ELECTRICAL SPECIFICATIONS Version SE - LN 029.1 034.1 039.1 046.1 052.1<br />

Power Supply<br />

<strong>Unit</strong><br />

Phase<br />

Frequency<br />

Voltage<br />

Voltage Tolerance<br />

Maximum starting current<br />

Nominal running current cooling<br />

Maximum running current<br />

Maximum current <strong>for</strong> wires sizing<br />

--- 3 3 3 3 3<br />

Hz 50 50 50 50 50<br />

V 400 400 400 400 400<br />

Minimum % -10% -10% -10% -10% -10%<br />

Maximum % +10% +10% +10% +10% +10%<br />

A 156 156 203 203 298<br />

A 73 90 98 111 127<br />

A 85 101 115 129 155<br />

A 94 111 126 142 171<br />

Fans Nominal running current in cooling<br />

A 5.2 5.2 7.8 7.8 10.4<br />

Compressor<br />

Phase<br />

Voltage<br />

Voltage Tolerance<br />

No. 3 3 3 3 3<br />

V 400 400 400 400 400<br />

Minimum % -10% -10% -10% -10% -10%<br />

Maximum % +10% +10% +10% +10% +10%<br />

A 80 96 107 121 145<br />

---<br />

Maximum running current<br />

Starting method Wye – Delta type (Y – Δ)<br />

ELECTRICAL SPECIFICATIONS Version SE - LN 061.1 073.1 087.1 102.1 118.1<br />

Power Supply<br />

<strong>Unit</strong><br />

Phase<br />

Frequency<br />

Voltage<br />

Voltage Tolerance<br />

Maximum starting current<br />

Nominal running current cooling<br />

Maximum running current<br />

Maximum current <strong>for</strong> wires sizing<br />

--- 3 3 3 3 3<br />

Hz 50 50 50 50 50<br />

V 400 400 400 400 400<br />

Minimum % -10% -10% -10% -10% -10%<br />

Maximum % +10% +10% +10% +10% +10%<br />

A 298 346 426 426 426<br />

A 133 154 203 248 274<br />

A 155 187 240 280 280<br />

A 171 205 264 308 308<br />

Fans Nominal running current in cooling<br />

A 10.4 15.6 15.6 15.6 15.6<br />

Compressor<br />

Phase<br />

Voltage<br />

Voltage Tolerance<br />

No. 3 3 3 3 3<br />

V 400 400 400 400 400<br />

Minimum % -10% -10% -10% -10% -10%<br />

Maximum % +10% +10% +10% +10% +10%<br />

A 145 171 410 264 264<br />

---<br />

Maximum running current<br />

Starting method Wye – Delta type (Y – Δ)<br />

Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.<br />

Maximum starting current: starting current of biggest compressor + fans current<br />

Notes<br />

Nominal current in cooling mode is referred to the following conditions: SST 7°C; ambient 35°C; compressor + fans current.<br />

Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current<br />

Maximum unit current <strong>for</strong> wires sizing is based on minimum allowed voltage<br />

Maximum current <strong>for</strong> wires sizing: (compressors full load ampere + fans current) x 1,1.<br />

KPMCU00104-10EN - page 15/36