unused ⎯ 0045 69 ⎯ ⎯ ⎯ ・<br />

・<br />

⎯<br />

0060 96<br />

PID/AT transfer G1 0061 97 1 R/W 0: PID control<br />

♠<br />

・<br />

・<br />

1: Autotuning (AT)<br />

0<br />

0064 100<br />

Auto/Manual J1 0065 101 1 R/W 0: Auto mode<br />

transfer ♠<br />

・<br />

・<br />

1: Manual mode<br />

0<br />

0068 104<br />

Remote/Local C1 0069 105 1 R/W 0: Local mode<br />

transfer ♠<br />

・<br />

・<br />

1: Remote mode<br />

0<br />

006C 108<br />

RUN/STOP SR 006D 109 1 R/W 0: STOP (Control stop)<br />

transfer ♦<br />

1: RUN (Control start)<br />

0<br />

Memory area ZA 006E 110<br />

transfer ♠<br />

・<br />

・<br />

7 R/W 1 to 8 1<br />

0071 113<br />

Interlock release AR 0072 114 7 R/W 0: Normal state<br />

♠<br />

・<br />

・<br />

1: Interlock release execution<br />

0<br />

0075 117<br />

Event 1 set value A1 0076 118 7 R/W Deviation action, Deviation action 50<br />

(EV1) ♠<br />

・<br />

・<br />

between channels, Temperature<br />

0079 121<br />

rise completion range*:<br />

Event 2 set value A2 007A 122 7 R/W<br />

−Input span to +Input span<br />

50<br />

(EV2) ♠<br />

・<br />

・<br />

Process action, SV action:<br />

007D 125<br />

Input scale low to<br />

Event 3 set value A3 007E 126 7 R/W Input scale high<br />

50<br />

(EV3) ♠<br />

・<br />

・<br />

MV action:<br />

0081 129<br />

−5.0 to +105.0 %<br />

Event 4 set value A4 0082 130 7 R/W<br />

(EV4) ♠<br />

*When temperature rise completion is 50<br />

・<br />

・<br />

selected at Event 3 action type.<br />

0085 133<br />

⎯<br />

⎯<br />

⎯<br />

Name<br />

Control loop<br />

break alarm<br />

(LBA) time ♠<br />

LBA deadband<br />

♠<br />

Set value (SV)<br />

♠<br />

Proportional<br />

band [heat-side]<br />

♣ ♠<br />

Integral time<br />

[heat-side]<br />

♣ ♠<br />

Derivative time<br />

[heat-side]<br />

♣ ♠<br />

Control response<br />

parameter<br />

♣ ♠<br />

Proportional<br />

band [cool-side]<br />

♣ ♠<br />

Integral time<br />

[cool-side]<br />

♣ ♠<br />

Derivative time<br />

[cool-side]<br />

♣ ♠<br />

Overlap/<br />

Deadband<br />

♣ ♠<br />

Manual reset<br />

♠<br />

Setting change<br />

rate limiter (up)<br />

♠<br />

Setting change<br />

rate limiter<br />

(down) ♠<br />

Area soak time<br />

♠<br />

Link area number<br />

♠<br />

Heater break<br />

alarm (HBA) set<br />

value ♠<br />

Heater break<br />

determination<br />

point ♠<br />

Heater melting<br />

determination<br />

point ♠<br />

PV bias<br />

♠<br />

PV digital filter<br />

♠<br />

PV ratio<br />

♠<br />

PV low input<br />

cut-off<br />

♠<br />

RS bias *<br />

