14.07.2014 Views

ELECTRIC POWER RATINGS GUIDE - Teknoxgroup

ELECTRIC POWER RATINGS GUIDE - Teknoxgroup

ELECTRIC POWER RATINGS GUIDE - Teknoxgroup

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

DIESEL<br />

<strong>RATINGS</strong> DEFINITIONS<br />

Prime Power<br />

Output available with varying load for an unlimited time. Average<br />

power output is 70% of the prime power rating. Typical peak demand<br />

of 100% of prime-rated ekW with 10% of overload capability for<br />

emergency use for a maximum of 1 hour in 12. Overload operation<br />

cannot exceed 25 hours per year. Prime power in accordance with<br />

ISO8528. Fuel stop power in accordance with ISO3046.<br />

Continuous Power<br />

Output available without varying load for an unlimited time. Average<br />

power output is 70 - 100% of the continuous power rating. Typical<br />

peak demand is 100% of continuous rated ekW for 100% of operating<br />

hours. Continuous power is in accordance with ISO8528. Fuel stop<br />

power in accordance with ISO3046.<br />