ELECTRIC POWER RATINGS GUIDE - Teknoxgroup
ELECTRIC POWER RATINGS GUIDE - Teknoxgroup
ELECTRIC POWER RATINGS GUIDE - Teknoxgroup
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
DIESEL<br />
<strong>RATINGS</strong> DEFINITIONS<br />
Prime Power<br />
Output available with varying load for an unlimited time. Average<br />
power output is 70% of the prime power rating. Typical peak demand<br />
of 100% of prime-rated ekW with 10% of overload capability for<br />
emergency use for a maximum of 1 hour in 12. Overload operation<br />
cannot exceed 25 hours per year. Prime power in accordance with<br />
ISO8528. Fuel stop power in accordance with ISO3046.<br />
Continuous Power<br />
Output available without varying load for an unlimited time. Average<br />
power output is 70 - 100% of the continuous power rating. Typical<br />
peak demand is 100% of continuous rated ekW for 100% of operating<br />
hours. Continuous power is in accordance with ISO8528. Fuel stop<br />
power in accordance with ISO3046.<br />
11