♠<br />

RS digital filter *<br />

♠<br />

RS ratio *<br />

♠<br />

Output<br />

distribution<br />

selection ♠<br />

RKC<br />

Iden-<br />

Modbus<br />

register address<br />

tifier HEX DEC<br />

A5 0086 134<br />

・<br />

・<br />

0089 137<br />

N1 008A 138<br />

・<br />

・<br />

008D 141<br />

S1 008E 142<br />

・<br />

・<br />

0091 145<br />

P1 0092 146<br />

・<br />

・<br />

0095 149<br />

I1 0096<br />

・<br />

0099<br />

D1<br />

CA<br />

P2<br />

I2<br />

D2<br />

V1<br />

MR<br />

HH<br />

HL<br />

TM<br />

LP<br />

A7<br />

NE<br />

NF<br />

PB<br />

F1<br />

PR<br />

DP<br />

RB<br />

F2<br />

RR<br />

DV<br />

009A<br />

・<br />

009D<br />

009E<br />

・<br />

00A1<br />

00A2<br />

・<br />

00A5<br />

00A6<br />

・<br />

00A9<br />

00AA<br />

・<br />

00AD<br />

00AE<br />

・<br />

00B1<br />

00B2<br />

・<br />

00B5<br />

00B6<br />

・<br />

00B9<br />

00BA<br />

・<br />

00BD<br />

00BE<br />

・<br />

00C1<br />

00C2<br />

・<br />

00C5<br />

00C6<br />

・<br />

00C9<br />

00CA<br />

・<br />

00CD<br />

00CE<br />

・<br />

00D1<br />

00D2<br />

・<br />

00D5<br />

00D6<br />

・<br />

00D9<br />

00DA<br />

・<br />

00DD<br />

00DE<br />

・<br />

00E1<br />

00E2<br />

・<br />

00E5<br />

00E6<br />

・<br />

00E9<br />

00EA<br />

・<br />

00ED<br />

00EE<br />

・<br />

00F1<br />

150<br />

・<br />

153<br />

154<br />

・<br />

157<br />

158<br />

・<br />

161<br />

162<br />

・<br />

165<br />

166<br />

・<br />

169<br />

170<br />

・<br />

173<br />

174<br />

・<br />

177<br />

178<br />

・<br />

181<br />

182<br />

・<br />

185<br />

186<br />

・<br />

189<br />

190<br />

・<br />

193<br />

194<br />

・<br />

197<br />

198<br />

・<br />

201<br />

202<br />

・<br />

205<br />

206<br />

・<br />

209<br />

210<br />

・<br />

213<br />

214<br />

・<br />

217<br />

218<br />

・<br />

221<br />

222<br />

・<br />

225<br />

226<br />

・<br />

229<br />

230<br />

・<br />

233<br />

234<br />

・<br />

237<br />

238<br />

・<br />

241<br />

Digits Attri-<br />

bute<br />

Data range<br />

7 R/W 0 to 7200 seconds<br />

(0: Unused)<br />

Factory<br />

set value<br />

480<br />

7 R/W 0 (0.0) to Input span 0 (0.0)<br />

7 R/W Setting limiter (low) to<br />

Setting limiter (high)<br />

7 R/W TC/RTD inputs:<br />

0 (0.0) to Input span<br />

(Unit: °C [°F])<br />

Voltage (V)/current (I) inputs:<br />

0.0 to 1000.0 % of Input span<br />

0 (0.0): ON/OFF action<br />

7 R/W PID control or heat/cool PID<br />

control:<br />

0 to 3600 seconds or 0.0 to<br />

