Technical Characteristics<br />
208VAC<br />
MODEL NUMBER<br />
FS0160CU<br />
208VAC - MPPt range 330Vdc-600Vdc<br />
FS0240CU FS0320CU FS0400CU FS0480CU FS0560CU FS0640CU<br />
NUMBER OF MOD<strong>UL</strong>ES 2<br />
3 4 5 6 7 8<br />
CABINET SIZE frame 0 frame 1 frame 2 frame 3<br />
OUTPUT<br />
INPUT<br />
EFFICIENCY<br />
AUXILIARY<br />
SUPPLY<br />
CABINET<br />
ENVIRON-<br />
MENT<br />
CONTROL<br />
INTERFACE<br />
PROTEC-<br />
TIONS<br />
Nominal AC Output <strong>Power</strong>(kVA) [1]<br />
Rated Output <strong>Power</strong> (+10%) (kVA) [2]<br />
Nominal Output AC Current(A)<br />
Operating Grid Voltage(VAC)<br />
Operating Range, Grid Frequency<br />
Voltage Ripple, PV Voltage<br />
Current Harmonic Distortion (THDi)<br />
<strong>Power</strong> Factor (cosine phi)<br />
<strong>Power</strong> Curtailment (kVA)<br />
MPPt Range (VDC) [3] /@Max.<strong>Power</strong><br />
Max. permissible DC voltage<br />
Max. permissible DC current (A)<br />
Max. Recommended PV peak power<br />
(kWp) (+20%)<br />
Californian efficiency<br />
Max. Efficiency PAC, nom<br />
Euroeta<br />
Max. Standby Consumption (Pnight)<br />
Control <strong>Power</strong> Supply<br />
Max. <strong>Power</strong> Consumption<br />
Dimensions [WxHxD]<br />
Weight (kg/lbs)<br />
Air Flow<br />
Type of ventilation<br />
Degree of protection<br />
Permissible Ambient Temperature [4]<br />
Relative Humidity<br />
Max. Altitude (above sea level) [4]<br />
Noise level [5]<br />
Communication<br />
Digital Inputs<br />
Analogue Inputs<br />
String SupervisorCommunication<br />
Digital Outputs<br />
Analogue Outputs<br />
Ground Fault Monitoring<br />
Heating Resistors<br />
Emergency Stop<br />
General AC Circuit Breaker<br />
AC contactor<br />
AC Circuit Breaker<br />
DC Contactor<br />
DC Fuses<br />
General DC protection<br />
Overvoltage Protection<br />
Lightning Protections<br />
mm<br />
inches<br />
160<br />
176<br />
444<br />
500A<br />
192<br />
98.0%<br />
98.3%<br />
98.0%<br />
< approx.<br />
80W<br />
240<br />
264<br />
666<br />
750A<br />
288<br />
< approx.<br />
120W<br />
320<br />
352<br />
888<br />
400<br />
440<br />
1110<br />
480<br />
528<br />
1332<br />
208Vac (± 10%)<br />
60Hz<br />
< 3%<br />
< 3% at nominal power<br />
0.90 leading … 0.90 lagging adjustable<br />
0...110%/0.1% Steps<br />
330V-600V / 330V-600V<br />
600V<br />
1000A 1250A 1500A<br />
98.0%<br />
98.3%<br />
98.0%<br />
384<br />
< approx.<br />
160W<br />
560<br />
616<br />
1554<br />
640<br />
704<br />
1776<br />
Built-in Internal transformer as standard<br />
(Optional external 3x208VAC power supply and UPS backup system)<br />
920W 1380W 1840W 2300W 2760W 3220W 3680W<br />
2380 x 1290 x 2210 3400 x 1290 x 2210 4750 x 1290 x 2210 5770 x 1290 x 2210<br />
93.7 x 50.8 x 87 133.9 x 50.8 x 87 187 x 50.8 x 87 227.2 x 50.8 x 87<br />
1720/3800 2470/3450 2780/6130 3540/7800 3850/8500 4590/10120 4900/10800<br />
Intake through rear lower part blown out through upper side<br />
Forced<br />
NEMA 3R<br />
-4º F to +122º F /-20ºC …+50ºC<br />
4% to 100%<br />
1000m; >1000m power derating 1% Sn (kVA) per 100m<br />
< 79 dBA<br />
RS232 / RS485 / USB / Ethernet, (Modbus RTU Protocol, Modbus TCP/IP)<br />
2 programmable inputs. Galvanically isolated.<br />
2 programmable and differential inputs; (0-20mA or ± 10mV to ± 10V) and PT100<br />
RS485 /Modbus RTU<br />
2 electrically-isolated programmable switched relays (250VAC, 8A or 30 VDC, 8A)<br />
1 Analogue. Output galvanically isolated.<br />
Floating PV array: Isolation Monitoring per MPP<br />
Grounded PV array (Positive pole and negative pole): GFDI protection per MPP<br />
Standard<br />
Optional<br />
Standard; External Operation<br />
Standard in each module<br />
Standard in each module<br />
Standard in each module<br />
Standard in each module<br />
Optional External Disconnecting Unit Cabinet<br />
(DC fuse protection and on-load disconnector with external operating handle)<br />
DC and AC Inverter sides ( Type 4) and Auxiliary Supply type 2- Internal Standard<br />
Optional (Integrated in the inverter)<br />
480<br />
< approx.<br />
200W<br />
98.0%<br />
98.3%<br />
98.0%<br />
576<br />
< approx.<br />
240W<br />
1750A<br />
672<br />
< approx.<br />
280W<br />
98.0%<br />
98.3%<br />
98.0%<br />
2000A<br />
768<br />
< approx.<br />
320W<br />
NOTES<br />
[1] Values at 50ºC.<br />
[2] Maximum ambient temperature 40ºC.<br />
[3] Values at 1.00·Vac nom and cos Ф = 1.<br />
[4] Other characteristics consult with <strong>Power</strong> <strong>Electronics</strong>.<br />
[5] Sound pressure level at a distance of 1m from the rear part.