Soler & Palau - Tangra
Soler & Palau - Tangra
Soler & Palau - Tangra
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Example of Selection<br />
FDA<br />
Series<br />
FDA 500<br />
S-C<br />
T<br />
Air Volume Q = 20000 m 3 /h<br />
Outlet Velocity<br />
Dynamic Pressure<br />
Total Pressure<br />
Fan Speed<br />
V = 13.6 m/s<br />
Pd = 114 Pa<br />
Pt = 737 Pa<br />
N = 828 rpm<br />
Absorbed Power W = 6.5 kW<br />
Total Efficiency = 62 %<br />
Sound Power Level Lw(A) = 95.3 dB(A)<br />
- Performance shown is for Installation type B - free inlet, ducted outlet. Performance ratings do not<br />
include the effects of appurtenances in the airstream. Power rating kW does not include drive losses.<br />
- The A-weighted sound ratings shown have been calculated per AMCA standard 301.<br />
Values shown are for inlet Lwi(A) sound power levels for installation type B - free inlet,<br />
ducted outlet. Ratings do not include the effect of duct end corrections.<br />
Technical specifications for information purposes only. <strong>Soler</strong> & <strong>Palau</strong>, S.A. reserves the right to change them without any previous notice.<br />