1999.9 seconds<br />

(0, 0.0: PD action)<br />

Position proportioning control:<br />

1 to 3600 seconds or 0.1 to<br />

1999.9 seconds<br />

7 R/W 0 to 3600 seconds or 0.0 to<br />

1999.9 seconds<br />

(0, 0.0: PI action)<br />

1 R/W 0: Slow<br />

1: Medium<br />

2: Fast<br />

When the P or PD action is<br />

selected, this setting becomes<br />

invalid.<br />

7 R/W TC/RTD inputs:<br />

1 (0.1) to Input span<br />

(Unit: °C [°F])<br />

Voltage (V)/current (I) inputs:<br />

0.1 to 1000.0 % of Input span<br />

7 R/W 0 to 3600 seconds or<br />

0.0 to 1999.9 seconds<br />

(0, 0.0: PD action)<br />

7 R/W 0 to 3600 seconds or<br />

0.0 to 1999.9 seconds<br />

(0, 0.0: PI action)<br />

7 R/W TC/RTD inputs:<br />

−Input span to +Input span<br />

(Unit:°C [°F])<br />

Voltage (V)/current (I) inputs:<br />

TC/RTD: 0<br />

V/I: 0.0<br />

TC/RTD:<br />

30 (30.0)<br />

V/I: 30.0<br />

240<br />

60<br />

PID control,<br />

Position<br />

proportioning<br />

control: 0<br />

Heat/cool<br />

PID control:<br />

2<br />

TC/RTD:<br />

30 (30.0)<br />

V/I: 30.0<br />

240<br />

−100.0 to +100.0 % of Input span<br />

7 R/W −100.0 to +100.0 % 0.0<br />

7 R/W 0 (0.0) to Input span/unit time<br />

0 (0.0): Unused<br />

7 R/W Unit time: 60 seconds<br />

(factory set value)<br />

7 R/W 0 minutes 00 seconds to<br />

199 minutes 59 seconds:<br />

RKC communication:<br />

0:00 to 199:59 (min:sec)<br />

Modbus: 0 to 11999 seconds<br />

0 hours 00 minutes to<br />

99 hours 59 minutes:<br />

RKC communication:<br />

0:00 to 99:59 (hrs:min)<br />

Modbus: 0 to 5999 minutes<br />

7 R/W 0 to 8<br />

(0: No link)<br />

60<br />

0<br />

0 (0.0)<br />

0 (0.0)<br />

RKC<br />

communication:<br />

0:00<br />

Modbus:<br />

0<br />

7 R/W When CT is CTL-6-P-N:<br />

0.0 to 30.0 A (0.0: Not used)<br />

When CT is CTL-12-S56-10L-N:<br />

0.0 to 100.0 A (0.0: Not used)<br />

0.0<br />

7 R/W 0.0 to 100.0 % of HBA set value 30.0<br />

(0.0: Heater break determination<br />

is invalid)<br />

7 R/W 0.0 to 100.0 % of HBA set value 30.0<br />

(0.0: Heater melting<br />

determination is invalid)<br />

7 R/W −Input span to +Input span 0<br />

7 R/W 0.0 to 100.0 seconds<br />

(0.0: Unused)<br />

0<br />

0.0<br />

7 R/W 0.500 to 1.500 1.000<br />

7 R/W 0.00 to 25.00 % of input span 0.00<br />

7 R/W −Input span to +Input span 0<br />

7 R/W 0.0 to 100.0 seconds<br />

(0.0: Unused)<br />

0.0<br />

7 R/W 0.001 to 9.999 1.000<br />

1 R/W 0: Control output<br />

1: Distribution output<br />

* Data on RS bias, RS ratio and RS digital filter is that in cascade control or ratio setting.<br />

