31.10.2012 Views

LBC II - Fahlke Control Systems KG

LBC II - Fahlke Control Systems KG

LBC II - Fahlke Control Systems KG

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Fahlke</strong> <strong>Control</strong> <strong>Systems</strong> GmbH Germany<br />

Rudolf-Diesel-Str. 3 • D-27356 Rotenburg<br />

Tel.: (0 42 61) 91 43-0


THEORY OF OPERATION<br />

The <strong>LBC</strong> <strong>II</strong> watches the preselected pressure within a pipeline and shut down a valve whenever a<br />

pressure drop above a certain value is observed. This threshold depends on the operating conditions<br />

of the line, and must be determined in a way that it does not interfere with normal operational<br />

pressure drops.<br />

The common mechanical line break systems are not independent of some physical parameters like<br />

absolute pressure, dynamic viscosity, density and temperature of the linefill. By this reasons, the<br />

threshold for closing the valve can not be maintained precisely, and the user is forced to select a<br />

worst case limit. In some cases this must be a very rough estimation and makes the line break device<br />

too sensitive for practical use.<br />

The best way to detect a line break is to measure the pressure and to react on a certain pressure<br />

gradient. This can only be achieved by an electronic device. The transport-lines can lead pressure<br />

waves, which can simulate pressure drops, and this is why the selected gradient must be observed for<br />

a certain period of time to decide whether the change in pressure is tolerable or not. A gradient of 0,6<br />

bar/minute can also be a drop of 10 millibars per second, which is certainly a value which should be<br />

ignored. This example shows, that not only the pressure gradient but also the time span is significant<br />

for a system leak.<br />

The combination of the gradient and the observing time results in an absolute value of linefill that will<br />

be lost, in respect to the line length observed. These parameters must be discussed when fixing a<br />

limit for the gradient and reaction speed of the protective device. It is important to be aware of the<br />

fact, that the oil (gas) loss until the moment of reaction will be very small in comparison to the loss<br />

that will occure after closing a valve anyway, and that on the other hand the safety for a proper<br />

decision will increase with the observing time for the controller.<br />

The basic function of the processor is to measure the pressure and to shift the measured values into a<br />

buffer. Then it calculates the average of the two halves of the buffer and compares them, which gives<br />

the average of a pressure gradient within the measuring period. The selection of the gradient is done<br />

by means of a thumbwheel switch on the front panel of the processor. The gradient can be selected<br />

within the limit of 0,2 until 1,8 bar/minute.


MAIN COMPONENTS OF THE <strong>LBC</strong><br />

The <strong>LBC</strong> has the dimension of 105 x 90 x<br />

195 mm and will be delivered installed into<br />

a stainless steel box IP54 of 380 x 210 x<br />

600 mm which includes battery back up<br />

with charger unit, junction box, relay box<br />

and select switch.<br />

The supply for the processor can be<br />

adapted to practically all voltages. For AC<br />

supplies, a transformer will convert the<br />

input voltage to the internal supply of 12 V<br />

DC. When DC supply is given, a DC/DC<br />

converter is installed on the supply board<br />

of the processor. The power used to feed<br />

the processor is less than 200 milliwatt, that<br />

can also easily be done by a solar cell,<br />

which can be delivered by <strong>Fahlke</strong> as an<br />

option.<br />

In all cases the processor will be backed up<br />

by a battery that makes sure operation<br />

continues for a minimum of ten days after<br />

the power supply fails.


THE MICROPROCESSOR<br />

has its program stored in proms. This allows to match its characteristics in line with the customers demands.<br />

Even if the basic parameters required change, a reprogramming can be achieved by simply changing the proms<br />

on site, because they are not soldered into the printed circuit board, but only plugged into sockets.<br />

