ZG 501 Padvault â Single-Phase Residential, 4i 4i ... - Pacific Power
ZG 501 Padvault â Single-Phase Residential, 4i 4i ... - Pacific Power
ZG 501 Padvault â Single-Phase Residential, 4i 4i ... - Pacific Power
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>ZG</strong> <strong>501</strong><br />
5 Design and Manufacturing Requirements<br />
The purpose of a single-phase padvault is to support single-phase transformers or<br />
single-phase sectionalizers. ASTM C857 A16 applies to wall strength. Walls shall be strong<br />
enough to hold pulling irons with a 1200 lb. pull strength. A vault beneath incidental light<br />
truck traffic shall meet ASTM C857 A−8.<br />
5.1 <strong>Padvault</strong> Layout<br />
Unless otherwise approved by PacifiCorp engineering, all dimensions and placement of<br />
hardware shall conform to those shown in Figure 1 and Figure 2.<br />
Figure 1—<strong>Single</strong>-<strong>Phase</strong> Pad for Sectionalizing Cabinets and Transformers,<br />
Vault and Grounding Grid (SI# 7999607)<br />
<strong>ZG</strong> <strong>501</strong><br />
Page 2 of 8<br />
13 Jun 13<br />
<strong>Padvault</strong> —<br />
<strong>Single</strong>-<strong>Phase</strong><br />
<strong>Residential</strong>,<br />
44 (48 48)<br />
MATERIAL SPECIFICATION<br />
Distribution<br />
2013 by PacifiCorp. All rights reserved.<br />
Engineer (E. Maleki):<br />
T&D Stds Mgr (J. Jones):