0<br />

Name<br />

Output<br />

distribution<br />

bias ♠<br />

Output<br />

distribution<br />

ratio ♠<br />

Proportional<br />

cycle time<br />

♠<br />

Minimum<br />

ON/OFF time of<br />

proportioning<br />

cycle ♠<br />

Manual<br />

manipulated<br />

output value<br />

♣ ♠<br />

Area soak time<br />

stop function<br />

♠<br />

EDS mode<br />

(for disturbance 1)<br />

♠<br />

EDS mode<br />

(for disturbance 2)<br />

♠<br />

EDS value 1<br />

(for disturbance 1)<br />

♠<br />

EDS value 1<br />

(for disturbance 2)<br />

♠<br />

EDS value 2<br />

(for disturbance 1)<br />

♠<br />

EDS value 2<br />

(for disturbance 2)<br />

♠<br />

EDS transfer time<br />

(for disturbance 1)<br />

♠<br />

EDS transfer time<br />

(for disturbance 2)<br />

♠<br />

EDS action time<br />

(for disturbance 1)<br />

♠<br />

EDS action time<br />

(for disturbance 2)<br />

♠<br />

EDS action wait<br />

time ♠<br />

(for disturbance 1)<br />

EDS action wait<br />

time ♠<br />

(for disturbance 2)<br />

EDS value<br />

learning times<br />

♠<br />

EDS start signal<br />

♠<br />

Operation mode<br />

♠<br />

Startup tuning<br />

(ST) ♠<br />

Automatic<br />

temperature rise<br />

learning ♠<br />

<strong>Communication</strong><br />

switch (for logic)<br />

♦<br />

RKC<br />

Iden-<br />

Modbus<br />

register address<br />

tifier HEX DEC<br />

DW 00F2 242<br />

・<br />

・<br />

00F5 245<br />

DQ<br />

T0<br />

VI<br />

00F6<br />

・<br />

00F9<br />

00FA<br />

・<br />

00FD<br />

00FE<br />

・<br />

0101<br />

ON 0102<br />

・<br />

0105<br />

RV 0106<br />

・<br />

0109<br />

NG 010A<br />

・<br />

010D<br />

NX 010E<br />

・<br />

0111<br />

NI 0112<br />

・<br />

0115<br />

NJ 0116<br />

・<br />

0119<br />

NK 011A<br />

・<br />

011D<br />

NM 011E<br />

・<br />

0121<br />

NN 0122<br />

・<br />

0125<br />

NO 0126<br />

・<br />

0129<br />

NQ 012A<br />

・<br />

012D<br />

NL 012E<br />

・<br />

0131<br />

NR 0132<br />

・<br />

0135<br />

NY 0136<br />

・<br />

0139<br />

NT 013A<br />

・<br />

013D<br />

NU 013E<br />

・<br />

0141<br />

EI 0142<br />

・<br />

0145<br />

Unused ⎯ 014F<br />

・<br />

0175<br />

246<br />

・<br />

249<br />

250<br />

・<br />

253<br />

254<br />

・<br />

257<br />

258<br />

・<br />

261<br />

262<br />

・<br />

265<br />

266<br />

・<br />

269<br />

270<br />

・<br />

273<br />

274<br />

・<br />

277<br />

278<br />

・<br />

281<br />

282<br />

・<br />

285<br />

286<br />

・<br />

289<br />

290<br />

・<br />

293<br />

294<br />

・<br />

297<br />

298<br />

・<br />

301<br />

302<br />

・<br />

305<br />

306<br />

・<br />

309<br />

310<br />

・<br />

313<br />

314<br />

・<br />

317<br />

318<br />

・<br />

321<br />

322<br />

・<br />

325<br />

Data range<br />

Factory<br />

set value<br />

7 R/W −100.0 to +100.0 % 0.0<br />

7 R/W −9.999 to +9.999 1.000<br />

7 R/W 0.1 to 100.0 seconds<br />

M: Relay contact output<br />

V: Voltage pulse output<br />

T: Triac output<br />

D: Open collector output<br />

M output:<br />

20.0<br />

V, T, D<br />

output: 2.0<br />

7 R/W 0 to 1000 ms 0<br />

7 R/W PID control:<br />

Output limiter (low) to<br />

Output limiter (high)<br />

Heat/cool PID control:<br />

−Cool-side output limiter (high) to<br />

+Heat-side output limiter (high)<br />

Position proportioning control<br />

(with FBR input):<br />

