<strong>ZG</strong> <strong>501</strong><br />

5 Design and Manufacturing Requirements<br />

The purpose of a single-phase padvault is to support single-phase transformers or<br />

single-phase sectionalizers. ASTM C857 A16 applies to wall strength. Walls shall be strong<br />

enough to hold pulling irons with a 1200 lb. pull strength. A vault beneath incidental light<br />

truck traffic shall meet ASTM C857 A−8.<br />

5.1 <strong>Padvault</strong> Layout<br />

Unless otherwise approved by PacifiCorp engineering, all dimensions and placement of<br />

hardware shall conform to those shown in Figure 1 and Figure 2.<br />

Figure 1—<strong>Single</strong>-<strong>Phase</strong> Pad for Sectionalizing Cabinets and Transformers,<br />

Vault and Grounding Grid (SI# 7999607)<br />

<strong>ZG</strong> <strong>501</strong><br />

Page 2 of 8<br />

13 Jun 13<br />

<strong>Padvault</strong> —<br />

<strong>Single</strong>-<strong>Phase</strong><br />

<strong>Residential</strong>,<br />

44 (48 48)<br />

MATERIAL SPECIFICATION<br />

Distribution<br />

2013 by PacifiCorp. All rights reserved.<br />

Engineer (E. Maleki):<br />

T&D Stds Mgr (J. Jones):