TEMPERATURE ACTUATED WATER REGULATING VALVES<br />
Type OWR, HWR & XWR<br />
GENERAL DESCRIPTION<br />
• Type OWR: Two-way temp. <strong>actuated</strong> <strong>water</strong> rgulating<br />
<strong>valves</strong>, open on <strong>temperature</strong> rise.<br />
Type HWR: Two-way temp. <strong>actuated</strong> <strong>water</strong> <strong>regulating</strong><br />
<strong>valves</strong>, open on <strong>temperature</strong> decrease.<br />
Type XWR: Three-way temp. <strong>actuated</strong> <strong>water</strong> <strong>regulating</strong><br />
<strong>valves</strong>.<br />
• Temperature sensing element (type OWR, HWR &<br />
XWR)<br />
Capil. tube: 1000mm2.4<br />
Bulb size: 3/4"150mm (models with 3/4" or less<br />
connection size)<br />
3/4" 320mm (models with 1" or more<br />
connection size)<br />
• Body material: Bronze for <strong>water</strong> and brine,<br />
cast iron for <strong>water</strong> only<br />
TYPE NUMBER SELECTION (SPECIFICATIONS)<br />
Type OWR<br />
TEMPERATURE ACTUATED VALVES TWO–WAY<br />
Unit: PSI {kgf/cm 2 }<br />
Catalog No.<br />
Valve<br />
Connection Temp. Max. Water Max. Max. Bulb Bulb Factory<br />
Wt.<br />
Body<br />
Range Temp. Water Temp. Size Setting<br />
(kg)<br />
Material Size Style (°F) (°F) Press. (°F) (mm) (°F)<br />
5004 G<br />
1/2"<br />
1.0<br />
19150<br />
5006 G 3/4" Rc<br />
1.2<br />
Bronze<br />
5010 G 1" (FPT)<br />
2.0<br />
5012 G 1–1/4" 86o 122<br />
176 19320 104 2.2<br />
5014 F<br />
1–1/2"<br />
14.5<br />
5020 F Cast Iron 2" Flange<br />
22.0<br />
32350<br />
OWR– 5024 F 2–1/2" 142<br />
26.0<br />
140<br />
HWR– 7504 G<br />
1/2"<br />
{10}<br />
1.0<br />
19150<br />
7506 G 3/4" Rc<br />
1.2<br />
Bronze<br />
7510 G 1" (FPT)<br />
2.0<br />
7512 G 1–1/4" 122 to 167<br />
212 19320 140 2.2<br />
7514 F 1–1/2"<br />
14.5<br />
7520 F Cast Iron 2" Flange<br />
22.0<br />
32350<br />
7524 F<br />
2–1/2"<br />
26.0<br />
Pressure at which valve starts openning.<br />
OWR & HWR with flange connection are supplied with JIS 10K (0.98 MPa) round companion flanges (JIS B2239) and bolt/nuts.<br />
Capillary tube ... Standard 1 meter, optional 0.5, 1.5 and 2 meters<br />
Type XWR<br />
TEMPERATURE ACTUATED VALVES THREE–WAY<br />
Unit: PSI {kgf/cm 2 }<br />
Catalog No.<br />
Valve<br />
Connection Temp. Max. Water Max. Max. Bulb Bulb Factory<br />
Wt.<br />
Body<br />
Range Temp. Water Temp. Size Setting<br />
(kg)<br />
Material Style Size (°F) (°F) Press. (°F) (mm) (°F)<br />
XWR–<br />
5004 G<br />
1/2"<br />
1.0<br />
19150<br />
5006 G 3/4"<br />
1.5<br />
86to 122<br />
176<br />
104<br />
5010 G<br />
1"<br />
2.5<br />
19320<br />
5012 G Rc 1–1/4"<br />
142<br />
3.0<br />
Bronze<br />
140<br />
7504 G (FPT) 1/2" {10}<br />
1.1<br />
19150<br />
7506 G<br />
3/4"<br />
1.5<br />
122 to 167<br />
100<br />
140<br />
7510 G 1"<br />
2.5<br />
19320<br />
7512 G 1–1/4"<br />
3.0<br />
Pressure at which valve starts openning.<br />
Capillary tube ... Standard 1 meter, optional 0.5, 1.5 and 2 meters<br />
1
VALVE ACTION<br />
Set Point is <strong>temperature</strong> for valve opening. Each cheractaristic of <strong>valves</strong> is different as follows.<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
ADJUSTMENT<br />
One full turn of adjusting screw changes pressure/<strong>temperature</strong> setting as shown below.<br />
OWR–<br />
HWR–<br />
XWR–<br />
OWR–<br />
HWR–<br />
Catalog No.<br />
04G<br />
06G<br />
10G<br />
12G<br />
14F<br />
20F<br />
24F<br />
Change in Temp. Setting<br />
Approx. 7.0°C<br />
Approx. 5.0°C<br />
Approx. 7.0°C<br />
DIMENSIONS<br />
Type OWR, HWR–G<br />
<br />
Type OWR–F, HWR<br />
<br />
Catalog No.<br />
L<br />
Unit: mm<br />
H h<br />
D<br />
<br />
<br />
<br />
<br />
OWR–<br />
HWR–<br />
5004 G 70 100 83<br />
5006 G 80 104 87<br />
42<br />
5010 G 90 116 97<br />
5012 G 100 121 102 59<br />
5014 F 148 125 105<br />
5020 F 173<br />
5024 F 179<br />
180 155 89<br />
7504 G 70 100 83<br />
7506 G 80 104 87<br />
42<br />
7510 G 90 116 97<br />
7512 G 100 121 102 59<br />
7514 F 148 125 106<br />
7520 F 173<br />
7524 F 179<br />
180 155 89<br />
Type XWR<br />
<br />
Catalog No.<br />
L<br />
H<br />
Unit: mm<br />
h<br />
h1<br />
D<br />
<br />
<br />
<br />
<br />
<br />
<br />
XWR–<br />
5004G 70 100 31 83<br />
5006G 80 104 39 87<br />
5010G 90 116 44 97<br />
5012G 100 121 54 102<br />
7504G 70 100 31 83<br />
7506G 80 104 39 87<br />
7510G 90 116 44 97<br />
7512G 100 121 54 102<br />
42<br />
59<br />
42<br />
59<br />
<br />
<br />
<br />
Unit: mm