The design is based on long practical experience with various leak detection systems, therefore it is very likely,<br />

that hard- and software configuration will cover all practical applications for detection of leaks in oil- and gas-<br />

lines.<br />

The hardware has an indication panel where serveral<br />

parameters can be seen, like:<br />

a) gradient positiv,<br />

b) gradient negative,<br />

c) if the order for closing the actuator (valve) has<br />

been given and the actuator is still running into<br />

closed position,<br />

d) or if actuator and valve are already closed,<br />

e) indication if reopening the actuator (valve) is<br />

working,<br />

f) battery low alarm,<br />

g) malfunction indication<br />

h) and processor function indication.<br />

All of them are shown by LED signals on the display.<br />

The actual measured line pressure and the pressure<br />

gradient are both alternating shown on an extra LCD<br />

display.<br />

The lower part of the front also consists of a two<br />

decade thumbwheel switch for the selection of the<br />

pressure gradient.<br />

LEITUNGSBRUCH-DETEKTIONS-SYSTEM<br />

LINEBREAK-DETECTION-SYSTEM<br />

Anzeige<br />

indication<br />

<strong>LBC</strong> <strong>II</strong><br />

<strong>Fahlke</strong><br />

<strong>Control</strong> <strong>Systems</strong><br />

Gradient Positiv<br />

Gradient Negative<br />

Läuft zu<br />

traveling closed<br />

Befehl zu<br />

acting closed<br />

Freigabe auf<br />

reopening<br />

Batterie Alarm<br />

Störung<br />

malfunction<br />

Computer Funktion<br />

Druck / pressure<br />

Funktionsschalter<br />

function<br />

switch<br />

Gradient<br />

Gradient


INDICATION PANEL OF THE <strong>LBC</strong><br />

LEITUNGSBRUCH-DETEKTIONS-SYSTEM<br />

LINEBREAK-DETECTION-SYSTEM<br />

Anzeige<br />

indication<br />

<strong>LBC</strong> <strong>II</strong><br />

<strong>Fahlke</strong><br />

<strong>Control</strong> <strong>Systems</strong><br />

Gradient Positiv<br />

Gradient Negative<br />

Läuft zu<br />

traveling closed<br />

Befehl zu<br />

acting closed<br />

Freigabe auf<br />

reopening<br />

Batterie Alarm<br />

Störung<br />

malfunction<br />

Computer Funktion<br />

Druck / pressure<br />

Funktionsschalter<br />

function<br />

switch<br />

Gradient<br />

Gradient<br />

An analog output represents the line pressure,<br />

this output can be switched to give either 0 to 10<br />

V DC or 0 to 20 milliamps, a life zero output is<br />

optional.<br />

With a modem the complete status of the<br />

processor can be transmitted to a control center,<br />

which can be very useful to monitor the line<br />

pressure and open/close status of the valve.<br />

Commands can also be transmitted to the<br />

compressor, thus using the line break device as<br />

a simple telecommunication plant to telecontrol<br />

a valve.<br />

0 = P 70 bar<br />

1 = GRAD 70 bar<br />

2 = P/G 70 bar<br />

3 = P 40 bar<br />

4 = GRAD 40 bar<br />

5 = P/G 40 bar<br />

6 = <strong>LBC</strong> sends data to modem<br />

7 = failure signalisation output 20 mA<br />

8 = signalisation voltage battery<br />

9 = signalisation A/D transducer coefficient


FUNCTION OF THE CONTROLLER<br />

Switched on, the processor will release the open command, thus allowing the valve to go<br />

to the open position until the limit switch "open" is reached. A LED "open" will be lit for<br />

this period, to show, that the output transistor is activated and the valve should be<br />

running.<br />

The computer measures the pressure in the line in adequate points and shifts the values<br />

into a buffer. At every shift the oldest value is pushed out of the buffer. Whenever a new<br />

value is sampled, the averages of the two halves of the buffer are calculated and also the<br />

difference between both averages.<br />

The LCD display blinks and gives for a period of seven seconds the value of absolute<br />

pressure, then for three seconds the pressure gradient. Two of the LEDs are used to<br />

indicate whether the sign of gradient is positive or negative.<br />

When a pressure drop reaches the predefined threshold, the valve will be closed. During<br />

the closing period a LED also indicates the fact that a control output is energized.<br />

The closing function will also be executed, when the line pressure goes below a certain<br />

pressure (ppmax).


