parameter descriptions vacon • 103<br />
After the Stop command, the speed of the motor is decelerated according<br />
to the set deceleration parameters.<br />
If the regenerated energy is high it may be necessary to use an external<br />
braking resistor for to be able to decelerate the motor in acceptable<br />
time.<br />
2.4 I / O START STOP LOGIC<br />
Values 0...4 offer possibilities to control the starting and stopping of the <strong>AC</strong><br />
drive with digital signal connected to digital inputs. CS = Control signal.<br />
The selections including the text 'edge' shall be used to exclude the possibility<br />
of an unintentional start when, for example, power is connected, re-connected<br />
after a power failure, after a fault reset, after the drive is stopped by Run Enable<br />
(Run Enable = False) or when the control place is changed to I / O control.<br />
The Start / Stop contact must be opened before the motor can be started.<br />
I/O stop logic uses accurate stop mode.Accurate stop mode is that the stop<br />
time is fixed from falling edge of DI to power stopping the drive.<br />
Selection<br />
number<br />
0<br />
Selection name<br />
CS1:Forward<br />
CS2:Backward<br />
Note<br />
The functions take place when the contacts are closed.<br />
FWD<br />
Set<br />
frequerty<br />
Output<br />
frequerty<br />
0Hz<br />
t<br />
Set<br />
frequerty<br />
REV<br />
Run enable<br />
Ctrl signal 1<br />
Ctrl signal 2<br />
Keypad<br />
start button<br />
Keypad<br />
stop button<br />
1 2 3 4 5 6 7 8 9 10 11 12 13<br />
Figure 9.3: Start/Stop logic, selection 0<br />