Output limiter (low) to<br />

Output limiter (high)<br />

Position proportioning control<br />

(without FBR input):<br />

0: Close-side output OFF,<br />

Open-side output OFF<br />

1: Close-side output ON,<br />

Open-side output OFF<br />

2: Close-side output OFF,<br />

Open-side output ON<br />

0.0<br />

1 R/W 0: No function 3: Event 3 0<br />

1: Event 1 4: Event 4<br />

2: Event 2<br />

1 R/W 0: No function<br />

0<br />

1: EDS function mode<br />

2: Learning mode<br />

1 R/W 3: Tuning mode<br />

0<br />

EDS function: External disturbance<br />

suppression function<br />

7 R/W −100.0 to +100.0 % 0.0<br />

7 R/W 0.0<br />

7 R/W 0.0<br />

7 R/W 0.0<br />

7 R/W 0 to 3600 seconds or<br />

0.0 to 1999.9 seconds<br />

7 R/W 0<br />

7 R/W 1 to 3600 seconds 600<br />

7 R/W 600<br />

7 R/W 0.0 to 600.0 seconds 0.0<br />

7 R/W 0.0<br />

7 R/W 0 to 10 times<br />

(0: No learning mode)<br />

1 R/W 0: EDS start signal OFF<br />

1: EDS start signal ON<br />

(for disturbance 1)<br />

2: EDS start signal ON<br />

(for disturbance 2)<br />

1 R/W 0: Unused<br />

1: Monitor<br />

2: Monitor + Event function<br />

3: Control<br />

1 R/W 0: ST unused<br />

1: Execute once<br />

2: Execute always<br />

1 R/W 0: Unused<br />

1: Learning<br />

ST 0146<br />

・<br />

0149<br />

326<br />

・<br />

329<br />

Y8 014A 330<br />

・<br />

・<br />

014D 333<br />

EF 014E 334 7 R/W RKC communication<br />

Least significant digit to 4th digit:<br />

<strong>Communication</strong> switch<br />

1 to 4<br />

5th digit to Most significant digit:<br />

Unused<br />

Data 0: OFF 1: ON<br />

335<br />

・<br />

373<br />

Modbus<br />

0<br />

b0 to b3: <strong>Communication</strong> switch<br />

1 to 4<br />

b4 to b15: Unused<br />

Data 0: OFF 1: ON<br />

[Decimal number: 0 to 15]<br />

⎯ ⎯ ⎯ ⎯<br />

For communication data (Engineering setting), refer to the SRZ <strong>Instruction</strong> Manual (IMS01T04-E).<br />

0<br />

1<br />

0<br />

3<br />

0<br />

0<br />

0<br />

• <strong>Communication</strong> data for multi-memory area data<br />

(only for Modbus)<br />

Use the register addresses of 0500H to 0553H to confirm or change set values of<br />

parameters in multi-memory areas which are not selected. For example, when memory area<br />

1 is selected, set values of parameters in memory-area 2 to 7 can be changed by these<br />

register addresses. [For RKC communication, communication parameter is used to do the<br />

same operation. Refer to SRZ <strong>Instruction</strong> Manual (IMS01T04-E).]<br />

Name<br />

Setting memory area<br />

number<br />

Modbus<br />

register address<br />

HEX DEC<br />

0500 1280<br />

・<br />

・<br />

0503 1283<br />

Digits Attribute<br />

Attribute<br />

Data range<br />

Modbus is a registered trademark of Schneider Electric.<br />

Company names and product names used in this manual are the trademarks or registered<br />

trademarks of the respective companies.<br />

RKC INSTRUMENT INC.<br />

®<br />

Factory<br />

set value<br />

R/W 1 to 8 1<br />

Event 1 set value (EV1) 0504 1284 R/W Deviation action,<br />

50<br />

・<br />

・ Deviation action between channels,<br />

0507 1287 Temperature rise completion range:<br />

Event 2 set value (EV2) 0508 1288 R/W 50<br />

−Input span to +Input span<br />

・<br />

・<br />

050B 1291 Process action, SV action:<br />

Event 3 set value (EV3) 050C 1292 R/W Input scale low to Input scale high 50<br />