ILLUSTRATION NO. 1<br />

The thumbwheel switch on the front panel of the processor serves for setting the gradient that will<br />

close the valve when a leak is detected in the line. A gradient of this magnitude will close the valve<br />

after 60 seconds. When the leak is greater, the time for detection becomes shorter.<br />

The relation between size of the leak and the time used for detection is a non linear function, that is<br />

shown in illustration no. 1.<br />

P<br />

K: GR > S<br />

A V 2<br />

G R / 2<br />

A V 1<br />

30 30<br />

G<br />

t


1,2<br />

1,1<br />

1,0<br />

0,9<br />

0,8<br />

0,7<br />

0,6<br />

0,5<br />

0,4<br />

0,3<br />

0,2<br />

0,1<br />

S (bar / min.)<br />

10,0 5,0 3,0 2,0<br />

10 20 30 40 50 60<br />

gradient (bar/minute)<br />

1,2<br />

1,0<br />

G<br />

0,7<br />

0,4<br />

0,2<br />

t (s)<br />

ILLUSTRATION NO. 2<br />

The following table gives the appoximate<br />

values for different leaks<br />

and selected thresholds:<br />

threshold selected (bar/minute)<br />

0,2 0,4 0,7 1,0 1,2 2,0 3,0<br />

0,2 60 - - - - - -<br />

0,3 32 - - - - - -<br />

0,4 29 60 - - - - -<br />

0,5 26 33 - - - - -<br />

0,6 24 36 - - - - -<br />

0,7 22 32 60 - - - -<br />

0,8 20 29 39 - - - -<br />

1,0 18 26 36 60 - - -<br />

1,2 18 24 32 42 60 - -<br />

3,0 10 15 20 24 26 30 60<br />

response time (seconds)


PRESSURE MEASUREMENT<br />

For on-line pressure measurement the system is<br />

fitted with a piezoresistiv transducer (Kistler 4043<br />

A50). The transducer is feeded by 3 milliampere<br />

constantly, the measure signal will be taken as an<br />

voltage (0...500 MV) at the wheatstone bridge and<br />

will be prepared by a 12 bit analog digital<br />

converter.<br />

The complete error of the transducer is smaller than 0,5 % by the whole temperature range from -20 up to<br />

+80° Celsius. The longterm change is less than 0,2 % a year. That indicates the transducer works excellent<br />

for absolute pressure measuring. It is mounted in a way to be isolation proof for serveral kilovolts.<br />

The connection to the processor is a four wire connection: two wires to feed the bridge ( 3 milliamps),<br />

and another two to give back the measured voltage (0,375 volts). The function of the transducer is watched<br />

by the processor. If the transducer fails or a wire is interrupted, the processor will give an alarm via a light<br />

emitting diode and will stop operation immediately in order to avoid a wrong operation.


DIMENSIONS OF THE <strong>LBC</strong> COMPONENTS<br />

( 3 )<br />

D = 9<br />

( 4 )<br />

( 1 )<br />

250<br />

D = 6,8<br />

( 7 )<br />

( 6 )<br />

2 x PG 21<br />

1 x PG 13,5<br />

380<br />

( 2 )<br />

( 5 )<br />

<strong>LBC</strong> <strong>II</strong><br />

( 6 )<br />

1 x PG 21<br />

2 x PG 13,5<br />

1 x PG 13,5 / blue<br />

250<br />

600<br />

210<br />

1 = battery<br />

2 = terminal box<br />

3 = on-off switch<br />

4 = battery charger<br />

5 = microprocessor <strong>LBC</strong><br />

6 = cable glands<br />

7 = relay box<br />

The electronic line break system<br />

can also be mounted in an explosion<br />

proof cabinet if necessary.


acoustic<br />

alarm<br />

CPU<br />

BLOCK DIAGRAMM OF THE <strong>LBC</strong><br />

alarm<br />

LEDs<br />

RAM<br />

2 K<br />

LCD-pressure<br />

control<br />

UV-EPROM<br />

2.........6 K<br />

interface-controller<br />

autotest<br />

modem<br />

command open<br />

command close<br />

limit switch<br />

open actuator<br />

limit switch<br />

close actuator<br />

measurement UB<br />

telefon<br />

connection<br />

watchdog output<br />

analog-output<br />

0.........20 mA<br />

piezo<br />

pressure<br />

transmitter

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!