High Resistance Ground<br />

Fault Protection with the<br />

PulserPlus.Net TM<br />

Chris Small – Post Glover<br />

John Levine – L 3 , Inc.


<strong>Failure</strong> <strong>Mode</strong><br />

<strong>Percentage</strong> <strong>of</strong> <strong>Failure</strong>s<br />

Line to Ground 98%<br />

Phase to Phase < 1.5%<br />

*Three Phase < 0.5%<br />

*Most three phase faults are man-made:<br />

i.e. accidents caused by improper operating<br />

procedure.


The massive energy released in a ground fault<br />

rapidly vaporizes the metal conductors involved,<br />

blasting molten metal and expanding plasma<br />

outward with extreme force.<br />

5-10 Arch Flash Explosions in US per day<br />

Over 2000 Arc Flash & Blast injuries & deaths a<br />

year in US<br />

Surfaces <strong>of</strong> nearby people and objects absorb<br />

this energy and are instantly heated to<br />

vaporizing temperatures.<br />

Source: NFPA, CapSchell


HRG<br />

AØ<br />

Source<br />

(Wye)<br />

N<br />

BØ<br />

CØ<br />

<br />

Advantages<br />

◦ Limits Ground Fault current<br />

to 10 Amps or less<br />

◦ Allows faulted circuit to<br />

continue operation<br />

◦ Eliminates 95% <strong>of</strong> arc flash<br />

potential<br />

◦ Significantly decreases<br />

shock potential


Can be connected via RS-485 or Ethernet<br />

Accessible via IP address (pre-loaded, but can<br />

be edited)<br />

Remote viewing possible<br />

Incorporate into Network Protection Scheme


Alarm Table – stores 200 alarms with value,<br />

time and date<br />

Events Table – stores 200 events such as<br />

faults cleared, pulsing started/stopped,<br />

password activities, etc with time and date<br />

Tables for charging current, passwords,<br />

timers and system data


Up to 2 GB SD card for back-up storage<br />

Pulser s<strong>of</strong>tware can be reloaded in the field<br />

Individual settings can be cloned to other<br />

units<br />

Data Tables can also be backed up


Tables can be accessed remotely through<br />

customer’s LAN.<br />

Data Logging will record all alarms, events<br />

and parameter changes<br />

◦ Allows customer to track/trend faults<br />

◦ More easily allows customer to locate intermittent<br />

faults


- Used to determine<br />

resistor failure<br />

- Can also indicate<br />

broken connection to<br />

neutral<br />

Ω


Monitors each phase and indicates which<br />

phase is faulted<br />

Knowing the faulted phase can assist with<br />

troubleshooting and repair


In ungrounded systems, a<br />

voltage is held on the system<br />

capacitance after a fault. In an<br />

arcing or intermittent fault, this<br />

can lead to a significant voltage<br />

build-up.<br />

In a high resistance grounded<br />

system, the resistance must be<br />

low enough to allow the system<br />

capacitance to discharge<br />

relatively quickly.


1. Press the CHRGNG<br />

CURRENT button<br />

2. One phase shorted<br />

through 55 Ω resistor<br />

3. Current in fault and thru<br />

neutral are measured<br />

Charging current = Square Root (Fault Current 2 – Resistor Current 2 )


• Much easier for<br />

installers and field<br />

technicians to<br />

change fault and<br />

pulse taps<br />

Terminal Block


Password protection to avoid unauthorized<br />

access<br />

Re-alarm if condition not cleared within time<br />

delay<br />

System Test & Charging Current<br />

Measurement disabled during fault<br />

Lamp test


Pulser Plus<br />

Digitally filters out (ignores)<br />

harmonics in your system to<br />

measure only the fundamental<br />

frequency where ground faults<br />

occur<br />

Capable <strong>of</strong> measuring and storing<br />

more parameters, including both<br />

voltage and current monitoring.<br />

Analog<br />

Unless an actual signal filter is in<br />

place to filter out the harmonics,<br />

this system is very susceptible to<br />

nuisance tripping<br />

Typically only measures either<br />

voltage OR current, not both, for<br />

monitoring. This could lead to an<br />

situation where there is a problem<br />

with the resistor (open) and the<br />

system will not detect it.


PulserPlus.Net TM<br />

Competitors<br />

Data Logging 200 alarms and 200<br />

events with real<br />

time/date stamp<br />

Loss <strong>of</strong> Ground<br />

Protection<br />

Charging Current<br />

Measurement<br />

Ethernet<br />

Communications<br />

Offers built in<br />

monitoring as well as<br />

current and voltage<br />

measurement for<br />

redundancy<br />

Standard<br />

Standard<br />

Not available<br />

Optional<br />

Not available<br />

Not available


Stand Alone Unit<br />

Wall Mount Unit<br />

OEM Kit<br />

Retr<strong>of</strong>it Kit


www.postglover.com<br />

www.l-3.com/private/post_glover