SOCOM (<strong>Heating</strong> Zone 1) – Model Parameter<br />

Total building heat load (from PNNL FEDS<br />

model):<br />

4.46×10 6 Btu/h = 1,306 kW<br />

Peak load taken from log data 4.10 ×10 6 Btu/h = 1,200 kW<br />

Load factor ( peak load / total load<br />

) 84%<br />

Peak temperatures T supply<br />

/T return<br />

340°F/250°F = 170°C/120°C<br />

Water mass flow calculated by flow model 84.5 gpm = 19.2 m³/h<br />

Δp @ CEP calculated by flow model 33.4 psi = 2.3 atm<br />

17