You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
geprŸfte<br />
Sicherheit<br />
UPS STATUS LED<br />
ON/OFF/TEST/SILENCE BUTTON<br />
REMOTE PORT<br />
Tel/Modem<br />
surge protection<br />
REMOTE PORT<br />
Tel/Modem<br />
surge protection<br />
BYPASS OUTLET<br />
BYPASS OUTLET<br />
UPS OUTLETS<br />
UPS OUTLETS<br />
EXT. BAT (option)<br />
AC INPUT<br />
AC INPUT<br />
CIRCUIT<br />
BREAKER<br />
EXT. BAT (option)<br />
SPECIFICATION<br />
MODEL<br />
CAPACITY<br />
INPUT Voltage<br />
Frequency<br />
OUTPUT Voltage (on battery)<br />
Frequency (on battery)<br />
Voltage Regulation (AVR)<br />
Transfer Time<br />
<strong>PRO</strong>TECTION Spike Protection<br />
and FILTERING Unit Input<br />
Overload Protection<br />
10 Base-T Cable Port<br />
Short Circuit<br />
BATTERY Type<br />
Typical Recharge Time<br />
Protection<br />
Back-up Time<br />
(a PC with 15" monitor)<br />
PHYSICAL Net Weight Kg (Ibs)<br />
Shipping Weight Kg (Ibs)<br />
Dimension<br />
W x D x H mm<br />
Input Inlet<br />
Receptacles<br />
ALARM Battery Back-up<br />
Battery Low<br />
Overload<br />
INTERFACE RS-232 Interface<br />
ENVIRONMENT Ambient Operation<br />
Audible Noise<br />
Storage Condition<br />
BNT-1000AP BNT-1200AP BNT-1500AP<br />
BNT-2000AP<br />
1000VA<br />
1200VA<br />
1500VA<br />
2000VA<br />
100V,110V,115V,120V,220V,230V,240V +/- 25% at line input<br />
50 or 60 Hz +/- 10% (auto sensing)<br />
Simulated sine wave at 100V,110V,115V,120V,220V,230V,240V +/- 5%<br />
50 or 60 Hz +/-1Hz<br />
AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal.<br />
AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal<br />
2/4 milliseconds, including detection time<br />
1065 Joules, 8/20µs for 100V~120V model, 420 Joules, 8/20µs for 220V~240V model<br />
Fuse or circuit breaker for overload & short circuit protection<br />
UPS automatic power off if overload exceeds 110% of nominal at 60 seconds and 130% at 3 seconds<br />
YES<br />
UPS output cut off immediately or input fuse protection<br />
Sealed, maintenance-free lead acid batteries with 3-6 years typical lifetime<br />
6 hours (to 90% of full capacity)<br />
Auto discharge protection<br />
≤40<br />
≤40<br />
≤40<br />
≤45<br />
minutes<br />
minutes<br />
minutes<br />
minutes<br />
13.4 (28.6) 13.4 (28.6)<br />
15.9 (35.0)<br />
15.9 (35.0)<br />
14.8 (32.6) 14.8 (32.6)<br />
17.3 (38.0)<br />
17.3 (38.0)<br />
130 x 382 x 192<br />
(5.1" x 15.0" x 7.5")<br />
IEC 320 power inlet<br />
NEMA 5-15R(1X0V) / IEC 320 female appliance coupler (2X0V)<br />
Slow beeping sound (about 0.47 Hz)<br />
Rapid beeping sound (about 1.824 Hz)<br />
Continuously beeping sound<br />
YES<br />
3,500 meters max, elevation. 0-95% humidity non-condensing, 0-40 deg C<br />