MSC/Circ.847<br />

ANNEX<br />

Page 45<br />

53.2.2.1 Location of sealing arrangements for ro-ro cargo spaces<br />

Ro-ro cargo spaces should be capable of being sealed from a location outside of such cargo<br />

spaces, if they are protected with a fixed gas fire-extinguishing system.<br />

53.2.2.1.4 Dimension of pumping and drainage arrangements<br />

With respect to drainage and pumping arrangements, reference is made to the interpretations<br />

of regulation II-2/37.3.1.<br />

53.2.2.2 Dimension of pumping and drainage arrangements<br />

With respect to drainage and pumping arrangements, reference is made to the interpretations<br />

of regulation II-2/37.3.1.<br />

53.2.2.3 Location of portable fire extinguishers including suitability and capacity<br />

With respect to portable fire extinguishers, reference is made to the interpretations of<br />

regulation II-2/37.1.5.3.<br />

53.2.3.1 Reference to MSC/Circ.729<br />

Reference is made to MSC/Circ.729 - Design guidelines and operational recommendations for<br />

ventilation systems in ro-ro cargo spaces.<br />

53.2.3.3 Alarm in case of loss of ventilating capacity<br />

The requirement to indicate any loss of ventilation capacity is considered complied with by an<br />

alarm on the bridge, initiated by fall-out of starter relay of fan motor. (See also interpretations<br />

of regulations II-2/37.1.6.3 and 38.3.3).<br />

53.2.3.5 Arrangement and construction of ventilation ducts<br />

Ventilation ducts should not pass through machinery spaces of category A unless fire insulated<br />

to A-60 standard.<br />

53.2.4.1 Degree of protection of electrical equipment at or below a height of 450 mm<br />

The electrical equipment referred to in this regulation should be of certified safe type and<br />

wiring, if fitted, and should be suitable for use in zone 1 areas as defined in IEC Publication 79<br />

- Electrical apparatus for explosive gas atmospheres (Gas Group II A and Temperature Class<br />

T 3). (See also interpretation 1 of regulation II-2/37.2.2.2).<br />

53.2.4.2 Degree of protection of electrical equipment above a height of 450 mm<br />

The degree of protection of electrical equipment required by this regulation will be realised<br />

through an enclosure of at least IP 55 as defined in IEC Publication 529 - Classification of<br />

degrees of protection provided by enclosures.