Clamp-On Method<br />
Fall-of-potential <strong>testing</strong>, and its modifications, conforms <strong>to</strong> IEEE 81. It<br />
is extremely reliable, highly accurate and can be used <strong>to</strong> test any size<br />
ground system. Additionally, the opera<strong>to</strong>r has complete control of the test<br />
set-up and can check or proof his/her results by <strong>testing</strong> at different probe<br />
spacing.<br />
Unfortunately, the Fall of Potential method also comes with several<br />
drawbacks:<br />
n It is extremely time consuming and labor intensive.<br />
n Individual ground electrodes must be disconnected from the system <strong>to</strong><br />
be measured.<br />
n There are situations where disconnection is not possible.<br />
The clamp-on ground tester performs a ‘stakeless’ test which is a ground<br />
<strong>resistance</strong> test performed without disconnecting the ground. Based<br />
on Ohm’s Law (R=V/I), the stakeless test induces a known voltage in a<br />
loop circuit that includes ground,<br />
measures resultant current flow<br />
and calculates the loop <strong>resistance</strong><br />
of the circuit. Four pole <strong>earth</strong><br />
testers also perform a stakeless<br />
test; however they use two clamps,<br />
a voltage clamp (V clamp) and a<br />
current clamp (I clamp), and keep<br />
the clamps separate <strong>to</strong> prevent<br />
interaction between the two.<br />
The opera<strong>to</strong>r must be certain that<br />
<strong>earth</strong> is included in the return<br />
loop and be aware that the tester<br />
measures the complete <strong>resistance</strong><br />
of the path (loop <strong>resistance</strong>).<br />
The Megger DET14C shown measuring a<br />
ground spike in a typical ground well.<br />
Fig 22: Basic clamp-on ground <strong>testing</strong> methodology<br />
All elements of the loop are measured in series. The method benefits<br />
from low return path <strong>resistance</strong>, i.e. where the ground <strong>resistance</strong> is large<br />
compared <strong>to</strong> the effective return loop <strong>resistance</strong>.<br />
Figure 22 shows the basic methodology of the stakeless test. The tester<br />
is clamped over R X , the ground being measured. All test current travels<br />
through the ground being measured (R X ) and divides between the<br />
remaining parallel <strong>resistance</strong>s (R 1 <strong>to</strong> R n ). In a multiple ground system,<br />
the circuit can be considered a loop consisting of the individual ground<br />
electrode, a return path via all other electrodes and the mass of <strong>earth</strong>.<br />
The single electrode will have a higher <strong>resistance</strong> than the remainder of<br />
grounds connected in parallel.<br />
Figure 23 shows a <strong>practical</strong> example of where the clamp-on method<br />
is highly effective because of the low return path loop <strong>resistance</strong>. The<br />
application is an interconnected parallel ground, like a lighting string.<br />
Importantly, ground forms part of the loop. The <strong>resistance</strong>-<strong>to</strong>-ground<br />
measure at R 6 is:<br />
R loop = V loop /I loop = R 6 + (1/(1/R 1 + 1/R 2 + 1/R 3 + 1/R 4 + 1/R 5 ))<br />
For six similar electrodes with a <strong>resistance</strong> of 10 Ω, the loop <strong>resistance</strong><br />
measured when <strong>testing</strong> each electrode would be:<br />