PYRAN S FIRE RESISTING GLASS<br />

CERTIFICATE No CF 291<br />

SCHOTT UK LIMITED<br />

This Certificate of Approval relates to the fire resistance of Pyran S glass when used in the following<br />

applications, as defined in BS 476: Part 22: 1987 subject to the undermentioned conditions.<br />

Application<br />

<strong>Fire</strong> Resistance<br />

Performance Integrity -<br />

(mins)<br />

Timber Screens 30 4<br />

Timber Screens 60 5<br />

Page<br />

No.<br />

Double Glazed Units in Timber Screens 30 – 60 6 – 7<br />

Timber Doorsets 30 8 –11<br />

‘<strong>Fire</strong>stile’ Doorsets 30 12 – 14<br />

Timber Doorsets 60 15 - 16<br />

Steel Screens 30 – 60 – 90 – 120 17 – 20<br />

Steel Doorsets 30 – 60 – 90 – 120 21 – 22<br />

Double Glazed Units in Steel Screens 30 – 60 – 90 23 – 24<br />

Double Glazed Units (comprising Venetian blinds) in Steel<br />

30 25<br />

Screens<br />

Butt-Jointed Screens 30 26 – 29<br />

Butt-Jointed Screens 60 30 – 31<br />

Structural Glazing 30 32 – 34<br />

This product is approved on the basis of:<br />

i) Initial type testing.<br />

ii) A design appraisal against TS25.<br />

iii) <strong>Certification</strong> of quality management system to ISO 9001: 2008.<br />

iv) Inspection and surveillance of factory production control.<br />

v) Audit testing.<br />

This Certificate of Approval must be read in conjunction with CERTIFIRE Technical Schedule TS25,<br />

<strong>Fire</strong> Resistant <strong>Glass</strong>, Glazing Systems and materials.<br />

General Requirements<br />

Where the glass is installed in a timber or steel framed screen, the orientation of the screen shall be<br />

no more than ±10º from the vertical.<br />

There is no restriction to the direction of exposure for the glass i.e. the glass is symmetrical.<br />

Orientation may, however, be restricted by the requirements of a non-symmetrical framing system or<br />

certain double glazed unit specifications.<br />

The edge cover to each pane shall be 25 mm maximum and 10 mm minimum.<br />

The glass is approved in a nominal thickness of 6, 8, 10, 12 and 15 mm.<br />

Page 2 of 34 Signed<br />

Issued: 9 th September 2002<br />

Revised:26 th June 2009<br />

Valid to: 8 th October 2012