・<br />

・ MV action:<br />

−5.0 to +105.0 %<br />

Event 4 set value (EV4) 0510 1296 R/W<br />

50<br />

050F 1295<br />

・<br />

・<br />

0513 1299<br />

Control loop break alarm 0514 1300 R/W 0 to 7200 seconds<br />

480<br />

(LBA) time<br />

・<br />

0517<br />

・<br />

1303<br />

(0: Unused)<br />

LBA deadband 0518 1304 R/W 0 (0.0) to Input span 0 (0.0)<br />

・<br />

051B<br />

・<br />

1307<br />

Set value (SV)<br />

051C<br />

・<br />

1308<br />

・<br />

R/W Setting limiter (low) to<br />

Setting limiter (high)<br />

TC/RTD: 0<br />

V/I: 0.0<br />

051F 1311<br />

Proportional band<br />

[heat-side]<br />

0520<br />

・<br />

0523<br />

1312<br />

・<br />

1315<br />

R/W TC/RTD inputs:<br />

0 (0.0) to Input span (Unit: °C [°F])<br />

Voltage (V)/current (I) inputs:<br />

TC/RTD:<br />

30 (30.0)<br />

V/I: 30.0<br />

0.0 to 1000.0 % of Input span<br />

0 (0.0): ON/OFF action<br />

Integral time [heat-side] 0524<br />

・<br />

0527<br />

1316<br />

・<br />

1319<br />

R/W PID control or heat/cool PID control:<br />

0 to 3600 seconds or<br />

0.0 to 1999.9 seconds<br />

(0, 0.0: PD action)<br />

Position proportioning control:<br />

1 to 3600 seconds or<br />

0.1 to 1999.9 seconds<br />

240<br />

Derivative time [heat-side] 0528<br />

・<br />

052B<br />

Control response<br />

parameter<br />

Proportional band<br />

[cool-side]<br />

052C<br />

・<br />

052F<br />

0530<br />

・<br />

0533<br />

Integral time [cool-side] 0534<br />

・<br />

0537<br />

Derivative time [cool-side] 0538<br />

・<br />

053B<br />

Overlap/Deadband<br />

053C<br />

・<br />

053F<br />

Manual reset 0540<br />

・<br />

0543<br />

Setting change rate limiter 0544<br />

(up)<br />

・<br />

0547<br />

Setting change rate limiter 0548<br />

(down)<br />

・<br />

054B<br />

Area soak time<br />

054C<br />

・<br />

054F<br />

Link area number 0550<br />

・<br />

0553<br />

1320 R/W<br />

・<br />

1323<br />

1324 R/W<br />

・<br />

1327<br />

1328<br />

・<br />

1331<br />

1332 R/W<br />

・<br />

1335<br />

1336 R/W<br />

・<br />

1339<br />

1340 R/W<br />

・<br />

1343<br />

0 to 3600 seconds or<br />

0.0 to 1999.9 seconds<br />

(0, 0.0: PI action)<br />

0: Slow<br />

1: Medium<br />

2: Fast<br />

When the P or PD action is selected,<br />

this setting becomes invalid. 2<br />

R/W TC/RTD inputs:<br />

1 (0.1) to Input span (Unit: °C [°F])<br />

Voltage (V)/current (I) inputs:<br />

0.1 to 1000.0 % of Input span<br />

0 to 3600 seconds or<br />

0.0 to 1999.9 seconds<br />

(0, 0.0: PD action)<br />

0 to 3600 seconds or<br />

0.0 to 1999.9 seconds<br />

(0, 0.0: PI action)<br />

TC/RTD inputs:<br />

−Input span to +Input span<br />

(Unit:°C [°F])<br />

Voltage (V)/current (I) inputs:<br />

−100.0 to +100.0 % of Input span<br />

The first edition: MAR. 2006 [IMQ00]<br />

The third edition: SEP. 2007 [IMQ00]<br />

HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN<br />

PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@<strong>rkc</strong>inst.co.jp<br />

FAX: 03-3751-8585 (+81 3 3751 8585) SEP. 2007<br />

60<br />

PID control,<br />

Position<br />

proportioning<br />

control: 0<br />

Heat/cool<br />

PID control:<br />

TC/RTD:<br />

30 (30.0)<br />

V/I: 30.0<br />

240<br />

1344<br />

・<br />

1347<br />

R/W −100.0 to +100.0 % 0.0<br />

1348 R/W 0 (0.0) to Input span/unit time<br />

0 (0.0)<br />

・<br />

1351<br />

0 (0.0): Unused<br />

1352 R/W Unit time: 60 seconds<br />

0 (0.0)<br />

・ (factory set value)<br />

1355<br />

1356 R/W 0 to 11999 seconds or 0 to 5999<br />

0<br />

・ minutes<br />

1359<br />

1360 R/W 0 to 8<br />

0<br />

・ (0: No link)<br />

1363<br />

For the Modbus data mapping function, see the SRZ <strong>Instruction</strong> Manual<br />

(IMS01T04--E).<br />

60<br />

0

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!