24 2. THE MARINE BOILER PLANT<br />

steam bubbles in the water which raises the surface. See Figure 2.3. Occasionally this<br />

cone seems to collapse creating a wave on the surface. In summary, one must keep in<br />

mind that when speaking <strong>of</strong> controlling the water level it is the number returned from a<br />

water level measurement that is controlled and not the actual chaotic water surface.<br />

Figure 2.3: Water surface in one-pass smoke tube boiler. Note that the surface is rising towards the flue gas<br />

pipes.<br />

2.4 Consumer and Load Characteristics<br />

The steam consumers onboard ships are mostly represented by ruthless on/<strong>of</strong>f operation<br />

<strong>of</strong> valves. Even on tank ships the controllers for the cargo pumps, driven by steam<br />

turbines, react very fast compared to the marine boiler dynamics. However, generally<br />

there is a mixture <strong>of</strong> load situations listed below:<br />

• Ramps: turbine units changing load will generate a ramp in the steam flow disturbance.<br />

• Steps: on/<strong>of</strong>f switching <strong>of</strong> e.g. heating sections for cargo or fuel.<br />

Regarding the step disturbances they are usually in the range from 10-30%, however,<br />

there is no onboard boiler equipment which prevents larger steps from occurring. However,<br />

at this point, by informing the consumer, AI tries to limit the load changes to about<br />

10 %<br />

min to avoid tripping1 the boiler.<br />

The steam load is interpreted as a disturbance in the boiler control system. The reason<br />

is that the consumer has full authority <strong>of</strong> the main steam line. This means that in theory,<br />

if sufficient firing is sustained, the consumer can empty the boiler for steam/water if the<br />

consumption is high enough.<br />

The type <strong>of</strong> disturbance and the frequency with which the disturbance occurs differ<br />

from one ship type to another. However, also within the same ship type the disturbance<br />

1 Tripping here refers to the forced burner shutdown caused by activating the water level alarms.